| 2003-06-19 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03051578 |
| | ADD: 3648 TURTLE ISLAND COURT |
| | CONT: M/I HOMES INC |
| | TEL: (561)471-3440 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | PROVIDE SOILS REPORT, WITH THE MINIMUM |
| | SAFE BEARING VALUE. |
| | |
| | 3) SHEET 4 OF 6 INDICATES THE USE OF |
| | ATTIC STORAGE WITHIN THE ROOF TRUSSSES, |
| | NOTE THAT THE BOTTOM CHORD OF THE TRUSS |
| | SHALL BE DESIGNED TO BEAR A MINIMUM OF |
| | 30LBS PSF LIVE LOAD TABLE 1604.1 |
| | |
| | 4)1609.4.3 LOAD REDUCTION. |
| | WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| | MORE LOADS IN COMBINATION WITH DEAD LOAD |
| | ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| | 1609.4.1 OR 1609.4.2, THE COMBINED |
| | EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| | PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| | LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| | FROM THE LOAD COMBINATION OF THE DEAD |
| | LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| | EFFECTS. INCREAS IN ALLOWABLE STRESS SPE |
| | CIFIED IN THE MATERIALS SECTIONS OF THIS |
| | CODE OR A REFRENCED STANDARD SHALL NOT |
| | BE USED WITH THESE LOAD COMBINATIONS |
| | EXCEPT THAT A DURATION OF LOAD INCREASE |
| | SHALL BE PERMITTED IN ACCORDANCE WITH |
| | CHAPTER 23. |
| | RE-EVALUATE TRUSS ANCHOR SCHEDULE. |
| | |
| | 5) PROVIDE ENGINEERING FOR BUTT GLASS |
| | ASSEMBLIES PER 2001 FBC 2406.2. |
| | |
| | 6)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | STORM SHUTTER ANCHOR SCHEDULE VS DETAIL |
| | SHEET. CONTRACTOR NEGLECTED TO INDICATE |
| | WHAT CONNECTION TYPE WAS TO BE USED, |
| | WITHOUT THIS INFORMATION THE SPACING IS |
| | USLESS? |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |