| 2003-06-20 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) HURRICANE MISSILE IMPACT PROTECTION |
| | SHUTTERS.THE SUBMITTED ARCH ALUMINUM |
| | DOOR PRODUCT APPROVAL NOA# 01-0910.09 |
| | REQUIRES THE INSTALLATION OF HURRICANE |
| | PROTECTION FOR THIS DOOR.SUBMIT A |
| | PRODUCT APPROVAL FOR SHUTTERS AND |
| | ANNOTATE ON THE PLANS. |
| | |
| | 2) THE SUBMITTED COPIES OF ARCH ALUMINUM |
| | DOOR PRODUCT APPROVAL NOA# 01.0910.09 |
| | ARE OF POOR QUALITY.THE INFORMATION, |
| | INCLUDING THE FASTENER SCHEDULE (SHEET 4 |
| | OF 4) IS NOT LEGIBLE.SUBMIT LEGIBLE |
| | COPIES.MIAMI-DADE PRODUCT APPROVALS |
| | CAN BE PRINTED FROM THEIR WEBSITE,WWW. |
| | MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM |
| | |
| | 3) FBC 1606.1.7WIND LOAD.THE PLANS |
| | SHALL STATE THE BASIC WIND SPEED, WIND |
| | IMPORTANCE FACTOR, WIND EXPOSURE |
| | CATEGORY, INTERNAL PRESSURE COEFFICIENT, |
| | AND EXTERIOR COMPONENT AND CLADDING |
| | DESIGN WIND PRESSURES SO THAT THEY CAN |
| | BE COMPARED TO THE PRODUCT APPROVAL. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |