| 2003-06-12 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE PROPOSED ALTERATIONS MAY REQUIRE |
| | PAYMENT OF IMPACT FEES.THE PROPOSALS |
| | SHOULD BE ASSESSED BY PALM BEACH COUNTY, |
| | THE PLANS STAMPED BY THEM AND A COPY OF |
| | THE RECEIPT SUBMITTED TO THE CITY OF |
| | WEST PALM BEACH CONSTRUCTION SERVICES |
| | DEPARTMENT BEFORE A BUILDING PERMIT CAN |
| | BE ISSUED. |
| | |
| | 3) FBC 1606.1.7SHEET S2, STRUCTURAL |
| | NOTES, CODES AND STANDARDS #1.IN |
| | ADDITION TO THE INFORMATION PROVIDED, |
| | THE PLANS SHALL ALSO STATE THE DESIGN |
| | WIND PRESSURES FOR SPECIFICATION OF THE |
| | ROOF COVERINGS AND NEW FRENCH DOOR. |
| | |
| | 4) ROOF COVERING.THE SUBMITTAL OF A |
| | PRODUCT APPROVAL IS NOTED.THE PLANS |
| | DO NOT STATE WHAT TYPE OF ROOF COVERING |
| | IS TO BE PROVIDED.AMEND THE PLANS TO |
| | SPECIFY THE TYPE OF ROOF SYSTEM/MATERIAL |
| | OVER THE NEW FRONT PORCH AND THE |
| | EXISTING REAR PORCH (FOLLOWING REMOVAL |
| | THE SECOND FLOOR 'BONUS ROOM') |
| | |
| | 5) FBC 1005.4.1REMOVAL OF EXISTING |
| | EXTERIOR DOOR.ANNOTATE THE BEDROOMS ON |
| | THE PLAN.IS THE EXTERIOR DOOR BEING |
| | REMOVED FROM A BEDROOM, AND IF SO DO THE |
| | REMAINING WINDOWS COMPLY WITH THE |
| | REQUIREMENTS FOR EMERGENCY EGRESS |
| | OPENINGS?ANNOTATE THE PLANS |
| | ACCORDINGLY. |
| | |
| | 6) FBC 2304.2.5SHEET S3, SOUTH |
| | ELEVATION, PATCHING OF WOOD SIDING AFTER |
| | REMOVAL OF THE EXISTING EXTERIOR DOOR. |
| | THE WOOD SIDING SHALL BE AT LEAST 6" |
| | CLEAR OF THE GROUND. |
| | |
| | 7) THE PLANS SHALL STATE THE DIMENSIONS |
| | (AS "NOT TO EXCEED.." IF NECESSARY) FOR |
| | THE NEW FRONT PORCH.WHAT IS THE |
| | SPACING OF THE COLUMNS?FROM THE |
| | SIMPSON CATALOGUE, THE ABA44 COLUMN BASE |
| | ANCHORS MAY HAVE INSUFFICIENT UPLIFT |
| | CAPACITY.CHECK AFTER ESTABLISHING THE |
| | PORCH DIMENSIONS. |
| | |
| | 8) FBC 1804.1.3 AND FBC 1606.1.3 |
| | SHEETS S2, PORCH SECTION.THE DOWELLED |
| | EXTENSION TO THE EXISTING PORCH SLAB IS |
| | SHOWN TO BE SUPPORTING THE NEW PORCH |
| | COLUMNS.THE COLUMNS SHALL BE |
| | ANCHORED TO A FOUNDATION CAPABLE OF |
| | RESISTING WIND-INDUCED UPLIFT.ALSO THE |
| | BOTTOM OF FOUNDATIONS SHALL EXTEND NO |
| | LESS THAN 12" BELOW FINISHED GRADE. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |