Plan Review Details - Permit 03051563
Plan Review Stops For Permit 03051563
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-06-25 Cont ID  
Sent By hmoser Date 2003-06-18 Time 19:24 Rev Time 3.00
Received By lhatten Date 2003-06-20 Time 09:26 Sent To  
Notes
2003-06-25 00:00:00REVIEW & STAMPED PLANS 06/20/2003
 CALC. FEES & PRINT CARD 06/25/2003

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-30 Cont ID  
Sent By mmclean Date 2003-05-27 Time 16:14 Rev Time 0.50
Received By btrobaug Date 2003-05-30 Time 10:11 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-19 Cont ID  
Sent By csiegber Date 2003-09-19 Time 12:16 Rev Time 0.00
Received By csiegber Date 2003-09-19 Time 12:16 Sent To M
Notes
2003-09-19 00:00:00TO PK BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-05-21 Time 09:49 Rev Time 0.00
Received By shernand Date 2003-05-21 Time 09:49 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-09-28 Cont ID  
Sent By pkrauss Date 2003-09-28 Time 14:22 Rev Time 0.25
Received By pkrauss Date 2003-09-28 Time 14:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-18 Cont ID  
Sent By csiegber Date 2003-09-19 Time 12:16 Rev Time 0.50
Received By hmoser Date 2003-06-18 Time 18:58 Sent To B
Notes
2003-06-18 00:00:00PASS PRIVISO
 SECTION 610.1.ABC.3.5.2 2001 ENERGY CODE
 AIR HANDLERING UNITS SHALL BE ALLOWED
 IN ATTICS IF FOLLOWINGS CONDITIONS ARE
 MET.
 1) THE SERVICE PANEL OF THE EQUIPMENT IS
 LOCATED WITHIN 6FT.OF ATTIC ACCESS.
 2) A DEVICE IS INSTALLED TO ALERT OWNER
 OR SHUT UNIOT DOWN WHEN CONDENSATION
 DRAIN IS NOT WORKING PROPERLY.
 3) THE ATTIC ACCESS OPENING IS OF SUFFIC
 IENT SIZE YO REPLACE AIRHANDLER
 4) A NOTE IS POSTED ON THE ELECTRIC
 SERVICE PANEL INDICATING THE HOMEOWNER
 THAT THE AIRHANDLER IS LOCATED IN THE
 ATTIC.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-06-17 Cont ID  
Sent By btrobaug Date 2003-05-30 Time 10:36 Rev Time 0.33
Received By jleech Date 2003-06-17 Time 17:37 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-27 Cont ID  
Sent By shernand Date 2003-05-21 Time 09:49 Rev Time 1.00
Received By mmclean Date   Time   Sent To E
Notes
***NONE***