Plan Review Details - Permit 03051469
Plan Review Stops For Permit 03051469
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-06-06 Cont ID  
Sent By jwitmer Date 2003-06-06 Time 11:19 Rev Time 0.50
Received By jwitmer Date 2003-06-06 Time 11:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-03 Cont ID  
Sent By jwitmer Date 2003-06-03 Time 16:13 Rev Time 1.11
Received By jwitmer Date 2003-06-03 Time 15:56 Sent To  
Notes
2003-06-03 00:00:00BUILDING PLAN REVIEW
 PERMIT:03051469
 ADD: 901 S FLAGLER
 CONT: KEVIN ADAIR
 TEL: (561)714-5259
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 DOOR INTO SPACE 1282 DOES NOT MEET
 THE MANEUVERING CLEARENCES ON EITHER THE
 PUSH OR PULL SIDE.
  
 2) DORS INTO SPACES 1279 & 1280 LOOK AS
 TO HAVE SIDE LIGHTS, 2405.2 HAZARDOUS
 LOCATION, SAFETY GLASS REQUIRED.
  
 3)ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)805-6715

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-08-22 Cont ID  
Sent By dpalmer Date 2003-08-22 Time 10:39 Rev Time 0.50
Received By dpalmer Date 2003-08-22 Time 10:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-21 Cont ID  
Sent By dpalmer Date 2003-05-21 Time 06:34 Rev Time 0.25
Received By dpalmer Date 2003-05-21 Time 06:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-19 Cont ID  
Sent By dpalmer Date 2003-05-19 Time 18:15 Rev Time 0.33
Received By dpalmer Date 2003-05-19 Time 18:15 Sent To  
Notes
2003-05-19 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SUBMIT PLAN THAT IS CLEAR
 ON WORK TO BE DONE. PLANS SHOW MORE
 ELECTRICAL WORK THAN WHAT IS MENTIONED
 ON PERMIT APPLICATION AND BY VALUE FOR
 SCOPE OF WORK. 104.2.1 ADMIN CODE
 104.6.5 FOR BLDG VALUATION. ADMIN CODE
  
 PLAN REVIEW CAN NOT BE COMPLETED AT THIS
 TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-06-02 Cont ID  
Sent By nmccray Date 2003-06-02 Time 13:00 Rev Time 0.00
Received By nmccray Date 2003-06-02 Time 13:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-06 Cont ID  
Sent By shernand Date 2003-06-02 Time 08:39 Rev Time 0.00
Received By jwitmer Date 2003-06-02 Time 08:38 Sent To  
Notes
2003-06-02 00:00:00COMM BOARD #21

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-06-02 Cont ID  
Sent By shernand Date 2003-06-02 Time 08:39 Rev Time 0.00
Received By shernand Date   Time   Sent To  
Notes
***NONE***