Plan Review Details - Permit 03051279
Plan Review Stops For Permit 03051279
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-08-07 Cont ID  
Sent By pkrauss Date 2003-08-09 Time 09:08 Rev Time 1.00
Received By lsmith Date 2003-08-07 Time 08:07 Sent To  
Notes
2003-08-07 00:00:00***************PROVISO*****************
  
 1. SEPARATE PERMITS REQUIRED FOR MECH,
 PLUMB & ROOF.NOT SIGNED ON PERMIT AT
 TIME OF APPLICATION.
  
 2. DESIGN PRESSURES TO BE SUBMITTED FOR
 ALL OPENINGS.
  
 3. UPLIFT ADJUSTMENTS TO BE SUBMITTED BY
 FLORIDA REGISTERED ENGINEER.
  
 4. ALL WINDOWS & GLASS DOORS ARE IMPACT
 NO HURRICANE PANELS REQUIRED.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-07-14 Cont ID  
Sent By kstevens Date 2003-08-06 Time 11:12 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2003-07-14 00:00:00****************FAILED***************
  
 THE FOLLOWING ITEMS ARE STILL NOT
 COMPLETED FOR BUILDING APPROVAL:
 1. PRODUCT APPROVALS EXTERIOR DOORS
 2. PRODUCT APPROVALS WINDOWS.
 (NOTE ONLY FIXED GLASS WINDOWS
 SUBMITTED.)
 3.STORM PANELS WITH SCHEDULE FOR
 INSTALLATION.
 4. A NOTICE OF COMMENCEMENT MUST BE
 FILED BEFORE A PERMIT CAN BE ISSUED.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-09 Cont ID  
Sent By kstevens Date 2003-07-11 Time 18:24 Rev Time 0.00
Received By lsmith Date 2003-05-30 Time 15:13 Sent To  
Notes
2003-05-30 00:00:00****************FAILED*************
  
 1. THE FOLLOWING PRODUCT APPROVALS MUST
 BE SUBMITTED: DADE COUNTY OR SBCCI:
 1. ROOF MATERIALS
 2. WINDOWS & DOORS
  
 2.PROVIDE ENERGY CALCULATIONS
 AS REQUIRED BY THE 2001 FLORIDA
 ENERGY EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
 SEE FBC CHAPTER 13-101.2.2.
  
 3. ALL WINDOWS/DOORS MUST MEET THE FBC
 FOR IMPACT.IF HURRICANE PANELS ARE
 REQUIRED PRODUCT APPROVALS MUST BE
 SUBMITTED SHOWING TYPEOF PANELS AND
 INSTALLATION SCHEDULE WITH TYPE OF
 ANCHORS.
  
 4. PER SHEET A-8 NOTES: UPLIFTS
 ADJUSTMENTS TO BE SUBMITTED SIGNED &
 SEALED BY FLORIDA REGISTERED ENGINEER.
  
 5. SEPARATE PERMITS REQUIRED FOR
 PLUMBING & MECHANICAL & ROOFING.
  
 6. A NOTICE OF COMMENCEMENT MUST BE FILE
 BEFORE A PERMIT CAN BE ISSUED.
  
 7. BEFORE A PERMIT TO CONSTRUCT MAY
 BE ISSUED IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2004-06-21 Cont ID  
Sent By jleahy Date 2004-06-21 Time 08:53 Rev Time 0.45
Received By jleahy Date 2004-06-21 Time 08:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-05-05 Cont ID  
Sent By mjacobs Date 2004-06-16 Time 15:22 Rev Time 0.50
Received By dpalmer Date 2004-05-05 Time 06:51 Sent To  
Notes
2004-05-05 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004,
 FS 481.219. PLEASE PROVIDE ALL LICENSE
 #'S ON TITLE BLOCK AS REQ'D PER ABOVE.
 PLEASE SEE TITLE BLOCK IS MISSING
 CA# AS REQ'D UNDER FS.
  
 2)NOTE: PLEASE PROVIDE LAYOUT OF EXIST-
 -ING DWELLING'S ELECTRICAL DEVICES.
 ALL ELECTRICAL IN EXSITING DWELLING
 MUST MEET CODE FOR DEVICES/WIRING TO
 2002 NEC PER FBC CHAPTER 34. 3401.7.1
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-04-09 Cont ID  
Sent By csiegber Date 2004-04-29 Time 16:50 Rev Time 0.33
Received By btrobaug Date 2004-04-09 Time 12:00 Sent To  
Notes
2004-04-09 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE: PLEASE NOTE, ALL PLANS DRAWN
 BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK: MUST BE SIGNED,
 DATED AND SEALED BY THAT ARCH/ENG.
 PER FS 481.221 471.025
 FAC 61G15-23.002, 61G1-16.004
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-07-25 Cont ID  
Sent By csiegber Date 2004-04-05 Time 14:05 Rev Time 0.50
Received By btrobaug Date 2003-07-25 Time 15:11 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-07-10 Cont ID  
Sent By alange Date 2003-07-24 Time 15:50 Rev Time 0.50
Received By btrobaug Date 2003-07-10 Time 10:30 Sent To P
Notes
2003-07-10 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE: PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 THE RISER DIAGRAM LISTS THE "NEW PANEL"
 AS 125 A MLO,THE PANEL SCHEDULE LIST
 SAME AS 100 AMP MAIN BREAKER,PLEASE
 CLARIFY.
  
 THE PANEL SHOWS THE W.HEATER AT 20 AMPS
 AND THE DRYER @ 20 AMPS,BUT THE LOAD
 CALCULATIONS LIST THEM AS 4500 WATTS
 AND 5000 WATTS RESPECTIVELY,PLEASE
 CORRELATE
  
 PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG,AND SHALL HAVE NO
 OTHER OUTLETS.
  
 PLEASE MAKE THE CORRECTIONS AND RESUBMIT
 FOR REVIEW.IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-22 Cont ID  
Sent By shernand Date 2003-07-02 Time 11:29 Rev Time 0.50
Received By btrobaug Date 2003-05-22 Time 12:20 Sent To P
Notes
2003-05-22 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING AND
 RESUBMIT FOR REVIEW.
  
 1} PLEASE PROVIDE LOAD CALCULATIONS AND
 RISER DIAGRAM OF THE EXISTING LOADS AND
 ALL ADDED LOADS,PER 215-5 NEC.INDICATE
 HOW SUB PANEL IS BEING FED.
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-06-16 Cont ID  
Sent By mjacobs Date 2004-06-16 Time 15:22 Rev Time 0.00
Received By mjacobs Date 2004-06-16 Time 15:21 Sent To E
Notes
2004-06-16 00:00:00SENT TO BT DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-04-29 Cont ID  
Sent By csiegber Date 2004-04-29 Time 16:50 Rev Time 0.00
Received By csiegber Date 2004-04-29 Time 16:50 Sent To E
Notes
2004-04-29 00:00:00TO DP DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-04-05 Cont ID  
Sent By csiegber Date 2004-04-05 Time 14:05 Rev Time 0.00
Received By csiegber Date 2004-04-05 Time 14:05 Sent To E
Notes
2004-04-05 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-24 Cont ID  
Sent By alange Date 2003-07-24 Time 15:50 Rev Time 0.00
Received By alange Date 2003-07-24 Time 15:50 Sent To E
Notes
2003-07-24 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-02 Cont ID  
Sent By shernand Date 2003-07-02 Time 11:29 Rev Time 0.00
Received By shernand Date 2003-07-02 Time 11:29 Sent To E
Notes
2003-07-02 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-05-21 Time 16:41 Rev Time 0.00
Received By shernand Date 2003-05-21 Time 16:41 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-16 Cont ID  
Sent By shernand Date 2003-05-16 Time 11:57 Rev Time 0.00
Received By shernand Date 2003-05-16 Time 11:57 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-08-09 Cont ID  
Sent By pkrauss Date 2003-08-09 Time 09:08 Rev Time 0.20
Received By pkrauss Date 2003-08-09 Time 09:08 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-05-27 Cont ID  
Sent By kstevens Date 2003-05-24 Time 10:57 Rev Time 0.25
Received By pkrauss Date 2003-05-27 Time 09:57 Sent To B
Notes
2003-05-27 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 PLEASE PROVIDE ENERGY & MANUAL J CALCS
 WITH MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-08-06 Cont ID  
Sent By kstevens Date 2003-08-06 Time 11:04 Rev Time 1.50
Received By kstevens Date 2003-08-06 Time 11:04 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-07-11 Cont ID  
Sent By btrobaug Date 2003-07-25 Time 15:52 Rev Time 0.33
Received By kstevens Date 2003-07-11 Time 18:14 Sent To B
Notes
2003-07-11 00:00:00DENIED
 REFERENCE: FLORIDA STATUTES
  
 1) SHT A-9 ALL PLANS DRAWN BY AN ARCHIT-
 ECT SHALL BE SIGNED, SEALED AND DATED.
 NO SEAL ON SHEET #9. 61G1-16.003
 2) FROM PREVIOUS REVIEW COMMENT NOT
 ADDRESSED.
 D) FLA STATUTES 61G1-16.004 MINIMUM
 INFORMATION REQUIRED, FIRM LICENSE NUM-
 BER REQUIRED ON EACH SHEET.
 3) WHEN RESUBMITTING PLANS, REMOVE AND
 REPLACE ANY PAGES AS NECESSARY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-24 Cont ID  
Sent By btrobaug Date 2003-07-10 Time 11:09 Rev Time 0.50
Received By kstevens Date 2003-05-24 Time 10:29 Sent To M
Notes
2003-05-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS.
 A) SECTION 909.1 ONLY FIXTURES OF THE
 BATHROOM GROUP SHALL DRAIN INTO THE WET
 VENT FOR THE BATHROOM. - TIE LAUNDRY
 SINK DOWNSTREAM OF BATHROOM FIXTURES.
 B) MINIMUM SIZE PIPE FOR WASHMACHINE IS
 2". TABLE 709.1 - CLEANOUT REQUIRED MIN.
 4' ABOVE FINISHED FLOOR AT W/MACHINE.
 C) MINIMUM SIZE TRAP FOR LAUNDRY SINK IS
 1-1/2" PER TABLE 709.1.
 ---SEE RED LINE CORRECTIONS ON PLANS AND
 MAKE CORRECTONS TO PLANS AND RESUBMIT.
 D) FLA. STATUTES 61G1-16.004 MINIMUM
 INFORMATION REQUIRED, FIRM LICENSE NUM-
 BER REQUIRED ON EACH SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-05-16 Time 11:57 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-05-21 00:00:00DENIED, NEED SURVEY