Plan Review Details - Permit 03051079
Plan Review Stops For Permit 03051079
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-10-10 Cont ID  
Sent By mmclean Date 2003-10-17 Time 12:54 Rev Time 1.00
Received By sthyng Date 2003-10-10 Time 07:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-26 Cont ID  
Sent By dpalmer Date 2003-10-07 Time 17:11 Rev Time 2.00
Received By sthyng Date 2003-06-25 Time 17:06 Sent To  
Notes
2003-06-26 00:00:00******CORRECTIONS*******
  
 1.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC FBC 13-103.1.2.
  
 2.)ADDITIONAL FEES DUE, $3.32.
  
 3.)IF YOU WISH TO REMOVE THE ELECTRIC
 FROM THE PLAN AND SUBMIT A SEPARATE
 PERMIT WITH SEPARATE PLANS AND PAY A
 FEE FOR THE ELECTRIC PERMIT, THE
 ELECTRIC MUST BE REMOVED FROM THE PLAN
 BY THE DESIGNER OF RECORD.THE ELECTRIC
 PERMIT APPLICATION MUST BE REMOVED FROM
 THE PERMIT.
  
 4.)WHEN RESUBMITTING, REPLACE CHANGED
 SHEETS ONLY. SUBMIT OLD REPLACED SHEETS,
 CLEARLY MARKED, SEPARATELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-29 Cont ID  
Sent By shernand Date 2003-06-25 Time 11:11 Rev Time 3.00
Received By sthyng Date 2003-05-28 Time 18:34 Sent To  
Notes
2003-05-29 00:00:00******CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ADDRESS THE HOLD ON THE PROPERTY.
  
 2.)APPROACH PERMIT REQUIRED; SEE
 ATTACHED.MECHANICAL PERMIT REQUIRED.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 4.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY BEFORE A PERMIT CAN BE
 ISSUED.THE PLANS MUST BE STAMPED AND
 THE
  
 5.)PLEASE PROVIDE AREA CALCULATIONS
 ON THE PLAN; EXISTING, PROPOSED, AND
 NEW TOTAL.
  
 6.)ENERGY CALCS REQUIRED, FBC13-101.2.
  
 7.)PROVIDE THE WINDOW INFORMATION FOR
 WINDOWS BEING INSTALLED; SIZE AND TYPE.
 WINDOWS AT BATH #1 AND #2 TO BE
 TEMPERED.ALL BEDROOMS MUST MEET EGRESS
 REQUIREMENTS FBC1004.5.
  
 8.)TWO COPIES OF ALL PRODUCT APPROVALS
 REQUIRED.SUBMIT THE FOLLOWING IN
 ADDITION TO THE ONES ALREADY SUBMITTED:
 ROOF
 GARAGE SIDE DOOR
 IMPACT PROTECTION
  
 9.A302, TYP SITE WALL DETAIL, FOOTER
 CANNOT ENCROACH OVER PROPERTY.SHOW ON
 FLOOR/FOUNDATION PLAN WITH PROPERTY
 LINE.
  
 10.) ATTIC ACCESS REQUIRED, FBC2309.
  
 11.)FBC11-4.22.2(1), 29" CLEARANCE FOR
 BATHROOM DOOR REQUIRED.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-10-17 Cont ID  
Sent By dpalmer Date 2003-10-17 Time 09:57 Rev Time 0.33
Received By dpalmer Date 2003-10-17 Time 09:57 Sent To B
Notes
2003-10-17 00:00:00SENT TO ST FOR PROCESSING

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-10-07 Cont ID  
Sent By csiegber Date 2003-10-16 Time 10:58 Rev Time 0.75
Received By dpalmer Date 2003-10-07 Time 17:00 Sent To B
Notes
2003-10-07 00:00:00*********** UNSAT********
  
 PLEASE SEE THAT PLANS MUST BE REVISED
 AND RESUBMITTED. PLEASE CALL TO SET UP
 TIME TO GO OVER PLANS BEFORE RESUBMITT-
 -ING.
 1)NOTE: PLEASE SEE RECEPT SPACING ALONG
 KITCHEN COUNTERSPACE PERE 210.52C1
  
 2)NOTE: PLEASE CORRECT SIZING OF
 CONDUCTORS ON PANEL SCHEDULE W/ OCP.
 20A SHOWN W/ #14'S ETC.
 PLEASE SEE THAT ALL OTHER CONDUCTORS ARE
 MISSING.
  
 3)NOTE: PLEASE SEE 424.3, SHOWS AHU AS
 10KW AND YET PANEL SCHEDULE SHOWS A
 20A-1P FEED???
  
 4)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 A #8 EQUIPMENT GROUNDING CONDUCTOR TO
 PANEL. BOTH MAIN AND PANEL ARE SHOWN TO
 BE 150A.PLEASE SEE 250.122 AS NOTED ON
 RISER, #8 SHOWN IS ONLY RATED UP TO
 100A'S. PLEASE ADJUST.
  
 5)NOTE: PLEASE CORRELATE RISER & PLANS,
 RISER SHOWS SERVICE AS EXISTING 150A AND
 PLAN SHOWS AS EXISTING 200A??
  
 6)NOTE: PLEASE SEE COPY OF FS 553.80(2),
 (B) WITH RESPECT TO DESIGN PROFESSIONALS
  
 7)NOTE: PLEASE SEE SD REQD IN MASTER
 BEDROOM SITTING RM.NFPA-72
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-06-20 Cont ID  
Sent By csiegber Date 2003-10-03 Time 09:34 Rev Time 0.75
Received By dpalmer Date 2003-06-20 Time 12:26 Sent To P
Notes
2003-06-20 00:00:00************* UNSAT **************
  
 PLANS/RISER IS SHOWN DIFFERENT FROM
 FIRST REVIEW AND NOW HAVE OTHER COMMENTS
  
 1)NOTE: PLEASE SEE THAT NEW PANEL IS
 SHOWN BEING FED FROM METER WITH A NEW
 MAIN AND IS NOT FED FROM EXISTING 200A
 PANEL.
 MAINS ARE TO BE GROUPED PER 230-72. NEC
  
 2)NOTE: PLEASE INCLUDE CONDUIT AND WIRE
 SIZES FOR UPGRADE OF PANEL FROM 100A TO
 150A.
  
 3)NOTE: PLEASE SHOW SIZE OF EXISTING
 SERVICE ENTRANCE CONDUCTORS AND METER
 CAN. SERVICE IS NOW SIZED TO 350A`S
 AND NEEDS TO HAVE GROUNDING ELECTRODE
 SYSTEM UPGRADED. DUE TO INCREASE IN
 OVERALL SERVICE SIZE. PLEASE SIZE
 SEC`S TO 310-15 AND GROUNDING ELECTRODE
 CONDUCTOR TO 250-66.
  
 4)NOTE: PLEASE PROVIDE AIC RATING FOR
 ANY NEW ELECTRICAL SERVICE EQUIPMENT.
 110-9/215-5
  
 5)NOTE: PLEASE INCLUDE NEW BLDG FOOTER
 STEEL TO BE PART OF GROUNDING ELECTRODE
 250-50 ALONG W/ EXISTING COLD WATER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.DUE TO THE SERVICE CHANGING
 AGAIN, THERE MAY BE OTHER COMMENTS.
 PLEASE CALL TO GO OVER COMMENTS AND
 SET UP A TIME TO GO OVER PLANS OR
 SERVICE.
  
 DEWEY PALMER
 ELECRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-16 Cont ID  
Sent By shernand Date 2003-06-13 Time 16:23 Rev Time 0.75
Received By dpalmer Date 2003-05-16 Time 17:07 Sent To P
Notes
2003-05-16 00:00:00*************** UNSAT ***********
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM,
 PANELS, LOAD CALCS AND NOTES TO PLANS.
 NOTE SHOWS A NEW 150A SERVICE, RISER
 SHOWS EXISTING 200A SERVICE? AND SUB
 PANEL IS SHOWN AS EXIST 100A TO REMAIN
 AND 150A NEW??
 215-5
  
 2)NOTE: PLEASE LIST ARC FAULT CIRCUITS
 PER 210-12
  
 3)NOTE: PLEASE SHOW ALL OULETS SERVING
 KITCHEN COUNTERSPACE AS GFI/ GFI
 PROETCTED. 210-8-A-6
  
 4)NOTE: PLEASE SHOW RECEPT SPACING ALONG
 COUNTERSPACE PER 210-52C1
  
  
  
  
  
 6)NOTE: PLEASE PROVIDE LICENSE/ FIRM #
 REQ`D ON TITLE BLOCK PER FS/FAC
 61G1-16.004 FOR ARCH OF RECORD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.PLEASE TAKE OUT ALL OLD/VOIDED
 SHEETSAND INSERT NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-10-16 Cont ID  
Sent By csiegber Date 2003-10-16 Time 10:58 Rev Time 0.00
Received By csiegber Date 2003-10-16 Time 10:58 Sent To E
Notes
2003-10-16 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-03 Cont ID  
Sent By csiegber Date 2003-10-03 Time 09:34 Rev Time 0.00
Received By csiegber Date 2003-10-03 Time 09:34 Sent To E
Notes
2003-10-03 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-25 Cont ID  
Sent By shernand Date 2003-06-25 Time 11:09 Rev Time 0.00
Received By shernand Date 2003-06-25 Time 11:09 Sent To E
Notes
2003-06-25 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-13 Cont ID  
Sent By shernand Date 2003-06-13 Time 16:23 Rev Time 0.00
Received By shernand Date 2003-06-13 Time 16:23 Sent To E
Notes
2003-06-13 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-13 Time 16:38 Rev Time 0.00
Received By shernand Date 2003-05-13 Time 16:38 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-05-23 Cont ID  
Sent By kstevens Date 2003-05-22 Time 07:31 Rev Time 0.35
Received By pkrauss Date 2003-05-23 Time 08:55 Sent To B
Notes
2003-05-23 00:00:00NO MECHANICAL INFORMATION SUBMITTED FOR
 REVIEW.PLEASE PROVIDE EQUIPMENT
 INFORMATION WITH MANUAL J CALCULATIONS
 WITH MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-06-21 Cont ID  
Sent By kstevens Date 2003-06-21 Time 10:07 Rev Time 0.25
Received By kstevens Date 2003-06-21 Time 10:07 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-05-22 Cont ID  
Sent By dpalmer Date 2003-06-20 Time 12:26 Rev Time 0.33
Received By kstevens Date 2003-05-22 Time 07:31 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-10-17 Cont ID  
Sent By shernand Date 2003-06-25 Time 11:09 Rev Time 0.00
Received By mmclean Date   Time   Sent To B
Notes
***NONE***