Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-23 Cont ID  
Sent By hpiskura Date 2003-06-23 Time 07:27 Rev Time 0.00
Received By hpiskura Date 2003-06-23 Time 07:13 Sent To  
Notes
2003-06-23 00:00:00CITY RECORDS DO NOT SHOW A PERMIT FOR
 THE AREA DEPICTED ON THE PLANS AS
 "STORAGE ABOVE".PLEASE PROVIDE
 CONSTRUCTION DETAILS FOR THE STRUCTURE,
 INCLUDING THE STAIRS, GUARD RAILS,
 HEADROOM AND DESIGN LIVE LOADS.SEE
 FBC 104.2.
  
 ALSO, THE ADDED AREA MAY BE SUBJECT TO
 IMPACT FEES COLLECTED BY THE COUNTY.
 THE PERMIT PLANS MUST BE STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.FBC 104.2.
  
 WHAT IS THE NATURE AND QUANTITY OF THE
 THINGS THAT WILL BE STORED IN THE
 STORAGE AREA?HOW WILL AN EGRESS PATH
 BE MAINTAINED?FBC 104.2.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-21 Cont ID  
Sent By dpalmer Date 2003-05-21 Time 06:41 Rev Time 0.50
Received By dpalmer Date 2003-05-21 Time 06:41 Sent To  
Notes
2003-05-21 00:00:00***************** UNSAT ***************
  
 PLEASE NOTE, PLANS ARE NOT COMPLETE AT
 THIS TIME THERE MAY BE OTHER COMMENTS.
 PLEASE SEE COMMENTS BELOW AND ADDRESS.
  
 1)NOTE: PLEASE CORRELATE PLAN W/ RISER
 DIAGRAM. PLAN SHOWS NEW 150A PANEL,
 RISER SHOWS NEW 200A DISC FEEDING EXIST-
 ING 150A PANEL? PANEL SCHEDULE SHOWS
 AS 200A PANEL?? ETC
  
 2)NOTE: RISER SHOWS A NEW 200A DISC
 BEING ADDED BY PLACING DOUBLE LUGS ON
 EXISTING METERCAN. PLEASE SHOW LOAD
 ON EXISTING METER, SERVICE ENTRANCE
 CONDUCTOR SIZE FOR NEW LOAD. PLEASE ALSO
 SHOW SIZE OF METERCAN? 215-5
  
 3)NOTE: PLEASE SEE 310-16 FOR SIZING
 OF NEW FEEDERS. SHOWS 1/0` FOR 200A DISC
 ?
  
 4)NOTE; PLEASE SEE 250-24. AN EQUIPMENT
 GROUNDING CONDUCTOR IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISC. SHOWS
 FROM METER TO MAIN ALSO.
  
 5)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULE.
 PLEASE SEE 700-12E FOR EM/ EXT LTS AND
 CIRCUITING.
  
 6)NOTE: PLEASE SEE THAT PLANS ARE SHOWN
 AS BLANK FOR NEW LIGHTING??
  
 7)NOTE: PLEASE CLARFIY IF BATH GFI
 RECEPT IS ON W/ BATH LT CIRCUIT? SHOWN
 AS #14, 15A?
  
 8)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215-3/ 230-42 ETC
  
 PLEASE SUBMIT ALL OF THE ABOVE INFORMAT-
 -ION FOR REVIEW. PLEASE REMOVE OLD/VOID-
 ED SHEETS AND INSERT NEW INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-06-13 Cont ID  
Sent By mcarsill Date 2003-06-13 Time 08:10 Rev Time 0.00
Received By mcarsill Date 2003-06-13 Time 08:10 Sent To  
Notes
2003-06-13 00:00:001) ANY TENANT SEPARATION WALLS PRESENT.
  
 2) ANY FIRE SPRINKLER OR FIRE ALARM
 EQUIPMENT PRESENT.
  
 3) INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILINGS REQUIRED.
  
 4) ELECTRICAL PLANS DO NOT DISPLAY
 EXISTING EXIT SIGNS.
  
 5) EXIT SIGN LEADS PERSONS DOWN CORRIDOR
 INTO STORAGE AREA. PLEASE EXPLAIN
 RATIONALE AND WHAT PREVENTS DOOR FROM
 BEING BLOCKED.
  
 6) WALL BETWEEN BUSINESS AND STORAGE
 RATED.
  
 7) WHAT WILL BE STORED IN STORAGE AREA.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-20 Cont ID  
Sent By shernand Date 2003-05-20 Time 16:28 Rev Time 0.00
Received By shernand Date 2003-05-20 Time 16:28 Sent To  
Notes
2003-05-20 00:00:00COMM BOARD #11

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-05-23 Cont ID  
Sent By pkrauss Date 2003-05-23 Time 11:16 Rev Time 0.40
Received By pkrauss Date 2003-05-23 Time 11:16 Sent To  
Notes
2003-05-23 00:00:00DENIED:
  
 1.PLEASE PROVIDE OUTSIDE AIR CALCS AS
 PER 2001 FBC(M) TABLE 403.3.
  
 2.PLEASE NOTE THE PROXIMITY OF THE
 OUTSIDE AIR INTAKE TO THE CONDENSING
 UNIT.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE AS PER
 2001 FBC(M) 606.2.1 & NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-14 Cont ID  
Sent By kstevens Date 2003-06-14 Time 10:19 Rev Time 1.00
Received By kstevens Date 2003-06-14 Time 10:12 Sent To  
Notes
2003-06-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 ADMIN. CODE, CHAPTER
 1 AND AMENDMENTS
  
 1) SUBMIT A SANITARY RISER DIAGRAM AND A
 WATER RISER DIAGRAM. SEC 104.2.1
 2) PROVIDE DETAIL FOR HDCP TOILET ROOM
 PER SEC 11-4.22
 3) INDICATE WIDTH OF TOILET ROOM FOR THE
 SECTION AT THE WATER CLOSET AND LAV.
 MINIMUM OPENING FOR W/C AND LAV SHALL BE
 5'3". SEC 405.3.1
 SHOW CLEAR FLOOR SPACE FOR W/C AND LAV.
 4) TABLE 403.1 REQUIRES A DRINKING
 FOUNTAIN. (ALSO SEE SEC 410.1)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692