Plan Review Details - Permit 03051031
Plan Review Stops For Permit 03051031
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-09-02 Cont ID  
Sent By rbrown Date 2003-09-02 Time 11:27 Rev Time 0.00
Received By rbrown Date 2003-09-02 Time 11:27 Sent To  
Notes
2003-09-02 00:00:00REVISION SUBMITTED 8-27-03 FOR INTERIOR
 WALL AND DOOR RELOCATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-07-22 Cont ID  
Sent By csiegber Date 2003-08-27 Time 14:11 Rev Time 0.00
Received By rbrown Date 2003-07-22 Time 10:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-25 Cont ID  
Sent By rbrown Date 2003-06-25 Time 11:48 Rev Time 0.00
Received By rbrown Date 2003-06-25 Time 11:48 Sent To  
Notes
2003-06-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 6/5/03:
  
 3) 11-4.15WATER COOLER. NOTE 17 STATES
 THAT THE TENANT IS TO PROVIDE A WATER
 COOLER.THE PLANS SHALL BE AMENDED/
 ANNOTATED TO SPECIFY THE REQUIREMENTS
 FOR SPOUT HEIGHT/LOCATION AND FOR
 WHEELCHAIR APPROACH CLEARANCES (REF:
 FIG. 27).ANY PLUMBING PLAN REVIEW
 COMMENTS ON THE WATER COOLER OR DRINKING
 FOUNTAIN REQUIREMENTS SHALL BE ADDRESSED
  
 4) FBC 11-4.13.6MANEUVERING CLEARANCES
 AT DOORS. DOOR 3 SHALL HAVE AT LEAST 18"
 CLEARANCE BETWEEN THE LEADING EDGE OF
 THE DOOR AND THE ADJACENT OFFICE WALL ON
 THE PULL SIDE OF THE DOOR (REF: FIG. 25)
  
 5) THE PLAN HAS BEEN REDRAWN.THE NEW
 SHEETS SHALL BE REVIEWED AND STAMPED
 'APPROVED' BY THE CITY PLACE
 ADMINISTRATION.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-05 Cont ID  
Sent By rbrown Date 2003-06-05 Time 08:22 Rev Time 0.00
Received By rbrown Date 2003-06-05 Time 08:22 Sent To  
Notes
2003-06-05 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.2THE SUBMITTED 'GENERAL
 NOTES' SHEET SHALL BE SIGNED, DATED AND
 SEALED BY THE DESIGN PROFESSIONAL OF
 RECORD.
  
 2) FBC 11-4.1.6(3)(E) ACCESSIBLE TOILET.
 THE PLAN DOES NOT STATE WHETHER THE
 EXISTING TOILET IS ACCESSIBLE, ADAPTABLE
 (PER FAIR HOUSING ACCESSIBILITY GUIDE,
 AS THIS IS A 'LIVE/WORK LOFT') OR
 NON-ACCESSIBLE.AMEND THE PLAN TO
 DEMONSTRATE COMPLIANCE WITH THE
 REQUIREMENT FOR AN ACCESSIBLE TOILET.
  
 3) FBC 11-4.1.3DRINKING FOUNTAIN.
 AMEND THE PLANS TO SHOW THE PROVISION OF
 AN ACCESSIBLE DRINKING FOUNTAIN WITH
 HEIGHT AND CLEARANCES IN COMPLIANCE WITH
 FIG 27.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-08-18 Cont ID  
Sent By dpalmer Date 2003-08-18 Time 11:27 Rev Time 0.33
Received By dpalmer Date 2003-08-18 Time 11:27 Sent To  
Notes
2003-08-18 00:00:00REDLINED REQ'D SIGN CIRCUIT 600.5

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-07-22 Cont ID  
Sent By dpalmer Date 2003-07-22 Time 15:29 Rev Time 0.50
Received By dpalmer Date 2003-07-22 Time 15:29 Sent To  
Notes
2003-07-22 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE NOTES FROM OTHER
 ELECTRICAL REVIEWS.
 PLANS ARE NOT SUFF. FOR COMPLETE REVIEW.
 CIRCUITING/PANEL SCHEDULES ETC .
  
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-06-25 Cont ID  
Sent By dpalmer Date 2003-06-25 Time 06:11 Rev Time 0.25
Received By dpalmer Date 2003-06-25 Time 06:11 Sent To  
Notes
2003-06-25 00:00:00*********** UNSAT *************
  
 PLANS FOR MIN ELEC AND LIFE SAFTEY REQ`D
  
  
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST
 REVIEW.
  
 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR EXIT/ EM LTS, THAT WILL HAVE AN
 AFFECT ON ELECTRICAL
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF ELECTRICAL WILL BE SEPARATE,
 PLEASE HAVE ELECTRICAL SUBMITTED IN
 ORDER TO REVIEW MIN LIFE SAFETY REQ'MENT
 -S FOR FIRE AND ELECTRICAL.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-05-27 Cont ID  
Sent By btrobaug Date 2003-05-27 Time 09:24 Rev Time 0.33
Received By btrobaug Date 2003-05-27 Time 09:24 Sent To  
Notes
2003-05-27 00:00:00PROVISO
 ~~~~~~~
 ELECTRICAL DRAWING TO BE SUBMITTED
 SEPERATLY WITH PERMIT APP BY ELECTRICAL
 CONTRACTOR.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 651/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-19 Cont ID  
Sent By dpalmer Date 2003-05-19 Time 09:12 Rev Time 0.33
Received By dpalmer Date 2003-05-19 Time 09:12 Sent To  
Notes
2003-05-19 00:00:00************ UNSAT ****************
  
 1)NOTE: PLANS NEED TO SHOW ALL CIRCUIT-
 -ING AND CORRELATE W/ A SUBMITTED PANEL
 SCHEDULE. 215-5.
  
 2)NOTE: PLEASE SHOW CIRCUITING FOR EM/
 EXT LTS PER 700-12E
  
 3)NOTE: PLEASE CLARIFY TWO OTHER NEW
 OFFICE AREAS SHOWN W/ NO ELECTRICAL?
  
 4)NOTE" PLEASE SHOW LOAD CALCUALTIONS,
 PER 220-3,220-10,220-11,220-13 AND ALL
 CONTINUOUS LOADS AT 125% 230-42/215-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-08-19 Cont ID  
Sent By nmccray Date 2003-08-19 Time 16:23 Rev Time 0.00
Received By nmccray Date 2003-08-19 Time 16:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2003-07-25 Cont ID  
Sent By mcarsill Date 2003-07-25 Time 15:38 Rev Time 0.00
Received By mcarsill Date 2003-07-25 Time 15:38 Sent To  
Notes
2003-07-25 00:00:001) PLEASE LOCATE ALL EXIT SIGNS AND
 EMERGENCY LIGHT FIXTURES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-06-26 Cont ID  
Sent By nmccray Date 2003-06-26 Time 12:24 Rev Time 0.00
Received By nmccray Date 2003-06-26 Time 12:24 Sent To  
Notes
2003-06-26 00:00:001) OCCUPANCY CLASSIFICATION CHANGE TO
 BUSINESS OFFICE THE MEANS OF EGRESS HAS
 TO BE MARKED IE EXIT LIGHT AND EMERGENCY
 LIGHTS.
  
 2) NO SIGNED CITY PLACE STAMP ON NEW
 PLANS SUBMITTED.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-06-04 Cont ID  
Sent By nmccray Date 2003-06-04 Time 14:44 Rev Time 0.00
Received By nmccray Date 2003-06-04 Time 14:44 Sent To  
Notes
2003-06-04 00:00:001) IS THIS BUILDING FIRE SPRINKLERED IF
 SO HOW DOES THESE WALLS AFFECT THE FIRE
 SPRINKLER COVERAGE.
  
 2) ARE THESE WALLS FLOOR TO CEILING.
  
 3) SEPARATE PLAN AND PERMIT APPLICATION
 WILL BE REQUIRED FOR FIRE SPRINKLER
 REMODEL.
  
 4) WHAT IS THE FINISH CLASSFICATION FOR
 THE WALLS.
  
 5) WILL THERE BE A NEED FOR FIRE ALARM
 REMODEL, IF SO SEPARATE PLAN AND PERMIT
 APPLICATION IS REQUIRED.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-08-27 Cont ID  
Sent By csiegber Date 2003-08-27 Time 14:10 Rev Time 0.00
Received By csiegber Date 2003-08-27 Time 14:10 Sent To B
Notes
2003-08-27 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-08-13 Cont ID  
Sent By alange Date 2003-08-13 Time 14:00 Rev Time 0.00
Received By alange Date 2003-08-13 Time 14:00 Sent To  
Notes
2003-08-13 00:00:00TO COMM BD. #24

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-13 Cont ID  
Sent By alange Date 2003-08-13 Time 13:45 Rev Time 0.00
Received By alange Date 2003-08-13 Time 13:45 Sent To  
Notes
2003-08-13 00:00:00TO COMM BD. #24

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-21 Cont ID  
Sent By shernand Date 2003-07-21 Time 09:11 Rev Time 0.00
Received By shernand Date 2003-07-21 Time 09:10 Sent To  
Notes
2003-07-21 00:00:00COMM BOARD #6

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-23 Cont ID  
Sent By shernand Date 2003-06-23 Time 13:35 Rev Time 0.00
Received By shernand Date 2003-06-23 Time 13:35 Sent To  
Notes
2003-06-23 00:00:00COMM BOARD #11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-05-15 Time 08:52 Rev Time 0.00
Received By shernand Date 2003-05-15 Time 08:52 Sent To  
Notes
2003-05-15 00:00:00COMM BOARD #57

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2003-07-26 Cont ID  
Sent By pkrauss Date 2003-07-26 Time 11:43 Rev Time 0.05
Received By pkrauss Date 2003-07-26 Time 11:43 Sent To  
Notes
2003-07-26 00:00:00NO MECHANICAL PLANS SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-05-23 Cont ID  
Sent By pkrauss Date 2003-05-23 Time 12:54 Rev Time 0.15
Received By pkrauss Date 2003-05-23 Time 12:54 Sent To  
Notes
2003-05-23 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-08-18 Cont ID  
Sent By kstevens Date 2003-08-18 Time 18:50 Rev Time 0.25
Received By kstevens Date 2003-08-18 Time 18:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-07-29 Cont ID  
Sent By kstevens Date 2003-07-29 Time 14:51 Rev Time 0.75
Received By kstevens Date 2003-07-29 Time 14:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-07-05 Cont ID  
Sent By kstevens Date 2003-07-05 Time 12:56 Rev Time 1.00
Received By kstevens Date 2003-07-05 Time 12:55 Sent To  
Notes
2003-07-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 A) FROM PREVIOUS REVIEW
 1) IF THE OCCUPANCY CLASSIFICATION OR
 OCCUPANCY SUBCLASSIFICATION OF ANY
 BUILDING OR STRUCTURE IS CHANGED, THE
 BUILDING, ELECTRICAL, GAS, MECHANICAL, &
 PLUMBING SYSTEMS SHALL BE MADE TO CON-
 FORM TO THE INTENT OF THE TECHNICAL
 CODES AS REQUIRED BY THE BUILDING OFFI-
 CAL. SEC 3401.2.2.1 BLDG CODE
 20 11-4.1.1(6) IF BATHING FACILITIES ARE
 PROVIDED ON A SITE, THEN EACH SUCH PUB-
 LIC OR COMMON USE BATHING FACILITY SHALL
 COMPLY WITH SECTION 11-4.23 - BATHING
 ROOM DETAIL REQUIRED. SHOW CLEAR FLOOR
 SPACE, TURNING CIRCLE, HEIGHTS, GRAB-
 BARS, ECT. SHOW COMPLIANCE FOR ALL SECT-
 IONS AND SUBSECTIONS REQUIRED BY CODE.
 *** NEW COMMENTS ***
 3) IF A WATER COOLER IS USED, IS SHALL
 COMPLY WITH ARI-1010 AS PER SEC 410.4 &
 MANUF INFO. IS REQUIRED AT TIME OF FINAL
 PLUMBING INSPECTION.
 4) TURNING CIRCLE NOT SHOWN IN TOILET
 ROOM. PLEASE SHOW ON TOILET ROOM DETAIL.
 SECTION 11-4.22.3
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-11 Cont ID  
Sent By kstevens Date 2003-06-11 Time 12:21 Rev Time 0.75
Received By kstevens Date 2003-06-11 Time 12:21 Sent To  
Notes
2003-06-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
  
 1) IF THE OCCUPANCY CLASSIFICATION OR
 OCCUPANCY SUBCLASSIFICATION OF ANY
 BUILDING OR STRUCTURE IS CHANGED, THE
 BUILDING, ELECTRICAL, GAS, MECHANICAL, &
 PLUMBING SYSTEMS SHALL BE MADE TO CON-
 FORM TO THE INTENT OF THE TECHNICAL
 CODES AS REQUIRED BY THE BUILDING OFFI-
 CAL.SEC 3401.2.2.1
 2) 11-4.1.1(6) IF TOILET FACILITIES ARE
 PROVIDED ON A SITE, THEN EACH SUCH PUB-
 LIC OR COMMON USE TOILET FICILITY SHALL
 COMPLY WITH 11-4.22. IF BATHING FACILIT-
 IES ARE PROVIDED ON A SITE, THEN EACH
 SUCH PUBLIC OR COMMON USE BATHING FACIL-
 ITY SHALL COMPLY WITH SECTION 11-4.23.
 SUBMIT DETAIL FOR BOTH THE TOILET ROOM
 AND THE BATHROOM. SHOW CLEAR FLOOR SPACE
 AND TURNING CIRCLE, HEIGHTS, GRAB BARS,
 ECT. SHOW DETAILS FOR ALL SUBSECTIONS.
 3) KITCHEN SINK SHALL CONFORM TO SECTION
 11-4.24 AND ALL SUBSECTIONS. SUBMIT DE-
 TAIL FOR SINK SHOWING COMPLIANCE WITH
 ALL SUBSECTIONS.
 4) TABLE 403.1 REQUIRES A DRINKING
 FOUNTAIN. (ALSO SEE SECTION 410.1)
 5) IF ANY CHANGES TO THE SANITARY PIPING
 OR WATER PIPING SYSTEMS, A SANITARY
 RISER DIAGRAM AND A WATER DIAGRAM SHALL
 BE REQUIRED. SEC 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692