| 2003-05-21 00:00:00 | ***************** UNSAT *************** |
| | |
| | PLEASE NOTE, PLANS ARE NOT COMPLETE AT |
| | THIS TIME THERE MAY BE OTHER COMMENTS. |
| | PLEASE SEE COMMENTS BELOW AND ADDRESS. |
| | |
| | 1)NOTE: PLEASE CORRELATE PLAN W/ RISER |
| | DIAGRAM. PLAN SHOWS NEW 150A PANEL, |
| | RISER SHOWS NEW 200A DISC FEEDING EXIST- |
| | ING 150A PANEL? PANEL SCHEDULE SHOWS |
| | AS 200A PANEL?? ETC |
| | |
| | 2)NOTE: RISER SHOWS A NEW 200A DISC |
| | BEING ADDED BY PLACING DOUBLE LUGS ON |
| | EXISTING METERCAN. PLEASE SHOW LOAD |
| | ON EXISTING METER, SERVICE ENTRANCE |
| | CONDUCTOR SIZE FOR NEW LOAD. PLEASE ALSO |
| | SHOW SIZE OF METERCAN? 215-5 |
| | |
| | 3)NOTE: PLEASE SEE 310-16 FOR SIZING |
| | OF NEW FEEDERS. SHOWS 1/0` FOR 200A DISC |
| | ? |
| | |
| | 4)NOTE; PLEASE SEE 250-24. AN EQUIPMENT |
| | GROUNDING CONDUCTOR IS ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISC. SHOWS |
| | FROM METER TO MAIN ALSO. |
| | |
| | 5)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH SUBMITTED PANEL |
| | SCHEDULE. |
| | PLEASE SEE 700-12E FOR EM/ EXT LTS AND |
| | CIRCUITING. |
| | |
| | 6)NOTE: PLEASE SEE THAT PLANS ARE SHOWN |
| | AS BLANK FOR NEW LIGHTING?? |
| | |
| | 7)NOTE: PLEASE CLARFIY IF BATH GFI |
| | RECEPT IS ON W/ BATH LT CIRCUIT? SHOWN |
| | AS #14, 15A? |
| | |
| | 8)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| | AT 125%. 215-3/ 230-42 ETC |
| | |
| | PLEASE SUBMIT ALL OF THE ABOVE INFORMAT- |
| | -ION FOR REVIEW. PLEASE REMOVE OLD/VOID- |
| | ED SHEETS AND INSERT NEW INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |