| 2003-06-18 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03051173 |
| | ADD: 10214 SAND CAY LANE |
| | CONT: G W PURUCKER HOMES |
| | TEL: (561)775-1170 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | NOTE: FUTURE POOL, |
| | 1803.1.3 EXCAVATION FOR ANY PURPOSE |
| | SHALL NOT EXTEND WITHIN 1 FT OF THE |
| | ANGLE OF REPOSE OR NARURAL SLOPE OF THE |
| | SOIL UNDER ANY FOOTING OR FOUNDATION, |
| | UNLESS SUCH FOOTING OR FOUNDATION IS |
| | FIRST PROPERLY UNDERPINNED OR PROTECTED |
| | AGAINST SETTLEMENT. COVERED LOGGIA , |
| | COLUMN FOOTING MAY REQUIRE UNDERPINNING. |
| | |
| | |
| | 1) 61G15-23.002(2) IF AN ENGINEER SIGNS |
| | AND SEALS PLANS A TITLE BLOCK ON EACH |
| | SHEET CONTAINING THE PRINTED NAME, |
| | ADDRESS, AND NUMBER OF THE ENGINEER OR |
| | BUSINESS WILL SATISFY THIS REQUIRMENT.] |
| | |
| | 2)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | A) ZERO LOT LINE, A/C COMPRESSOR ON LOT |
| | (11). |
| | B)PROVIDE DOCUMENTATION FOR AN EASEMENT |
| | (EMERGENCY ACCESS) FOR BEDROOM# 2. |
| | |
| | 3)905.2.1 APPROVED SINGLE-STATION OR |
| | MULTIPLE STATION SMOKE DETECTORS SHALL |
| | BE INSTALLED IN ACCORDANCE WITH NFPA 72, |
| | CHAPTER 2, WITHIN EVERY DWELLING UNIT |
| | WITHIN AN APARTMENT HOUSE, CONDOMINIMUM, |
| | OR TOWNHOUSE AND EVERY GUEST OR SLEEPING |
| | ROOM IN A MOTEL, HOTEL, OR DORMITORY & |
| | SLEEPING ROOMS IN RESIDENTIAL CARE/ |
| | ASSISTED LIVING OCCUPANCIES. WHERE MORE |
| | THAN ONE DETECTOR IS REQUIRED TO BE |
| | INSTALLED WITHIN INDIVIDUAL DWELLING |
| | UNIT, THE DETECTOR SHALL BE WIRED IN |
| | SUCH A MANNER THAT THE ACTUATION OF ONE |
| | ALARM WILL ACTIVATE ALL THE ALARMS IN |
| | THE INDIVIDUAL UNIT. ALARMS SHALL ALSO |
| | BE MOUNTED ON THE HALL SIDE OF BEDROOMS |
| | EITHER WALL OR CEILING APPLICATION. |
| | |
| | 4) MEAN ROOF HEIGHT: SHEET A_2.1, SHOULD |
| | BE TAKEN FROM HEIGHEST BEAM THEN 1/2 THE |
| | ROOF HEIGHT, 12'+5'-3"= 17'-3". |
| | |
| | 5) SHEET A-4 BUCK DETAIL: |
| | 1707.4.4.2 TAPERED BUCKS: |
| | SHALL EXTEND BEYOND THE INTERIOR FACE |
| | OF THE WINDOW OR DOOR FRAME SUCH THAT |
| | FULL SUPPORT OF THE FRAME IS SUPPORTED. |
| | |
| | 6) SHEET A-7 AIR HANDLER LIVE LOAD, |
| | ATTIC STORAGE IN GARAGE, FINK TRUSS (T2) |
| | INDICATES 0 LBS LIVE LOAD ON BOTTOM |
| | TRUSS CHORD.T1604.1 30 LBS ATTIC STORAGE |
| | |
| | 7) DESIGN PROFESSIONAL TO REVIEW & |
| | APPROVE, APPROVE WITH COMMENTS BEFORE |
| | TRUSS ENGINEERING IS SUBMITTED TO THE |
| | BUILDING DEPARTMENT. |
| | |
| | 8) SHEET A-5, ATTACHMENT SCHEDULE |
| | A) THE ATTACHMENT FOR FLAT TILE AND |
| | BARREL TILE TO MATCH PRODUCT TESTING RE- |
| | PORTS. CALCULATIONS FOR ROOF ZONES 1,2 |
| | & 3 SUBMITTED WHAT TYPE OF FASTENING |
| | SYSTEM WILL BE USED? |
| | |
| | BARREL TILE INDICATES THE USE OF BOX |
| | NAILS OR (SINKERS) WHAT IS THE VALUE FOR |
| | THIS NAIL? |
| | |
| | WIRE LATH SOFFITS: THIS DOES NOT INDI- |
| | CATE IF THE METAL LATH WILL BE FLAT OR |
| | RIBBED LATH, HIRIBBED LATH IS TO BE FAST |
| | ENED TO HORIZONTAL FRAMING MEMBERS WITH |
| | 1 3/4" PENETRATION INTO THE FRAMING MEM- |
| | BER @ 4" O.C. (EACH RIB) |
| | ASTM C-1063.7.10.1.1 |
| | |
| | WIRE LATH WALLS: THIS SAME SECTION |
| | ASTM C-1063.7.10.1.1. FLAT WIRE LATH |
| | SHALL BE NAILED @ 7" O.C. WITH THE NAIL |
| | CLEATED OVER TO ENGAGE 3 STRANDS. |
| | |
| | 9) SHUTTER INSTALLATION SCHEDULE, INDI- |
| | CATES THE USE OF CALK-INS @ 12" O.C. |
| | THE CONTRACTOR IS TAKING THE VALUE FOR |
| | 3000PSI CONCRETE. EITHER THE CONTRACTOR |
| | CHANGE THE INSTALLATION SCHEDULE TO RE- |
| | FLECT THE VALUE FOR MASONARY BLOCK, |
| | ANCHORS @ 7" O.C. OR SUBMIT A NOTIRIZE |
| | AFFADAVIT STATING THE CALK-INS TO BE A |
| | MINIMUM OF 2 3/4" TO ASSURE THE VALUES |
| | FOR 3000 PSI CONCRETE. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)659-8096 X 8412 |
| | FAX: (561)659-8026 |