Plan Review Details - Permit 03051238
Plan Review Stops For Permit 03051238
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-11-22 Cont ID  
Sent By jwitmer Date 2004-11-22 Time 08:15 Rev Time 0.25
Received By jwitmer Date 2004-11-22 Time 08:15 Sent To  
Notes
2004-11-22 00:00:0011-22-04 SUBMITTALS, PRODUCT APPROVALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-10-06 Cont ID  
Sent By csiegber Date 2004-02-18 Time 10:46 Rev Time 8.00
Received By jwitmer Date 2003-10-06 Time 16:00 Sent To  
Notes
2003-10-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03051238
 ADD: 750 EXECUTIVE CENTER DR W
 CONT: EXECUTIVE TRUST, LTD
 TEL: (561)547-0207
 (561)547-5512
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 3RD REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PROVIDE A RECORDED PLAT, PLEASE PRO-
 VIDE US IN WRITING WHICH OF THE
 PROPOSEDSTREET NAMES YOUR FIRM WILL BE
 USING.
 A) MALIBU BAY COURT
 B) MALIBU BAY DRIVE
  
 3) FAIR HOUSING, THE PLAN FROM URBAN
 DESIGN STUDIOS DOES NOT INDICATE WHERE
 THE ACCESSIBLE ROUTE FROM THE PUBLIC
 WAYIS, NOR DO WE INDICATE CURB CUTS ON
 THE PLAN. OTHER AREAS IN QUESTION ARE
 THE
 DUMPSTERS AND THE RECYCLING CENTER NEXT
 TO DUMPSTER NO WALKWAY. DETECTABLE
 WARN-INGS ON WALKING SURFACES. APPENDIX
 A4.3.11.3 STAIRWAY WIDTHS 48" WIDE EXIT
 STAIRWAY IS NEEDED TO ALLOW ASSISTED
 EVACUATION.
  
 4) SITE AMENITIES UNDERSTOOD THAT THE
 SITE AMENITIES WILL BE UNDER SEPERATE
 PERMIT AND SEPERATE REVIEW.
  
 5) THE ONLY PRODUCT TESTING REPORT SUB-
 MITTED IS THE OVERHEAD DOOR FOR THE
 CLUBHOUSE. THE LETTER FROM HOUSING
 TRUSTGROUP INDICATES THAT THE REMAINDER
 OF
 THE PRODUCT REPORTS WAS TO BE SUBMITTED
 SEPTEMBER 30. NO SUCH REPORTS WERE
 RECEIVED NOR WAS THE INFORMATION FOR
 STORM SHUTTERS OR HURRICANE
 PREPAREDNESSPLAN. SEPERATE PERMITS WITH
 ASSOCIATED
 REVEIWS AND FEES WILL BE REQUIRED!!!!!!
  
 6) 105.3.6 ADMINISTRATION CODE,
 SPECIAL INSPECTOR, RESIDENT INSPECTOR
 PROGRAM, WILL BE REQUIRED TO REGISTER
 WITH DON NEELY 805-6665.
  
 7) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITEY KNOWN, OR IS IN
 QUESTIONTHE BUILDING OFFICIAL MAY
 REQUIRE EXPLORATIONS, TEST OR OTHER
 ADEQUATE PROOF AS TO THE PERMISSIBLE
 SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 SUBMITTED WAS A SINGLE COPY OF A REPORT,
 SUBMIT 3 SIGNED/SEALED REPORTS.
  
 8) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
 PROVIDE WORST CASE SENERIO FOR EACH UNIT
 AND CLUBHOUSE.
  
 9) STATE STAUTE 553.895(2) MULTIFAMILY
 RESIDENTIAL BUILDINGS 3 STORIES OR
 GREATER REQUIRE FIRE SPRINKLER PLANS
 TO BE SUBMITTED AS PART OF THE PERMIT
 READY PACKAGE. SEPERATE PLANS WILL ALSO
 BE REQUIRED FOR THE FIRE SPRINKLER
 PERMIT!!!!
  
 10)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 *************CLUBHOUSE****************
  
 11)2504.2.2 INSTALLATION OF EXTERIOR
 LATHING AND FRAMING SHALL COMPLY WITH
 ASTM C-1063.HI RIB LATH TO BE NAILED @
 4" O.C. W/ 2" ROOFING NAILS OR STAPLES.
 SHEET AM-4.
  
 12)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
 USP HTD19- 2560 UPLIFT.
  
 NOTE TRUSSES ARE TO BE DESIGNED WITH
 10 LBS. LIVE LOAD!!!!!
  
 13) BREEZEWAYS: PLANS INDICATE A 2 HR.
 WALL BUT ONLY A 1HR "C" LABEL DOOR.
 705.1.3.4 REQUIRES A 1 1/2HR "B" LABEL
 DOOR, AVERAGE TEMPERATURE RISE DEVELOPED
 ON THE UNEXPOSED SIDE SHALL NOT EXCEED
 450 DEGREES AT THE END OF 30 MIN OF
 STANDARD FIRE TEST EXPOSURE.
  
 14) PLANS EITHER NOT SEALED OR MISSING
 PAGES:
 SET# 1 REVIEW SET
 COMPLETE BUT UNSEALED SHEETS
 SET# 2 ED-1 IS OLD
 SET# 3 ED-1 IS OLD
 MISSING COVER
 MISSING S-T2.1
 S-T2.2
 SA.1
 SA.2
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-09-23 Cont ID  
Sent By csiegber Date 2003-09-30 Time 16:30 Rev Time 6.50
Received By jwitmer Date 2003-09-23 Time 12:33 Sent To  
Notes
2003-09-23 00:00:00BUILDING PLAN REVIEW
 PERMIT:03051238
 ADD:750 EXECUTIVE CENTER DRIVE WEST
 CONT:EXECUTIVE TRUST, LTD
 TEL: (561)547-0270
 (561)547-5512
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)PROVIDE A RECORDED PLAT, AND SITE PLAN
 WITH THE APPROVED STREET NAMES. INDICATE
 ALL SITE AMENITIES.
 WE RECEIVED A SITE PLAN AS OF 9/22/03
  
 I HAD E-MAILED THE COUNTY WITH THE PRO-
 POSED STREET NAMES THAT WAS SUBMITTED
 LAST 11/25/02.
 THE COUNTY WILL RESERVE EITHER OF THE
 FOLLOWING STREET NAMES ONCE YOUR FIRM
 NOTIFIES ME IN WRITING YOUR CHOICE OF
 PROPOSED STREET NAMES.
 A) MALIBU BAY COURT
 B) MALIBU BAY DRIVE
  
 3) FAIR HOUSING: PROVIDE THE SITE PLAN
 THAT CONFORMS TO THE FAIR HOUSING
 GUIDELINES FOR MULTIFAMILY HOUSING. IN-D
 ICATE AN ACCESSIBLE ROUTE TO ALL BUILD-
 INGS AND AMENITIES ASA WELL AS PUBLIC
 TRANSPORTATION, ETC LEASING OFFICE RE-
 QUIRES HANDICAPPED PARKING.
 YOUR COMMENT IS TO REFER TO THE CIVIL
 PLANS WHICH HAVE NOT BEEN SUBMITTED???
  
 4) IT IS UNDERSTOOD THAT THE SITE AMENIT
 IES PACKAGE WILL BE PERMITTED LATTER.
  
 5) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) THE OVERHEAD GARAGE DOOR.
  
  
 PLEASE INDICATE ON THE PLANS THAT ONLY
 THE FIRST FLOOR CAN BE NON-IMPACT GLAZ-
 ING AS REQUIRED BY CITY'S IMPLEMENTA-
 TION STANDARD FOR HURRICANE MISSLE
 IMPACT PROTECTION.103.6,1606.1.4 AND
 1707.4.
  
 IT IS UNDERSTOOD THAT YOU WISH TO MAKE
 APPLICATION FOR STORM SHUTTERS PERMIT AT
 A LATER DATE.
 REQUIRED IN THE STORM SHUTTER PACK-
 AGE WILL BE:
 PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 ITEM #13 OF STANDARD A PRE-STORM PREPA
 RATION PLAN MUST BE SUBMITTED TO THE
 BUILDING OFFICIAL.ANY SUCH PLAN SHALL
 INCLUDE, AT A MINIMUM, ON-SITE LOCATION
 OF SCHUTTERS, PARTY RESPONSIBLE FOR SE-
 CURING THE SHUTTERS, (SAID PARTY MUST BE
 LOCATED WITHIN PALM BEACH COUNTY), TOTAL
 NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL
 OPENINGS.PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN 12 HRS OR LESS OF
 THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH. BASED UPON THIS CODE PROVISION,
 ACCEPTANCE OF ALTERNATE MATERIALS AND ME
 THODS MAY BE APPROVED ON A CASE -BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT
 EVIDENCE OR PROOF TO SUBSTANIATE ANY
 CLAIM REGARDING THE ALTERNATE.
  
 6) 105.3(6) ADMINISTRATIVE CODE,
 SPECIAL INSPECTOR, RESIDENT INSPECTOR
 PROGRAM, WILL BE REQUIRED TO REGISTER
 WITH THE OUTSIDE INSPECTOR COORDINATOR
 DON NEELY 805-6665.
  
 7) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL I
 S NOT DEFINITEY KNOWN, OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL P
 ROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 8) STATE STATUTE 553.895(2) MULTIFAMILY
 RESIDENTIAL BUILDINGS 3 STORIES OR GREAT
 ER REQUIRE FIRE SPRINKLER PLAN TO BE SUB
 MITTED AS PART OF THE PERMIT READY
 PACKAGE. SEPERATE PLANS WILL ALSO BE RE-
 QUIRED FOR THE FIRE SPRINKLER PERMIT!!!!
  
 9)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 *******CLUBHOUSE*********
  
 10) AM-4 MAILBOX DETAIL, 2X4 WOOD FRAM-
 ING DETAIL, FRAMING C/C? MISSING NEW
 AM-4.
  
 11) AM-4 MISSING SHEET AND DETAIL FOR
 HI-RIB LATH.
  
 12) CLUBHOUSE MISSING NEW AM-7 WITH
 TRUSS ANCHOR SCHEDULE.
 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 12) MISSING NEW SHEET AM-8 DETAIL 8 & 13
 2X4 BLOCKING DRAWN IN THE CMU, NOT AT-
 TACHED TO THE CMU.
  
 ***APARTMENT BUILDING COMMENTS********
  
 13) 9-24-03 DELETE COMMENT# 13.
  
 14) S-D1/ S-D5 INDICATES THE SLAB AND FO
 UNDATION AS 12" VERTICALLY.
 1804.1.3 THE BOTTOM OF THE FOUNDA-
 TION SHALL EXTEND NO LESS THAN 12"
 BELOW FINISH GRADE.
 1804.1.7 W.P.B. AMENDMENTS REQUIRE
 A MINIMUM OF 4" SLAB ABOVE GRADE. WITH
 THE FOUNDATION A TOTAL OF 16" MINIMUM
 VERTICAL MEASUREMENT FOR FOUNDATIONS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-07 Cont ID  
Sent By csiegber Date 2003-09-22 Time 16:37 Rev Time 16.50
Received By jwitmer Date 2003-06-07 Time 15:25 Sent To  
Notes
2003-06-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03051238
 ADD:750 WEST EXECUTIVE CENTER DRIVE
 CONT:PLAN REVIEW
 CONTACT: EXECUTIVE TRUST, LTD
 TEL: (561)547-0270
 (561)547-5512
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 GENERAL SITE COMMENTS:
  
 NOTE: PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 PROVIDE PROOF OF OWNERSHIP. THE P. B. C.
 COUNTY PROPERTY APPRAISERS OFFICE
 INDICATES DIFFERENT OWNERSHIP.
  
 2) PROVIDE RECORDED PLAT, AND SITE PLAN
 WITH THE APPROVED STREET NAMES,
 INDICATEALL SITE AMENITIES.
  
 3) FAIR HOUSING: PROVIDE THE SITE PLAN
 THAT CONFIRMS TO THE FAIR HOUSING
 GUIDELINES FOR MULTI HOUSING. AN
 ACCESSIBLE ROUTE TO ALL BUILDINGS,
 AMENITIES,
 ED PUBLIC TRANSPORTATION ETC.LEASING
 OFFICE REQUIRES HANDICAPPED PARKING.
  
 4) MISSING SITE AMENITIES PACKAGE!
 A) GAZEBO
 B) TRASH COMPACTOR
 C) ENTRY GATES OR GUARDHOUSE
 D) SIGNAGE AND IF WALLS OF FENCE
 AROUND THE PROPERTY
 E) INFORMATION FOR FOUNTAIN IN LAKE
 WHERE THE ELECTRIC WILL BE PULLED
 FROM ETC...SRPERATE PERMIT REQUIRED
  
 5) POOL "EFFECTIVE BARRIER" SEE ZONING
 REQUIREMENTS AS WELL AS 424.1 PUBLIC
 SWIMMING POOLS 64E-9.002 EFFECTIVE
 BARRIERS: SEPERATING THE POOL FROM ALL
 OTHER AREAS INCLUDING THE INTERIOR OF
 THE
 CLUBHOUSE AND POOL AREA.
  
 GENERAL INFORMATION:REQUIRED 1606.1.4
  
 5)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR
 PROTECTEDWITH AN IMPACT RESISTANT
 COVERING MEET- ING THE REQUIREMENTS OF
 SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30
 FTOF GRADE SHALL MEET THE REQUIREMENTS
 OF LARGE MISSLE TEST.
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) WINDOWS, SINGLE HUNG, CASEMENT,
 FIXED OR HORIZONTAL ROLLER
 B) DOORS, GLAZED AND SOLID DOORS
 OR SLIDING DOORS OR OVERHEAD
 C) STORM SHUTTERS A COPY OF THE CITYS
 IMPLEMENTSTION STANDARD FOR HURRI-
 CANE MISSLE IMPACT PROTECTION WILL
 PROVIDED EXPLAINING THE STANDARD
 FOR LARGE PROJECTS AND A SAMPLE
 ATTACHMENT SCHEDULE.
 D) ROOF ASSEMBLIES PRODUCT TESTING
 REPORT.
  
 7)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 8)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 9)1707.4.5.2 MULLIONS SHALL BE
 DESIGN-ED TO TRANSFER THE DESIGN
 PRESSURE LOADSAPPLIED BY THE WINDOW OR
 DOOR ASSEMBLIESTO THE ROUGH OPENING
 SUBTRATE.
  
 10)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE
 USEDFOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 11)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE
 INSTALLATIONSCHEDULE SUMMARIZING &
 IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL
 PRES-SURE ZONES, SLAT TYPES, ETC.,
 SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 12) ROOF ASSEMBLIES: 1504.1 WIND RESIS-
 TANCE OF ROOFS: ROOF DECKS AND ROOF
 COV-ERINGS SHALL BE DESIGNED FOR WIND
 LOADS IN ACCORDANCE WITH CHAPTER 16.
 PROVIDE
 PRODUCT TESTING REPORTS.
  
 13) 105.3(6) ADMINISTRATIVE CODE,
 SPECIAL INSPECTOR (RESIDENT INSPECTOR
 PROGRAM) REGISTER WITH OUTSIDE INSPEC-
 TION COORDINATOR DON NEELY 805-6665.
  
 14)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 SUPPLY SIGNED/ SEALED SOILS REPORT FROM
 ARDAMANFILE # 02/2199 10/31,2002,
 REQUIRING 3,000 PSF
  
 15) STATE STATUTE 553.895(2) MULTI-FAM-
 ILY RESIDENTIAL BUILDINGS WHETHER DESIGN
 ATED AS TOWNHOUSE,CONDOMINIMUMS, APART-
 MENT HOUSES, TENEMENTS,GARDEN APARTMENTS
 OR BY ANY OTHER NAME ARE TO BE FIRE
 SPRINKLERED. MISSING PLANS.903.8.2
  
 16)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 ********CLUBHOUSE*******
  
 17) SHEET AM-2, WOMENS RESTROOM HANDI-
 CAPPED STALL REQUIRES 18" PULL SIDE OF
 LATCH.
  
 18) AM-1 ROOF SHEATHING REQUIREMENTS:
 W.P.B. CITY AMENDMENTS TABLE 2306.1
 ROOF COVERING 1509: INSULATION, CORRECT
  
 19) AM-4 MAILBOXES, REACH RANGES,
 FAIR HOUSING, ANSI A117.1
 308.2.1 FORWARD REACH RANGES UNOBSTRUCT-
 ED 15"/48"
 308.3.1 SIDE REACH RANGES UNOBSTRUCTED
 15"/48"
  
 20) AM-4 MAIL BOX DETAIL, 2X4 WOOD FRAME
 WALL DETAIL, FRAMING C/C?
  
 21) AM-4 MAIL BOX DETAIL HI-RIB LATH
 CEILING ATTACHMENT/ SPACING? SEE ASTM
 C-1063.
  
 22)AM-2, AM-5 WINDOW SCHEDULE, LEASING
 OFFICE, CLOSING OFFICE, UNIT# 6 FIXED
 WINDOWS SEE 2405.2.1(3) GLAZING IN HAZ-
 ARDOUS LOCATIONS.
  
 23) CHECK WALL PRESSURES, WINDOW #3,
 INTERIOR & END ZONES, OVERHEAD DOOR?
  
 24) 13-400.1 ENERGY CODE SEE AM-7 CLUB-
 HOUSE DETAIL # 2. EXTERIOR BLOCK WALL,
 MEET THE MINIMUM INSULATION REQUIREMENTS
 FOR EXTERIOR BLOCK WALL "R-7" GENERAL
 BUILDINGS < 5,000 SQ FT (PRESCRIPTIVE
 REQUIREMENT)
  
 25) AM-7 CLUBHOUSE TRUSS ANCHOR SCHEDULE
 INDICATES USE OF NU-VUE PRODUCTS WITH
 LISTED LOADS, NOTE ON RIGHT SIDE OF PAGE
 INDICATES USE OF USP PRODUCTS OR EQUAL,
 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
 IF OTHER PRODUCTS ARE USED, LIST THEIR
 LOAD CARRYING CAPACITY.
  
 26) AM-8 DETAILS 8 & 13, 2X4 BLOCKING
 DRAWN IN BLOCK, NOT ATTACHED TO THE CMU.
  
 ****APPARTMENT BUILDING COMMENTS*****
  
 27) 1014.1.1 STAIRS DO NOT MEET THE
 REQUIREMENT OF AN OPEN STAIRWAY. AT
 LEAST 50% OF THE BALCONY, PORCH,GALLERY
 OR SIMILAR SPACE SHALL BE OPEN ON THE
 LONG SIDE.
 THE EXCEPTION TAKEN FOR ARRANGEMENT
 & NUMBER OF EXITS 1004.1.4(3) WHEN YOU
 READ THE CODE ARTICLE THIS DEALS WITH
 SMOKE ISSUES IN A ENCLOSED EXIT ACCESS
 CORRIDOR. NOTE THE CODE ARTICLE DOES NOT
 DESCRIBE CONDITIONS DESCIBED UNDER
 1006.2 DEALING WITH EXTERIOR EXITWAY
 STAIRS.
 TWO ISSUES NEED TO BE ADDRESSED:
 A) 1004.1.4 IF THIS IS GOING TO BE CONS
 IDERED AN INTERIOR STIARWAY WITH THE
 EXCEPTION TAKEN IN 1004.1.4(3) VS 1/2
 THE DIAGONAL. IF 1004.1.4(2) THIS EXCEP-
 TION IS TAKEN, THEN 903.2 KICKS IN.
 AUTOMATIC SPRINKLER SYSTEMS INSTALLED IN
 LIEU OF OR, AS AN ALTERNATE TO OTHER
 REQUIREMENTS, AS PERMITTED BY THIS CODE
 SHALL BE CONSIDERED REQUIRED SYSTEMS AND
 SHALL COMPLY WITH NFPA 13 NOT 13R.
 B) THE SECOND ISSUE WILL BE THE OPEN
 STAIRWAY VS CLOSED.IF THE OWNERS APPLIES
 FOR A VARIANCE FOR THIS TO BE CONSIDERED
 A OPEN STAIRWAY:
 THE ISSUE OF 1/2 THE DIAGONAL VS 1/3 THE
 DIAGONAL WILL ALSO REQUIRE A NFPA 13
 SYSTEM. 1006.2.4 WILL ALSO BE AN ISSUE
 REQUIRING OPENING PROTECTIVES WITHIN 10
 FEET OF THE STAIRWAY, 3/4 HR RATING.
  
 28)905.2.1 RESIENTIAL SMOKE ALARMS:
 NFPA 72.A-8-1.2.1(B) ALL SMOKE DETECTORS
 SPECIFIED IN A-8-1.2.1(A) FOR EXISTING
 CONSTRUCTION ARE REQUIRED, AND, IN ADD-
 TION, A SMOKE DETECTOR IS REQUIRED IN
 EACH SLEEPING ROOM.
 ELEC. PLAN DO NOT INDICATE SMOKE DE-
 TECTORS IN THE HALLWAYS ADJACENT TO
 SLEEPING ROOMS.
  
 29) SHEET S-D1 DETAIL"A" STEEL COLUMN
 DOESN'T GIVE WELD SIZES.
  
 30) 1804.1.3 THE BOTTOM OF THE FOUNDA-
 TION SHALL EXTEND NO LESS THAN 12"
 BELOW FINISH GRADE. 1909.1 MINIMUM SLAB
 THICKNESS SLAB ON GRADE 31/2".SHEET S-D5
 THE FOUNDATION SCHEDULE HAS FOUNDATION
 DEPTHS OF 12" NOT THE 15 1/2" REQUIRED
 BY CODE. THE OTHER ISSUE IS THE ARCH
 SHEET A-DT5 DETAIL "N" THE SLAB IS ONLY
 8" BENEATH THE GRADE. ALSO SEE 1403.1.6
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-10-08 Cont ID  
Sent By dpalmer Date 2003-10-08 Time 10:56 Rev Time 1.00
Received By dpalmer Date 2003-10-08 Time 10:56 Sent To  
Notes
2003-10-08 00:00:00PLANS ONLY NEED TO BE STAMPED.
 ALLELECTICAL COMMENTS ADDRESSED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-10-02 Cont ID  
Sent By dpalmer Date 2003-10-02 Time 13:36 Rev Time 1.50
Received By dpalmer Date 2003-10-02 Time 13:35 Sent To  
Notes
2003-10-02 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE COMMENTS FROM
 PREVIOUS REVIEW.
 PLEASE SEE THAT FEEDERS ARE STILL BEING
 SHOWN SMALLER THAN #2 AL.
 IT WAS NOTED ON NOTE #20, HOWEVER NO
 CHANGES HAVE BEEN MADE TO PLANS.
  
 2)NOTE: IT WAS NOTED ON LAST REVIEW THE
 PLANS WERE ONLY IN FOR PLAN REVIEW AND
 THE CODE CHANGED ON JULY 1ST ,2003 TO
 THE 2002 NEC. IT WAS REQUESTED TO ADJUST
 PLANS ACCORDING TO 2002 NEC.
 PLEASE SEE 210.12 AND SEE PLANS.
 CIRCUITING ETC.
  
 3)NOTE: PLEASE SEE THAT PLANS ARE STILL
 ONLY IN FOR "PLAN REVIEW" AND WHEN
 SUBMITTING FOR PERMIT, PLEASE SUBMIT
 REQ'D # OF SETS FOR REVIEW AND STAMPING.
  
 4)NOTE: PLEASE CLARIFY IF CONDUCTORS FOR
 CLUBHOUSE SERVICE ENT AND FEEDERS ARE
 COPPER OR ALUM?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. ONCE AGAIN, IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-08-27 Cont ID  
Sent By dpalmer Date 2003-08-27 Time 17:41 Rev Time 1.00
Received By dpalmer Date 2003-08-27 Time 17:41 Sent To  
Notes
2003-08-27 00:00:00************** UNSAT *****************
  
 ******* NOTE *****
 PLANS HAVE ONLY BEEN IN FOR PLAN REVIEW
 AND NOT FOR PERMIT. PLEASE SEE THAT
 SINCE LAST REVIEW WE HAVE ADOPTED THE
 2002 NEC. PLEASE ADJUST PLANS FOR CODES
 REFERENCED AND ANY CHANGES NEEDED.
  
 1)NOTE: PLEASE SEE THAT ONLY ONE SET
 WAS SUBMITTED FOR REVIEW AND STAMPING?
 PLEASE SEE THAT ONE OLD SET FOR EACH:
 (APTS AND CLUBHOUSE) WERE SUBMITTED ALSO
  
 2)NOTE: IT WAS NOTED THAT NOTE FOR ALUM
 CONDUCTORS ON ED-1 WAS ADJUSTED, HOWEVER
 FEEDERS ON PLANS HAVE NOT BEEN ADJUSTED.
 PLEASE CORRECT.
  
 3)NOTE: PLEASE SEE THAT NEW SHEET EP-1
 IS MISSING FROM NEW SET. PLEASE SUBMIT
 COMPLETED SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 EELCTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-21 Cont ID  
Sent By dbaxter Date 2003-08-12 Time 13:11 Rev Time 3.00
Received By dpalmer Date 2003-05-20 Time 16:17 Sent To  
Notes
2003-05-21 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE WIND LOAD DETAIL FOR
 LIGHT POLES SHOWN AT 120 MPH. PLEASE SEE
 FBC FOR 140 MPH MIN. PLEASE SUBMIT
 DETAIL FOR THIS.
  
 2)NOTE: PLEASE CLARIFY HEIGHT REQ`MENTS
 FOR ADA FHAR,24 CFR 100.205
  
 3)NOTE: AS PER LOCAL AMENDMENTS 310-2(B)
 1&2. NO ALUM CONDUCTORS SMALLER THAN
 #2. PLEASE ALSO NOTE THAT ALUM IS NOT
 PERMITTED FOR GROUNDING OR BODNING.
  
 4)NOTE: PLEASE SEE UNIT "C" E-43
 PLEASE SEE MISSING SD OUTSIDE BEDROOM.
 UNIT "B" E-42
  
 5)NOTE: PLEASE SEE SOME UNIT LAYOUTS ARE
 MISSING ROOM DESIGNATIONS.
  
 6)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% (HOUSE). 215-3/230-42
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE NOTE THAT ALL OTHER BLDG TYPES,
 SITE/ AMEND AND CLUBHOUSE TO BE UNDER
 SEPARATE PERMITS.

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2004-03-12 Cont ID  
Sent By mamini Date 2004-03-12 Time 13:48 Rev Time 0.00
Received By mamini Date 2004-03-12 Time 13:48 Sent To  
Notes
2004-03-12 00:00:00PASSED:
 1. SEE PERMIT # 04030717 FOR UNDERGROUND
 UTILITIES AND SITE WORK
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2003-09-23 Cont ID  
Sent By mamini Date 2003-09-23 Time 14:30 Rev Time 1.00
Received By mamini Date 2003-09-23 Time 14:30 Sent To  
Notes
2003-09-23 00:00:00PASSED WITH PROVISOS:
 1. CIVIL/SITE PLANS HAVE BEEN REVIEWED
 FOR COMPLIANCE WITH THE CITY REQUIREMENT
 AND STANDARDS AND FOUND TO BE
 SATISFACTORY FOR PERMITTING.HOWEVER
 THE APPLICANT IS REQUIRED TO APPLY UNDER
 A SEPARATE PERMIT APPLICATION FOR
 "UNDERGROUND UTILITIES AND SITE WORK"
 PERMIT AND PAY THE APPROPRIATE FEES.
 IN ADDITION THE APPLICANT IS OBLIGATED
 TO ADDRESS ANY ADDITIONAL COMMENTS THAT
 THE CONSTRUCTION SERVICES DEPARTMENT MAY
 HAVE AT THE TIME OF THE ACTUAL
 PERMITTING.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-08-19 Cont ID  
Sent By mamini Date 2003-08-19 Time 08:46 Rev Time 1.00
Received By mamini Date 2003-08-19 Time 08:46 Sent To  
Notes
2003-08-19 00:00:00FAILED:
 1. PLEASE PROVIDE THE ITEMS THAT WE
 ASKED IN PREVIOUS REVIEW DATED 5-16-03
 AS SOON AS THEY BECOME AVAILABLE SO THAT
 THE CIVIL ENGINEERING REVIEW CAN BE
 COMPLETED.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-05-16 Cont ID  
Sent By mamini Date 2003-05-16 Time 09:00 Rev Time 1.00
Received By mamini Date 2003-05-16 Time 09:00 Sent To  
Notes
2003-05-16 00:00:00FAILED:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND SITE WORK WILL BE REQUIRED
 2. SUBMITTALS FOR UNDERGROUND UTILITIES
 AND SITE WORK PERMIT SHOULD INCLUDE
 COPY OF SFWMD PERMIT, STORM WATER CALC.,
 PERVIOUS & IMPERVIOUS AREA CALC. FOR THE
 TOTAL SITE, POLLUTION/ EROSION PLAN,
 EASEMENT REQUIRMENT, ETC.
 3. CIVIL PLANS MUST BE APPROVED BY
 PUBLIC UTILITIES FOR ALL THE CONNCTIONS
 TO CITY SERVICES PRIOR TO BEING REVIEWED
 BY BUILDING DEPARTMENT.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-10-03 Cont ID  
Sent By mcarsill Date 2003-10-03 Time 07:38 Rev Time 0.00
Received By mcarsill Date 2003-10-03 Time 07:38 Sent To  
Notes
2003-10-03 00:00:001) PLANS WERE REVIEWED ON 10.2.03
 COULD NOT LOCATE FIRE SPRINKLER PLANS
 WITH THE DRAWINGS THAT WERE SUBMITTED
 BY THE INTERESTED PARTIES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-09-02 Cont ID  
Sent By mcarsill Date 2003-09-02 Time 15:56 Rev Time 0.00
Received By mcarsill Date 2003-09-02 Time 15:56 Sent To  
Notes
2003-09-02 00:00:001) IT APPEARS THAT NO CHANGES HAVE BEEN
 MADE TO THE CUL-DE-SAC NOTED NEAR
 THE APARTMENT BUILDING. PREVIOUS
 DISCUSSIONS HAVE TAKEN PLACE AND THIS
 OFFICE IS UNSURE IF CHANGES HAVE BEEN
 MADE. ATTEMPTS TO SCALE THE CUL-DE-SAC
 INDICATES THAT IT MIGHT NOT MEET
 MINIMUM CODE REQUIREMENTS. PLEASE
 ADVISE IN WRITING.
  
 2) ALL FIRE ALARM SYSTEMS SHALL BE
 UL LISTED SINCE FIRE ALARM PERMITS
 WILL BE RECEIVED AFTER THE
 AUGUST 1, 2003 IMPLEMENTATION DATE.
  
 3) NO FIRE SPRINKLER PLANS PROVIDED
 WITH DRAWINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-05-28 Cont ID  
Sent By nmccray Date 2003-05-28 Time 15:03 Rev Time 0.00
Received By nmccray Date 2003-05-28 Time 15:03 Sent To  
Notes
2003-05-28 00:00:00DENIED: CLUBHOUSE
 1) PLEASE INDICATE WHAT KIND OF WORK OR
 MAINTENANCE WILL BE DONE IN THE WORK
 ROOM AND MAINTENANCE ROOM. ARE THERE
 GOING TO BE ANY FLAMMABLES OR
 COMBUSTIBLES LIQUIDS OR SOLIDS STORED IN
 THESE AREAS.
  
 2) SEPARATE PLAN AND PERMIT APPLICATION
 MAYBE NEEDED FOR CLUBHOUSE.
  
 APARTMENTS:
 1) SEPARATE PLAN AND PERMIT APPLICATION
 WILL BE REQUIRED FOR FIRE ALARM SYSTEM.
  
 2) SEPARATE PLAN AND PERMIT APPLICATION
 WILL BE REQUIRED FOR FIRE SORINKLER
 SYSTEM.
  
 3) PLEASE NOTE ELECTRICAL COMMENTS ON
 SMOKE DETECTOR OUTSIDE SLEEPING AREA.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-03-17 Cont ID  
Sent By csiegber Date 2004-03-17 Time 09:16 Rev Time 0.00
Received By csiegber Date 2004-03-17 Time 09:16 Sent To Z
Notes
2004-03-17 00:00:00REVISED SITE PLAN

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 10:46 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 10:46 Sent To B
Notes
2004-02-18 00:00:00TO JW DESK/SIBMITTAL/PA

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-17 Cont ID  
Sent By csiegber Date 2004-02-17 Time 16:28 Rev Time 0.00
Received By csiegber Date 2004-02-17 Time 16:28 Sent To B
Notes
2004-02-17 00:00:00TO JW DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-09-30 Cont ID  
Sent By mmclean Date 2004-01-29 Time 08:25 Rev Time 0.00
Received By csiegber Date 2003-09-30 Time 16:29 Sent To B
Notes
2003-09-30 00:00:00TO JW DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-09-29 Time 13:46 Rev Time 0.00
Received By csiegber Date 2003-09-29 Time 13:46 Sent To  
Notes
2003-09-29 00:00:00TO COMM BD#53

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-22 Cont ID  
Sent By csiegber Date 2003-09-22 Time 16:37 Rev Time 0.00
Received By csiegber Date 2003-09-22 Time 16:37 Sent To B
Notes
2003-09-22 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-12 Cont ID  
Sent By dbaxter Date 2003-08-12 Time 13:11 Rev Time 0.00
Received By dbaxter Date 2003-08-12 Time 13:11 Sent To E
Notes
2003-08-12 00:00:00TO COMM. BD. #37.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-05-15 Time 08:14 Rev Time 0.00
Received By shernand Date 2003-05-15 Time 08:14 Sent To  
Notes
2003-05-15 00:00:00COMM BOARD #48

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-10-02 Cont ID  
Sent By pkrauss Date 2003-10-02 Time 10:51 Rev Time 1.50
Received By pkrauss Date 2003-10-02 Time 10:51 Sent To  
Notes
2003-10-02 00:00:00PROVISO:APARTMENTS
 DRYERS INDICATED ON PLAN SHEET ACD-2,
 SHALL BE INSTALLED FOR FINAL INSPECTION.
  
 ENVIRONMENTAL CONTROLS SHALL BE MOUNTED
 IN ACCESSBILE LOCATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-09-09 Cont ID  
Sent By hmoser Date 2003-09-09 Time 14:52 Rev Time 1.00
Received By hmoser Date 2003-09-09 Time 14:51 Sent To  
Notes
2003-09-09 00:00:00PLAN DENIED
 #1) BATH EXHAUST MUST TERMINATE IN TO A
 1HR.SHAFT TO ROOF.
 #2) REFER TO SECTION 504.6 CLOTHES DRYER
 DUCT.EXHAUST)
 #3) REFER TO SECTION 604.1 BALANCED
 RETURN AIR EXECPTION #1.
 #4) NO EQUIPMENT SCHEDULE.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-05-28 Cont ID  
Sent By pkrauss Date 2003-05-28 Time 14:06 Rev Time 1.30
Received By pkrauss Date 2003-05-28 Time 14:06 Sent To  
Notes
2003-05-28 00:00:00DENIED:CLUBHOUSE
 1.INDICATE WHAT TYPE OF "MAITENANCE"
 WILL BE DONE IN THE MAINTENANCE GARAGE.
 PLEASE PROVIDE CLARIFY IF ANY FLAMABLES
 OR COMBUSTIBLES ARE TO BE STORED IN THIS
 AREA.SHOW COMPLIANCE WITH 2001 FBC(M)
 TABLE 403.3 FOR VENTILATION REQUIREMENTS
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS OR TO A
 SUPERVISORY SIGNAL TO BE INDICATED AT A
 CONSTANTLY ATTENDED LOCATION.
  
 APARTMENTS:
 1.PLEASE NOTE AS PER THE FAIR HOUSING
 ACT, ENVIRONMENTAL CONTROLS SHALL BE AT
 AN ACCESSIBLE LOCATION.
  
 2.PLEASE PROVIDE OUTSIDE AIR CALCS AS
 PER 2001 FBC(M) NATURAL MEANS 402.2 OR
 MECHANICAL MEANS TABLE 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-10-02 Cont ID  
Sent By kstevens Date 2003-10-02 Time 09:15 Rev Time 0.50
Received By kstevens Date 2003-10-02 Time 09:15 Sent To  
Notes
2003-10-02 00:00:00PASSED/PROVISO
  
 THERMAL EXPANSION PROTECTION VALVE -
 SUBMIT MANUF SPECIFICATION SHEETS - SHOW
 CAPABILITY TO WORK FOR MULTIPLE UNITS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-09-03 Cont ID  
Sent By kstevens Date 2003-09-03 Time 17:47 Rev Time 0.50
Received By kstevens Date 2003-09-03 Time 17:47 Sent To  
Notes
2003-09-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
  
 1) SECTION 104.2.1 TWO SETS OF SIGNED &
 SEALED SETS OF PLANS REQUIRED FOR REVIEW
 AND STAMPING.
 2) FROM PREVIOUS REVIEW, FOR CLAIRITY
 THE SAME NUMBER WILL BE USED.
 4) THERMAL EXPANSION PROTECTION REQUIRED
 607.3.2
 5) MANUF. INFORMATION (SPEC. SHEETS) RE-
 QUIRED FOR INSTA-HOT TANKLESS WATER
 HEATERS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-28 Cont ID  
Sent By kstevens Date 2003-05-28 Time 15:57 Rev Time 1.50
Received By kstevens Date 2003-05-28 Time 15:57 Sent To  
Notes
2003-05-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) SHT AU-4 DETAIL 3/ADT-4, BACKING FOR
 TUB & W/C TO COMPLY WITH FHA DESIGN MAN-
 UAL. SEE PAGE 6.9 - HEIGHT, LENGTH &
 WIDTH TO BE THE SAME AS SHOWN.
 2) SHTS PT1.3, PT1A.3, PT2.3, & PT2A.3,
 FULL OPEN VALVES REQUIRED AT THE BASE OF
 EVERY WATER RISER. SECTION 606.1(3)
 3) SHT PD-1 PLUMBING GENERAL NOTES:
 #2 PVC NOT APPROVED FOR DISTRIBUTION
 PIPE. SEE TABLE 605.5
 #6 DIELECTRIC UNIONS APPROVED FOR GAS
 PIPING ONLY. PLEASE DELETE REFERENCE.
 4) SHT PD-1 WATER HEATER DETAIL - NOTE
 CONCERNING AIR CHAMBERS. AIR CHAMBERS
 ARE NOT APPROVED. PLEASE DELETE REFEREN-
 CE. - THERMAL EXPANSION CONTROL REQUIRED
 PLEASE SHOW ON DETAIL. SECTION 607.3.2
 5) SHT PM-2 INSTANTANEOUT WATER HEATERS,
 MANUF. INFO. REQUIRED. W/HEATERS SHALL
 BE LISTED WITH AN APPROVED TESTING
 AGENCY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 2 Status P Date 2004-03-17 Cont ID  
Sent By dkanning Date 2004-03-17 Time 11:17 Rev Time 7.50
Received By dkanning Date 2004-03-17 Time 11:14 Sent To  
Notes
2004-03-17 00:00:00SIGNED AND SEALED LANDSCAPE PLANS MUST B
 BE APPROVED PRIOR TO LANDSCAPE INSPECTIO
 N.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-29 Cont ID  
Sent By csiegber Date 2004-03-17 Time 09:16 Rev Time 0.00
Received By mmclean Date 2004-01-29 Time 08:25 Sent To I
Notes
2004-01-29 00:00:00DENIED, BY ROBIN SINGER, PLANNING
 MANAGER & DAVID KANNING, PLANNER
 659-8031
 - DOORS ON GROUND FLOOR TO ACCESS LIVING
 ROOM, NOT BEDROOM.
 - DOORS FACING EXECUTIVE CENTER DR TO
 ACCESS PATH TO PUBLIC SIDEWALK
 - NEED LANDSCAPE PLAN FOR REVIEW
 - WAITING FOR BACKGROUND STATEMENT ON
 RELOCATION OF EASEMENTS FOR FINAL
 APPROVAL OF PLAT
2003-05-19 00:00:00PLAN REVIEW ONLY NO SITE PLAN SUBMITTED


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved