| Plan Review Stops For Permit 03050583 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2003-07-24 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-07-24 |
Time |
10:43 |
Rev Time |
1.50 |
| Received By |
sthyng |
Date |
2003-07-24 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2003-07-24 00:00:00 | 18" MIN BELOW GRADE PER SOILS REPORT | | | S/W CONTRACTOR | | | | | | PROVISO - SUBMIT LETTER FROM ENGINEER | | | RE: CHANGE IN FOOTING SIZE BEFORE 1ST | | | INSPECTION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2003-06-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-07-23 |
Time |
18:32 |
Rev Time |
2.50 |
| Received By |
sthyng |
Date |
2003-06-26 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2003-06-26 00:00:00 | ******CORRECTIONS******* | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SMOKE DETECTORS ON EXISTING HOUSE | | | MUST COMPLY WITH FBC 905.2.2, | | | FBC3401.7.1.2. | | | | | | 2.)THE SURVEY SHOWS AN INCORRECT | | | FLOOD ZONE DESIGNATION.PLEASE REVISE. | | | | | | 3.)THE PLANS ARE STAMPED FOR IMPACT | | | FEES BUT THE SQUARE FOOTAGE ON THE PLAN, | | | 2608, IS NOT CONSISTENT WITH THE | | | AMOUNT ON THE STAMP (2393).233-5025 | | | | | | 4.)SEE THE PREVIOUS LIST, ITEM #13, | | | REGARDING ATTACHMENTS F AND H (S3) NOT | | | LISTED ON ANCHOR SCHEDULE (S2). | | | | | | 5.)THE SITE PLAN, A1, SHOWS AN | | | "EXISTING 2-STORY RESIDENCE".REVISE. | | | | | | 6.)PROVIDE A SOILS INVESTIGATION | | | REPORT. | | | | | | 7.)THE CASEMENT WINDOW PRODUCT | | | APPROVAL HAS SHEETS FOR A FIXED WINDOW | | | IN IT; MULLION PRODUCT APPROVAL WAS | | | NOT SUBMITTED; PRODUCT APPROVALS NOT | | | LEGIBLE (SEE PREVIOUS CORRECTION NOTE | | | #15).SEE WWW.MIAMIDADE.GOV (FIND A | | | DEPARTMENT, BUILDING CODE COMPLIANCE, | | | PRODUCT CONTROL) TO DOWNLOAD DADE | | | COUNTY PRODUCT APPROVALS. | | | | | | WHEN RESUBMITTING, CLOUD OR OTHERWISE | | | MARK ALL CHANGES.REPLACE SHEETS WHICH | | | HAVE BEEN REVISED, AND ATTACH ONE COPY | | | OF THE OLD SHEETS SEPARATELY.DO THIS | | | FOR ALL SETS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-05-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-06-24 |
Time |
15:24 |
Rev Time |
3.00 |
| Received By |
sthyng |
Date |
2003-05-27 |
Time |
19:37 |
Sent To |
|
|
| Notes |
| 2003-05-28 00:00:00 | ********CORRECTIONS******** | | | | | | 1.)SIGN THE OWNER/AGENT LINE ON THE | | | ENERGY CALC. | | | | | | 2.)PROVIDE A COPY OF THE SURVEY | | | REFERRED TO ON THE PLAN WITH ELEVATIONS, | | | IF AVAILABLE. | | | | | | 3.)THE AREA TABULATIONS (A2) SHOULD | | | INCLUDE EXISTING AREAS, PROPOSED, AND | | | NEW TOTALS. | | | | | | 4.)THIS PROPERTY IS IN A FLOOD ZONE. | | | THE FINISHED FLOOR ELEVATION IS | | | REQUIRED TO BE 6" ABOVE THE BASE FLOOD | | | ELEVATION (7'), CITY OF WEST PALM BEACH | | | MUNICIPAL CODE 95-546. | | | | | | 5.)ADDITIONAL FEES DUE, $543.97. | | | | | | 6.)THE WINDOW AT THE SHOWER MUST | | | COMPLY WITH FBC 2405.2. | | | | | | 7.)THE ROOF SHEATHING (FOYER SECTION, | | | A3, WALL SECTION A5) MUST COMPLY WITH | | | CITY OF WEST PALM BEACH AMENDMENT TO | | | THE FBC, TABLE 2306.1, ATTACHED. | | | | | | 8.)THE SOFFIT VENTING IS REQUIRED | | | TO COMPLY WITH FBC 2309.7, CANNOT | | | "MATCH EXISTING" (FOYER SECTION, A3). | | | | | | 9.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE | | | STAMPED AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.233-5025 | | | | | | 10.) ATTIC ACCESS REQUIRED, FBC2309. | | | | | | 11.)PROVIDE A DETAIL FOR THE NEW | | | FRAME WALL (A2 FLOOR PLAN).INSULATION | | | IS REQUIRED BETWEEN CONDITIONED AND | | | NON-CONDITIONED SPACE. | | | | | | 12.)S2, ROOF FRAMING PLAN, SHOWS | | | ATTACHMENT D, TARGET UPLIFT 2230 WHICH | | | EXCEEDS THE MAX UPLIFT OF 1845 ON THE | | | TRUSS ANCHOR SCHEDULE. | | | | | | 13.)ATTACHMENTS F AND H, ROOF FRAMING | | | PLAN (S3), ARE NOT LISTED ON THE | | | ANCHOR SCHEDULE. | | | | | | 14.)SHOW THE SOUTH PROPERTY LINE ON | | | THE FOUNDATION PLAN.THE FOOTER FOR THE | | | PRIVACY WALL CANNOT ENCROACH THE | | | PROPERTY LINE. | | | | | | 15.)SUBMIT TWO LEGIBLE COPIES OF THE | | | FOLLOWING PRODUCT APPROVALS: | | | FIXED GLASS WINDOW | | | CASEMENT | | | MULLION | | | FRENCH DOORS | | | SIDELITS | | | GARAGE DOOR | | | ROOF SHINGLES | | | IMPACT PROTECTION |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2003-07-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-07-18 |
Time |
06:09 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-07-18 |
Time |
06:09 |
Sent To |
P |
|
| Notes |
| 2003-07-18 00:00:00 | LPLANS REDLINED BY ENG/ARCH FOR RECEPT | | | SPACING. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2003-06-24 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-17 |
Time |
11:05 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-06-24 |
Time |
15:24 |
Sent To |
B |
|
| Notes |
| 2003-06-24 00:00:00 | **************** UNSAT *************** | | | | | | PLEASE SEE NOTES FROM FIRST REVIEW. | | | NOTE #`S 4 AND # 5 ARE STILL OUTSTANDING | | | | | | 1)NOTE: PLEASE SEE MISSING RECEPTS PER | | | 210-52 | | | | | | 2)NOTE: PLEASE SEE CHAPTER 34 FBC FOR | | | ADDTIONS. 3401.7.1.1 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-05-15 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-18 |
Time |
16:08 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2003-05-15 |
Time |
06:47 |
Sent To |
P |
|
| Notes |
| 2003-05-15 00:00:00 | ************ UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE MEANS OF EGRESS LT | | | CONTROL FROM REC RM DOOR TO OUTSIDE | | | WALK. S-4? TO BE ADDED? 210-70 | | | | | | 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED CIRCUITS ON PANEL SCHEDULE | | | 210-12 | | | | | | 3)NOTE: PLEASE LIST THE REQ`D BATH CIR- | | | -CUIT ON PANEL SCHEDULE 210-52D/210-11C3 | | | #12,20A | | | | | | 4)NOTE: PLEASE SEE A COUPLE OF RECEPTS | | | MISSING TO MEET 210-52/ OFFICE AND NEW | | | BEDROOM. | | | | | | 5)NOTE: PLEASE SEE FBC CHAPTER 34 FOR | | | ADDITIONS TO EXISTING STRUCTURES. THE | | | SQ FT BEING ADDED EXCEEDS % 3401.7.1.1 | | | PLEASE SHOW / CLARIFY ORIG ELECTRICAL | | | AS EXISTING AND THAT IT MEETS CURRENT 99 | | | NEC FOR ELECTRICAL REQ`MENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. PLEASE TAKE OUT ANY OLD/VOIDED | | | SHEETS AND INSERT NEWSHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2003-05-14 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-06 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2003-05-14 |
Time |
17:14 |
Sent To |
P |
|
| Notes |
| 2003-05-14 00:00:00 | SENT TO PLUMBING,ON VACATION./WRT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-07-17 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-17 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-17 |
Time |
11:05 |
Sent To |
E |
|
| Notes |
| 2003-07-17 00:00:00 | DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-06-18 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-18 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-18 |
Time |
16:08 |
Sent To |
E |
|
| Notes |
| 2003-06-18 00:00:00 | DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-05-06 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-06 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-06 |
Time |
11:02 |
Sent To |
E |
|
| Notes |
| 2003-05-06 00:00:00 | BT DESK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2003-05-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-05-19 |
Time |
18:33 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2003-05-20 |
Time |
13:34 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-07-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-07-23 |
Time |
18:32 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2003-07-23 |
Time |
18:32 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2003-05-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-07-18 |
Time |
06:16 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2003-05-19 |
Time |
18:33 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2003-05-06 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2003-05-06 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
I |
|
| Notes |
|
|