Plan Review Details - Permit 03050853
Plan Review Stops For Permit 03050853
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-12 Cont ID  
Sent By rmcdouga Date 2003-08-12 Time 09:44 Rev Time 3.00
Received By rmcdouga Date 2003-08-12 Time 09:44 Sent To  
Notes
2003-08-12 00:00:00BUILDING PROVISO
  
 1) TRUSS CONNECTOR SCHEDULE CONTAINS
 SOME ERRORS. SUBMIT REVISED SCHEDULE.
 SEE 2003 USP CATALOG AND 2002 SIMPSON
 HIGH WIND-RESISTANT CONSTRUCTION CATALOG
  
 2) SUBMIT PRODUCT APPROVALS FOR THE
 FIXED ARCHED TOP (TOMBSTONE) FIXED GLASS
 WINDOWS.
  
 3) THE TRUSS DRAWINGS AND LAYOUT ARE NOT
 REQUIRED TO BE SUBMITTED FOR PLAN
 REVIEW. THEY ARE TO BE GIVEN TO THE
 INSPECTOR AT THE ROOF FRAMING INSPECTION
 NOTE: THE TRUSS DRAWINGS ARE REQUIRED TO
 HAVE THE ORIGINAL WET SIGNATURE OF THE
 TRUSS ENGINEER. THE MEAN ROOF HEIGHT IS
 INCORRECT ON THE DRAWINGS(PLANS SPECIFY
 16'-9"MEAN ROOF HEIGHT).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-25 Cont ID  
Sent By alange Date 2003-08-07 Time 14:58 Rev Time 5.00
Received By rmcdouga Date 2003-06-25 Time 15:56 Sent To  
Notes
2003-06-25 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) GLASS BLOCK ON THE ZERO LOT LINE IS
 REQUIRED TO BE ONE HOUR FIRE RATED.
 SPECIFY THIS ON THE FLOOR PLAN AND
 SUBMIT THE MANUFACTURE'S SPECIFICATIONS
 AND LISTING INFORMATION FOR THE ONE HOUR
 RATED GLASS BLOCK.
  
 4) SUBMIT ENGINEERED DRAWINGS, SPECIFICA
 TIONS, ETC. FOR BUTT GLAZING AS REQUIRED
 BY FBC 2406.2.
  
 5) WINDOWS WITHIN (3) FEET HORIZONTALLY
 OF A TUB OR A SHOWER ARE REQUIRED TO BE
 SAFETY GLAZING PER FBC 2405.2(2). PLEASE
 SPECIFY ON THE FLOOR PLAN.
  
 6) THE FIXED GLASS WINDOWS IN THE GRAND
 ROOM ARE REQUIRED TO BE SAFETY GLAZING
 PER FBC 2405.2(4). PLEASE SPECIFY ON THE
 FLOOR PLAN.
  
 7) ASTM C 926 REQUIRES STUCCO ON METAL
 LATH OVER A SOLID BASE TO BE 7/8".
 PLEASE REVISE WINDOW JAMB DETAIL AT
 FRAME WALL ON SHEET 5 AND DETAIL C ON
 SHEET 6A.
  
 8) FBC 1609.4 DOES NOT ALLOW THE ONE-
 THIRD INCREASE ON THE STEEL CALCULATIONS
 FOR TRUSS ANCHORS. PLEASE REVISE THE
 VALUES IN THE ANCHOR SCHEDULE ON SHEET
 3A. SEE 2003 USP OR 2002 SIMPSON HIGH
 WIND EDITION CATALOGS. HETAL16 WITH 5-
 10D X 1-1/2" NAILS HAS UPLIFT OF 1365#,
 NOT 1383#. THERE ARE OTHER DISCREPACIES
 WITH LISTED VALUES.
  
 9) TRUSS DRAWINGS ARE NOT REQUIRED TO BE
 SUBMITTED FOR PLAN REVIEW. THE ARE
 REQUIRED TO BE SUBMITTED TO THE BUILDING
 INSPECTOR IN THE FIELD AT THE ROOF
 FRAMING INSPECTION.
  
 10) SUBMIT KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS. SPECIFY THE
 ANCHOR TYPE AND SPACING. CLARIFY THE
 TYPES OF MOUNTING BRACKETS (HEADERS,STUD
 ANGLE, ETC.) THAT WILL BE USED AT THE
 TOP AND BOTTOM OF THE PANELS. SAMPLE OF
 INSTALLATION SCHEDULE IS ATTACHED.
  
 11) THE MULLION CALCULATIONS FOR WINDOWS
 26A AND 16A DO NOT APPEAR TO BE CORRECT.
 PLEASE PROVIDE CLARIFICATION ON HOW THE
 INFORMATION USED TO ENTER THE TABLE WAS
 CALCULATED. (TRIBUTARY WIDTH AND MULLION
 SPAN)
  
 12) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - UNCLIPPED MULLIONS (EXPIRED)
 - DOUBLE OUTSWING DOOR
 - SINGLE OUTSWING FRENCH DOOR
 - SINGLE OUTSWING DOOR WITH HALF LITE
 - TOMB STONE FIXED GLASS WINDOWS (THE
 PROD. APP. THAT WAS SUBMITTED IS FOR
 CIRCLE TOP WINDOWS)
 - THE 96" X 80" FIXED GLASS WINDOW (#26)
 IS INCORRECTLY INDICATED ON THE PROD.
 APPROVAL CHART THAT WAS SUBMITTED.
 THIS SIZE IS NOT LISTED ON THE CHART
 AND IT EXCEEDS THE LARGEST SIZE THAT
 IS LISTED.
  
 13) THE DOOR IN THE WALL BETWEEN THE
 GARAGE AND THE CONDITIONED SPACE IS
 REQUIRED TO BE SOLID CORE OR INSULATED
 PER FBC CHAPTER 13. PLEASE INDICATE ON
 PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-05-17 Cont ID  
Sent By dpalmer Date 2004-05-17 Time 14:07 Rev Time 0.33
Received By dpalmer Date 2004-05-17 Time 14:07 Sent To P
Notes
2004-05-17 00:00:00REDLINED MISSING RECEPT IN BEDRM #3
 210.52

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-19 Cont ID  
Sent By csiegber Date 2004-05-14 Time 11:51 Rev Time 0.33
Received By dpalmer Date 2003-05-19 Time 15:20 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-14 Cont ID  
Sent By csiegber Date 2004-05-14 Time 11:50 Rev Time 0.00
Received By csiegber Date 2004-05-14 Time 11:50 Sent To E
Notes
2004-05-14 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-07 Cont ID  
Sent By alange Date 2003-08-07 Time 14:57 Rev Time 0.00
Received By alange Date 2003-08-07 Time 14:57 Sent To B
Notes
2003-08-07 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-13 Cont ID  
Sent By shernand Date 2003-05-13 Time 16:55 Rev Time 0.00
Received By shernand Date 2003-05-13 Time 16:55 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-04 Cont ID  
Sent By kstevens Date 2003-05-24 Time 05:55 Rev Time 0.25
Received By pkrauss Date 2003-06-04 Time 07:45 Sent To B
Notes
2003-06-04 00:00:00MECHANICAL PERMIT 03050868

Review Stop P PLUMBING
Rev No 2 Status N Date 2004-05-28 Cont ID  
Sent By kstevens Date 2004-05-28 Time 09:36 Rev Time 0.50
Received By kstevens Date 2004-05-28 Time 09:36 Sent To  
Notes
2004-05-28 00:00:00NO PLUMBING PLANS REVISED - SUBMITTED
 WITH ELECTRICAL REVISION BUT NOT TO BE
 REVISED

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-05-24 Cont ID  
Sent By dpalmer Date 2004-05-17 Time 14:07 Rev Time 0.25
Received By kstevens Date 2003-05-24 Time 05:55 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-05-13 Time 16:55 Rev Time 1.00
Received By mmclean Date   Time   Sent To E
Notes
***NONE***