Plan Review Details - Permit 03051173
Plan Review Stops For Permit 03051173
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-10-30 Cont ID  
Sent By jwitmer Date 2003-10-30 Time 11:25 Rev Time 0.33
Received By jwitmer Date 2003-10-30 Time 11:25 Sent To  
Notes
2003-10-30 00:00:0010-30-03 REV. 10-15-03JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-11 Cont ID  
Sent By csiegber Date 2003-10-21 Time 15:44 Rev Time 0.50
Received By jwitmer Date 2003-08-11 Time 08:57 Sent To  
Notes
2003-08-11 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 03051173
 ADDRESS: 10214 SAND CAY LANE
 CONT: G W PURUCKER HOMES
 TELL # (561)722-6141
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 ********PROVISO*********
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 RE-EVALUATE TRUSS ANCHOR SCHEDULE BEFORE
 FOOR FRAMING INSPECTION.
 SIMPSON HETA 20 / 1240
 SIMPSON HTSM16/ 840
  
 JIM WITMER
 (561)805-6715

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-23 Cont ID  
Sent By btrobaug Date 2003-08-08 Time 10:33 Rev Time 3.50
Received By lsmith Date 2003-06-18 Time 07:10 Sent To  
Notes
2003-06-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03051173
 ADD: 10214 SAND CAY LANE
 CONT: G W PURUCKER HOMES
 TEL: (561)775-1170
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 NOTE: FUTURE POOL,
 1803.1.3 EXCAVATION FOR ANY PURPOSE
 SHALL NOT EXTEND WITHIN 1 FT OF THE
 ANGLE OF REPOSE OR NARURAL SLOPE OF THE
 SOIL UNDER ANY FOOTING OR FOUNDATION,
 UNLESS SUCH FOOTING OR FOUNDATION IS
 FIRST PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT. COVERED LOGGIA ,
 COLUMN FOOTING MAY REQUIRE UNDERPINNING.
  
  
 1) 61G15-23.002(2) IF AN ENGINEER SIGNS
 AND SEALS PLANS A TITLE BLOCK ON EACH
 SHEET CONTAINING THE PRINTED NAME,
 ADDRESS, AND NUMBER OF THE ENGINEER OR
 BUSINESS WILL SATISFY THIS REQUIRMENT.]
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A) ZERO LOT LINE, A/C COMPRESSOR ON LOT
 (11).
 B)PROVIDE DOCUMENTATION FOR AN EASEMENT
 (EMERGENCY ACCESS) FOR BEDROOM# 2.
  
 3)905.2.1 APPROVED SINGLE-STATION OR
 MULTIPLE STATION SMOKE DETECTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 72,
 CHAPTER 2, WITHIN EVERY DWELLING UNIT
 WITHIN AN APARTMENT HOUSE, CONDOMINIMUM,
 OR TOWNHOUSE AND EVERY GUEST OR SLEEPING
 ROOM IN A MOTEL, HOTEL, OR DORMITORY &
 SLEEPING ROOMS IN RESIDENTIAL CARE/
 ASSISTED LIVING OCCUPANCIES. WHERE MORE
 THAN ONE DETECTOR IS REQUIRED TO BE
 INSTALLED WITHIN INDIVIDUAL DWELLING
 UNIT, THE DETECTOR SHALL BE WIRED IN
 SUCH A MANNER THAT THE ACTUATION OF ONE
 ALARM WILL ACTIVATE ALL THE ALARMS IN
 THE INDIVIDUAL UNIT. ALARMS SHALL ALSO
 BE MOUNTED ON THE HALL SIDE OF BEDROOMS
 EITHER WALL OR CEILING APPLICATION.
  
 4) MEAN ROOF HEIGHT: SHEET A_2.1, SHOULD
 BE TAKEN FROM HEIGHEST BEAM THEN 1/2 THE
 ROOF HEIGHT, 12'+5'-3"= 17'-3".
  
 5) SHEET A-4 BUCK DETAIL:
 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 6) SHEET A-7 AIR HANDLER LIVE LOAD,
 ATTIC STORAGE IN GARAGE, FINK TRUSS (T2)
 INDICATES 0 LBS LIVE LOAD ON BOTTOM
 TRUSS CHORD.T1604.1 30 LBS ATTIC STORAGE
  
 7) DESIGN PROFESSIONAL TO REVIEW &
 APPROVE, APPROVE WITH COMMENTS BEFORE
 TRUSS ENGINEERING IS SUBMITTED TO THE
 BUILDING DEPARTMENT.
  
 8) SHEET A-5, ATTACHMENT SCHEDULE
 A) THE ATTACHMENT FOR FLAT TILE AND
 BARREL TILE TO MATCH PRODUCT TESTING RE-
 PORTS. CALCULATIONS FOR ROOF ZONES 1,2
 & 3 SUBMITTED WHAT TYPE OF FASTENING
 SYSTEM WILL BE USED?
  
 BARREL TILE INDICATES THE USE OF BOX
 NAILS OR (SINKERS) WHAT IS THE VALUE FOR
 THIS NAIL?
  
 WIRE LATH SOFFITS: THIS DOES NOT INDI-
 CATE IF THE METAL LATH WILL BE FLAT OR
 RIBBED LATH, HIRIBBED LATH IS TO BE FAST
 ENED TO HORIZONTAL FRAMING MEMBERS WITH
 1 3/4" PENETRATION INTO THE FRAMING MEM-
 BER @ 4" O.C. (EACH RIB)
 ASTM C-1063.7.10.1.1
  
 WIRE LATH WALLS: THIS SAME SECTION
 ASTM C-1063.7.10.1.1. FLAT WIRE LATH
 SHALL BE NAILED @ 7" O.C. WITH THE NAIL
 CLEATED OVER TO ENGAGE 3 STRANDS.
  
 9) SHUTTER INSTALLATION SCHEDULE, INDI-
 CATES THE USE OF CALK-INS @ 12" O.C.
 THE CONTRACTOR IS TAKING THE VALUE FOR
 3000PSI CONCRETE. EITHER THE CONTRACTOR
 CHANGE THE INSTALLATION SCHEDULE TO RE-
 FLECT THE VALUE FOR MASONARY BLOCK,
 ANCHORS @ 7" O.C. OR SUBMIT A NOTIRIZE
 AFFADAVIT STATING THE CALK-INS TO BE A
 MINIMUM OF 2 3/4" TO ASSURE THE VALUES
 FOR 3000 PSI CONCRETE.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-08 Cont ID  
Sent By btrobaug Date 2003-08-08 Time 10:33 Rev Time 0.50
Received By btrobaug Date 2003-08-08 Time 10:23 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-23 Cont ID  
Sent By mmclean Date 2003-05-19 Time 16:23 Rev Time 1.00
Received By btrobaug Date 2003-05-23 Time 07:38 Sent To P
Notes
2003-05-23 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CHANGES TO
 THE PLANS FOR CODE COMPLIANCE AND
 RESUBMIT FOR REVIEW.
  
 1} THE RISER DIAGRAM INDICATES A 150 AMP
 PANEL WITH A 200AMP "DISCONNECT",
 PLEASE CORRELATE.
  
 2} THE 1/0 CONDUCTORS ARE INCORRECT FOR
 A 200 AMP OCP.FROM THE METER TO THE
 PANEL.
  
 3} THE 50 AMP OCP.IS NOT CORRECT FOR A
 10000 W AHU @ 125%
  
 4} PLEASE LIST THE REQ,D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG."SHALL HAVE NO
 OTHER OUTLETS".
  
 5} THERE MUST BE SMOKE DETECTORS SHOWN
 ON THE PLAN TO COMPLY WITH NFPA-72
 8-1.4.1.6
  
 6} PLEASE GIVE ROOM DESIGNATIONS ON
 ELECRICAL PLAN.
  
 7} RECEPTACLES ARE MISSING FROM THE
 MASTER BATH. COMPLY WITH 210-52(D).
  
 8} BATH #3 NOT IN COMPLIANCE WITH
 210-52(D).
  
 9} THE MASTER BEDROOM &,BEDROOM #2,THE
 GUEST BEDROOM AND THE DINNING ROOM ALL
 NEED RECEPTACLES ADDED TO COMPLY WITH
 210-52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-21 Cont ID  
Sent By csiegber Date 2003-10-21 Time 15:44 Rev Time 0.00
Received By csiegber Date 2003-10-21 Time 15:44 Sent To B
Notes
2003-10-21 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-01 Cont ID  
Sent By alange Date 2003-08-01 Time 14:08 Rev Time 0.00
Received By alange Date 2003-08-01 Time 14:08 Sent To B
Notes
2003-08-01 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-05-15 Time 08:32 Rev Time 0.00
Received By shernand Date 2003-05-15 Time 08:32 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-05 Cont ID  
Sent By kstevens Date 2003-05-24 Time 06:46 Rev Time 0.25
Received By pkrauss Date 2003-06-05 Time 06:58 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-05-24 Cont ID  
Sent By btrobaug Date 2003-05-23 Time 09:02 Rev Time 0.25
Received By kstevens Date 2003-05-24 Time 06:45 Sent To M
Notes
2003-05-24 00:00:00NO PLUMBING PLANS SUBMITTED

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-19 Cont ID  
Sent By shernand Date 2003-05-15 Time 08:32 Rev Time 1.00
Received By mmclean Date   Time   Sent To E
Notes
2003-05-19 00:00:005/19/03 REVIEWD BY GRACE JOYCE OK WITH
 GUEST HOUSE. MM


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved