| Plan Review Stops For Permit 03051018 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-05-14 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-14 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-14 |
Time |
11:11 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2003-05-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-05-21 |
Time |
17:16 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-05-21 |
Time |
17:16 |
Sent To |
|
|
| Notes |
| 2003-05-21 00:00:00 | PASSED/PROVISO | | | | | | 704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 705.1.2 PENETRATIONS SHALL BE PRO- | | | TECTED BY AN APPROVED PENETRATION FIRE- | | | STOP SYSTEM AS TESTED IN ACCORDANCE WITH | | | ASTM E 814, WITH A MINIMUM POSITIVE | | | PRESSURE DIFFERENTIAL OF 0.01 INCH OF | | | WATER COLUMN AND AN F RATING OF NOT LESS | | | THAN REQUIRED RATING OF THE WALL | | | PENETRATED. | | | | | | FIRE STOP INFORMATION REQUIRED AT TIME | | | OF INSPECTION |
|
|
|