Plan Review Details - Permit 03050948
Plan Review Stops For Permit 03050948
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-28 Cont ID  
Sent By pkrauss Date 2003-05-22 Time 15:31 Rev Time 2.00
Received By sthyng Date 2003-05-28 Time 13:27 Sent To  
Notes
2003-05-28 00:00:00******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED.
  
 2.)FBC 3401.7.1.2, SHOW EGRESS AND
 SMOKE DETECTORS FOR THE BEDROOMS IN THE
 EXISTING HOUSE.
  
 3.)FIRESTOP REQUIRED 705.3.
  
 4.)PROVIDE SOFFIT VENT SIZES, TO
 COMPLY WITH FBC 2309.7.
  
 5.)ENERGY CALCS REQUIRED FBC13-101.2.
  
 6.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY BEFORE A PERMIT CAN BE
 ISSUED.THE PLANS MUST BE STAMPED AND
 THE RECEIPT ATTACHED.233-5025.
  
 7.)ADDITIONAL FEES REQUIRED; $828.62.
  
 8.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 9.)TWO COPIES OF PRODUCT APPROVALS
 ARE REQUIRED.
  
 10.)TWO DIFFERENT ROOF PRODUCT
 APPROVALS WERE SUBMITTED.SUBMIT ONLY
 WHAT YOU ARE INSTALLING.
  
 11.)A SINGLE HUNG EGRESS WINDOW
 PRODUCT APPROVAL WAS SUBMITTED.ALTHOUGH
 YOU MAY USE THIS PRODUCT IF YOU WISH,
 IT IS NOT REQUIRED BECAUSE THE REGULAR
 25 SINGLE HUNG MEETS EGRESS REQUIREMENTS
  
 12.)PROVIDE THE DOOR PRODUCT APPROVAL
 (TWO COPIES).

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-05-21 Time 16:17 Rev Time 0.50
Received By btrobaug Date 2003-05-21 Time 16:41 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-05-21 Time 16:17 Rev Time 0.00
Received By shernand Date 2003-05-21 Time 16:17 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-12 Cont ID  
Sent By sgraham Date 2003-05-21 Time 11:16 Rev Time 0.00
Received By shernand Date 2003-05-12 Time 13:19 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-05-22 Cont ID  
Sent By kstevens Date 2003-05-22 Time 08:21 Rev Time 0.35
Received By pkrauss Date 2003-05-22 Time 15:10 Sent To B
Notes
2003-05-22 00:00:00DENIED:MECHANICAL PERMIT 03050949
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.PROVIDE ENERGY & MANUAL J CALCS AS
 PER 2001 FBC CHAPTER 13 SUB-SECTION 600.
  
 2.INDICATE IF A/C EQUIPMENT IS NEW
 OR EXISTING.PROVIDE MAKE, MODEL, BTU
 OF THE AHU & SEER OF THE C.U.
  
 3.PROVIDE SQUARE FOOTAGE OF EXISTING
 & SQUARE FOOTAGE OF THE ADDITION.
  
 4.PLEASE NOTE, EXHAUST FAN REQUIRED IN
 THE NEW BATHROOM AS PER 2001 FBC(M)
 402.2.SHOULD TOILET ROOM BE SEPARATED
 FROM BATH AREA BY A DOOR, AN EXHAUST FAN
 WILL ALSO BE REQUIRED FROM THE TOILET
 ROOM AS PER 2001 FBC(M) 502.13.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-05-22 Cont ID  
Sent By btrobaug Date 2003-05-21 Time 16:57 Rev Time 0.33
Received By kstevens Date 2003-05-22 Time 08:21 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-05-21 Cont ID  
Sent By sgraham Date 2003-05-21 Time 11:16 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-12 Time 13:19 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-05-14 00:00:00DENIED, NEED SURVEY SHOWING ADDITION