Plan Review Details - Permit 03050608
Plan Review Stops For Permit 03050608
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-01-14 Cont ID  
Sent By shill Date 2004-02-06 Time 14:37 Rev Time 1.00
Received By shill Date 2004-01-14 Time 13:18 Sent To  
Notes
2004-01-14 00:00:00*****CORRECTIONS****
  
 REVISION #1
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ZONING APPROVAL REQUIRED.
  
 2.)WHEN RESUBMITTING, SUBMIT OLD
 SHEETS.
  
 3.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS.
  
 4.)PLEASE NOTE THAT IF THE UNDER AIR
 AREA CHANGES, NEW ENERGY CALCS
 REFLECTING THE NEW CONDITIONED FLOOR
 AREA WILL BE REQUIRED.
  
 5.)PROVIDE A VALUE FOR THE ADDITIONAL
 SCOPE OF WORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-10-20 Cont ID  
Sent By csiegber Date 2004-01-14 Time 09:29 Rev Time 3.00
Received By sthyng Date 2003-10-20 Time 11:39 Sent To Z
Notes
2003-10-20 00:00:00*****CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE A VALUE FOR THE ADDITIONAL
 WORK.
  
 2.)INSULATION REQUIRED IN ADJACENT
 WALLS, FBC13-602.1.B, 13-602.1.C.1.2.
  
 3.)PROVIDE A DETAIL FOR THE HANDRAIL.
  
 4.)STAIR 1-3 AND 1-4, SUM OF TWO
 RISERS AND A TREAD TO BE NOT LESS THAN
 24" NOR MORE THAN 25", FBC1007.3.
  
 5.)SIMPSON HHU210 NOT IN THE CATALOG.
 CLARIFY.CHECK FASTENERS SPECIFIED ON
 THE PLAN AGAINST EITHER THE 2003 CATALOG
 OR TECHNICAL BULLETIN.
  
 6.)YOU ARE BUILDING A NEW PARTITION
 WALL ON THE FIRST FLOOR OF THE GARAGE.
 IS THIS CURRENTLY GARAGE SPACE BEING
 CONVERTED TO HABITABLE SPACE?
 IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 7.)PROVIDE PRODUCT APPROVALS FOR
 THE IMPACT DOORS; 2 LEGIBLE COMPLETE
 SETS.
  
 8.)ENERGY CALCS REQUIRED,FBC13-101.
  
 9.)SUBMIT A NEW SITE PLAN FOR
 ZONING APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-05-28 Cont ID  
Sent By shernand Date 2003-05-20 Time 09:53 Rev Time 1.00
Received By shill Date 2003-05-28 Time 13:26 Sent To  
Notes
2004-02-18 00:00:00NOTE - SOILS REPORT WITH PERMIT 03092021
2003-05-28 00:00:00******PROVISO*******
 FINISHED FLOOR ELEVATION TO BE 7.5 MIN.
 PER CITY OF WEST PALM BEACH MUNICIPAL
 CODE, 95-546.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-12-24 Cont ID  
Sent By btrobaug Date 2003-12-24 Time 09:44 Rev Time 0.50
Received By btrobaug Date 2003-12-24 Time 09:24 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-02 Cont ID  
Sent By csiegber Date 2003-12-23 Time 15:16 Rev Time 0.50
Received By btrobaug Date 2003-10-02 Time 15:55 Sent To P
Notes
2003-10-02 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NO ELECTRICAL PERMIT APPLICATION
 SUBMITTED WITH PLANS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 E-MAIL:[email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-05-14 Cont ID  
Sent By csiegber Date 2004-05-14 Time 09:22 Rev Time 0.00
Received By csiegber Date 2004-05-14 Time 09:22 Sent To M
Notes
2004-05-14 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-06 Cont ID  
Sent By shill Date 2004-02-06 Time 14:36 Rev Time 0.00
Received By shill Date 2004-02-06 Time 14:36 Sent To B
Notes
2004-02-06 00:00:00TO SMH DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-01-14 Time 09:29 Rev Time 0.00
Received By csiegber Date 2004-01-14 Time 09:29 Sent To B
Notes
2004-01-14 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-23 Cont ID  
Sent By mmclean Date 2004-01-13 Time 12:05 Rev Time 0.00
Received By csiegber Date 2003-12-23 Time 15:16 Sent To E
Notes
2003-12-23 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-30 Cont ID  
Sent By csiegber Date 2003-09-30 Time 08:56 Rev Time 0.00
Received By csiegber Date 2003-09-30 Time 08:55 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-20 Cont ID  
Sent By shernand Date 2003-05-20 Time 09:53 Rev Time 0.00
Received By shernand Date 2003-05-20 Time 09:53 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-07 Cont ID  
Sent By sgraham Date 2003-05-19 Time 15:49 Rev Time 0.00
Received By shernand Date 2003-05-07 Time 13:27 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-05-25 Cont ID  
Sent By pkrauss Date 2004-05-25 Time 13:06 Rev Time 0.35
Received By pkrauss Date 2004-05-25 Time 12:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-09 Cont ID  
Sent By csiegber Date 2004-05-14 Time 09:22 Rev Time 0.35
Received By pkrauss Date 2004-01-09 Time 09:40 Sent To B
Notes
2004-01-09 00:00:00MECHANICAL PERMIT REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-10-15 Cont ID  
Sent By kstevens Date 2004-01-06 Time 10:21 Rev Time 0.33
Received By pkrauss Date 2003-10-15 Time 12:26 Sent To P
Notes
2003-10-15 00:00:00MECHANICAL PERMIT REQUIRED.THIS IS
 NOT A REVISION TO PERMIT 03050608.
 MECHANICAL PLANS WERE NOT SUBMITTED WITH
 THE ORIGINAL PLANS.PLEASE SUBMIT PLANS
 WITH MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-01-06 Cont ID  
Sent By kstevens Date 2004-01-06 Time 10:20 Rev Time 1.00
Received By kstevens Date 2004-01-06 Time 10:20 Sent To M
Notes
2004-01-06 00:00:00REVISION OK - ADDED W/C, LAV, & SINK

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-11 Cont ID  
Sent By btrobaug Date 2003-12-24 Time 09:45 Rev Time 0.50
Received By kstevens Date 2003-10-11 Time 06:40 Sent To M
Notes
2003-10-11 00:00:00REVISION - DENIED
 REFERENCE: FLORIDA ADMIN CODE
  
 1) PLUMBING PERMIT REQUIRED
 2) SEE ATTACHED SHEET: 61G15-23.002(2)
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET. IF PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME ADDRESS AND CERITFICATE OF AUTHOR-
 IZATION NUMBER OF THE ENGINEERING BUSIN-
 ESS ON EACH SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status F Date 2004-01-13 Cont ID  
Sent By mmclean Date 2004-01-13 Time 12:05 Rev Time 0.00
Received By mmclean Date 2004-01-13 Time 12:05 Sent To I
Notes
2004-01-13 00:00:00NO OUTSIDE ACCESS TO BLDG.NEED TO
 ENCLOSE STAIRS CALLED CONTR WILL PROVIDE
 NEW DRAWINGS MM

Review Stop Z ZONING
Rev No 3 Status F Date 2003-10-21 Cont ID  
Sent By mmclean Date 2003-10-21 Time 16:54 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-10-21 00:00:0010/21/03 DENIED, CANNOT HAVE A GUEST
 HOUSE IN SF7 NO KITCHEN. NEEED TO HAVE
 ENG REMOVE ELEC SHOWING THE KITCHEN
 CALLED CONTR FILE H MM

Review Stop Z ZONING
Rev No 2 Status P Date 2003-05-19 Cont ID  
Sent By sthyng Date 2003-10-20 Time 15:31 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-05-08 Cont ID  
Sent By shernand Date 2003-05-07 Time 13:28 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-05-08 00:00:00DENIED, NEED SURVEY SHOWING LOCATION
 OF PERGOLA