Plan Review Details - Permit 03050701
Plan Review Stops For Permit 03050701
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-30 Cont ID  
Sent By shernand Date 2003-05-30 Time 15:19 Rev Time 0.00
Received By shernand Date 2003-05-30 Time 15:19 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-08 Cont ID  
Sent By shernand Date 2003-05-08 Time 11:08 Rev Time 0.00
Received By shernand Date 2003-05-08 Time 11:08 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-06-19 Cont ID  
Sent By kstevens Date 2003-06-19 Time 12:01 Rev Time 0.33
Received By kstevens Date 2003-06-19 Time 12:01 Sent To  
Notes
2003-06-19 00:00:00COMBUSTION AIR TO BE VERIFIED AT SITE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-06-02 Cont ID  
Sent By kstevens Date 2003-06-02 Time 18:14 Rev Time 1.00
Received By kstevens Date 2003-06-02 Time 18:14 Sent To  
Notes
2003-06-02 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) PIPING SHALL NOT BE INSTALLED IN
 SOLID FLOOR SLABS. SEC 404.6
 2) 1-1/4" PIPE REQUIRED FOR 200KBTU'S.
 (SEE BBQ & RANGE) @ 125'.
 3) MINIMUM SIZE FOR 717K BTU'S @ 125' IS
 2". (2-1/2" SHOWN)
 4) IF THERE IS TO BE WELDED PIPING, THE
 CERTIFICATION, & PICTURE I.D. OF THE
 PERSON DOING THE WELDING SHALL BE SUB-
 MITTED ALONG WITH THE WELDING PROCEDURE
 PRIOR TO ISSUING PERMIT. (SHT P400 GAS
 PIPING SPECIFICATIONS "A")
 5) FROM PREVIOUS REVIEW, PLEASE SUBMIT
 CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2001 FUEL GAS CODE SEC. 304.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-20 Cont ID  
Sent By shernand Date 2003-05-30 Time 15:19 Rev Time 0.50
Received By kstevens Date 2003-05-20 Time 07:49 Sent To  
Notes
2003-05-20 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 A) PLANS FOR GAS NOT APPROVED AT TIME OF
 PERMIT WITH PLUMBING. PROVISO INDICATED
 THAT PLANS SHALL BE SUBMITTED AT TIME OF
 APPLICATION FOR GAS. THE FOLLOWING IN-
 FORMATION REQUIRED FOR GAS PERMIT.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692