Plan Review Details - Permit 03051521
Plan Review Stops For Permit 03051521
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-16 Cont ID  
Sent By shernand Date 2003-07-16 Time 09:55 Rev Time 0.33
Received By kstevens Date 2003-07-29 Time 10:29 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-07 Time 13:01 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 13:01 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-29 Cont ID  
Sent By shernand Date 2003-05-29 Time 12:21 Rev Time 0.00
Received By shernand Date 2003-05-29 Time 12:21 Sent To P
Notes
2003-05-29 00:00:00KSTEVENS DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-20 Cont ID  
Sent By shernand Date 2003-05-20 Time 16:36 Rev Time 0.00
Received By shernand Date 2003-05-20 Time 16:36 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-07-29 Cont ID  
Sent By kstevens Date 2003-07-29 Time 10:30 Rev Time 0.33
Received By kstevens Date 2003-07-29 Time 10:30 Sent To  
Notes
2003-07-29 00:00:00PROVISO - BACKFLOW REQUIRED

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-16 Time 09:55 Rev Time 0.50
Received By kstevens Date 2003-07-07 Time 16:24 Sent To  
Notes
2003-07-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA STATUTES.
  
 1) BACKFLOW REQUIRED FOR IRRIGATION,
 2) RAIN SENSOR REQUIRED
 3) A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL DRAWINGS AND SPECIFICATION
 SHEETS. THE TITLE BLOCK MUST, AT A MINI-
 MUM CONTAIN THE FOLLOWING INFORMATION.
 A) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 B) FIRM LICENSE NUMBER
 C) NAME OR IDENTIFICATION OF PROJECT
 D) DATE PREPARED
 ***********61G1-16.004**********
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-06-20 Cont ID  
Sent By shernand Date 2003-07-07 Time 13:01 Rev Time 0.50
Received By kstevens Date 2003-06-11 Time 17:07 Sent To  
Notes
2003-06-20 00:00:00DENIED
 REFERENCE: FBC-2001 AMENDMENTS TO FBC,
 CHAPTER 1, ADMIN & AMEND.
  
 1) SECTION 104.2.1 TWO OR MORE COPIES OF
 SPECIFICATIONS AND OF DRAWING DRAWN TO
 SCALE WITH SUFFICIENT CLARITY AND DETAIL
 TO INDICATE THE NATURE AND CHARACTER OF
 THE WORK SHALL ACCOMPANY THE APPLICATION
 FOR A PERMIT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-24 Cont ID  
Sent By shernand Date 2003-05-29 Time 12:21 Rev Time 0.33
Received By kstevens Date 2003-05-24 Time 16:32 Sent To  
Notes
2003-05-24 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1, ADMIN.
 CODE, AND AMENDMENTS TO THE BLDG. CODE.
  
 1) SECTION 104.2.1 AS REQUIRED BY 104.3.
 1.1 OF THE CODE, TWO OR MORE COPIES OF
 SPECIFICATIONS, AND OF DRAWINGS DRAWN TO
 SCALE WITH SUFFICIENT CLARITY AND DETAIL
 TO INDICATE THE NATURE AND CHARACTER OF
 THE WORK, SHALL ACCOMPANY THE APPLICAT-
 ION FOR A PERMIT. ... ALL INFORMATION,
 DRAWINGS SPECS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692