Plan Review Details - Permit 03050583
Plan Review Stops For Permit 03050583
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-07-24 Cont ID  
Sent By sthyng Date 2003-07-24 Time 10:43 Rev Time 1.50
Received By sthyng Date 2003-07-24 Time 10:43 Sent To  
Notes
2003-07-24 00:00:0018" MIN BELOW GRADE PER SOILS REPORT
 S/W CONTRACTOR
  
 PROVISO - SUBMIT LETTER FROM ENGINEER
 RE: CHANGE IN FOOTING SIZE BEFORE 1ST
 INSPECTION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-26 Cont ID  
Sent By kstevens Date 2003-07-23 Time 18:32 Rev Time 2.50
Received By sthyng Date 2003-06-26 Time 10:34 Sent To  
Notes
2003-06-26 00:00:00******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SMOKE DETECTORS ON EXISTING HOUSE
 MUST COMPLY WITH FBC 905.2.2,
 FBC3401.7.1.2.
  
 2.)THE SURVEY SHOWS AN INCORRECT
 FLOOD ZONE DESIGNATION.PLEASE REVISE.
  
 3.)THE PLANS ARE STAMPED FOR IMPACT
 FEES BUT THE SQUARE FOOTAGE ON THE PLAN,
 2608, IS NOT CONSISTENT WITH THE
 AMOUNT ON THE STAMP (2393).233-5025
  
 4.)SEE THE PREVIOUS LIST, ITEM #13,
 REGARDING ATTACHMENTS F AND H (S3) NOT
 LISTED ON ANCHOR SCHEDULE (S2).
  
 5.)THE SITE PLAN, A1, SHOWS AN
 "EXISTING 2-STORY RESIDENCE".REVISE.
  
 6.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 7.)THE CASEMENT WINDOW PRODUCT
 APPROVAL HAS SHEETS FOR A FIXED WINDOW
 IN IT; MULLION PRODUCT APPROVAL WAS
 NOT SUBMITTED; PRODUCT APPROVALS NOT
 LEGIBLE (SEE PREVIOUS CORRECTION NOTE
 #15).SEE WWW.MIAMIDADE.GOV (FIND A
 DEPARTMENT, BUILDING CODE COMPLIANCE,
 PRODUCT CONTROL) TO DOWNLOAD DADE
 COUNTY PRODUCT APPROVALS.
  
 WHEN RESUBMITTING, CLOUD OR OTHERWISE
 MARK ALL CHANGES.REPLACE SHEETS WHICH
 HAVE BEEN REVISED, AND ATTACH ONE COPY
 OF THE OLD SHEETS SEPARATELY.DO THIS
 FOR ALL SETS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-27 Cont ID  
Sent By dpalmer Date 2003-06-24 Time 15:24 Rev Time 3.00
Received By sthyng Date 2003-05-27 Time 19:37 Sent To  
Notes
2003-05-28 00:00:00********CORRECTIONS********
  
 1.)SIGN THE OWNER/AGENT LINE ON THE
 ENERGY CALC.
  
 2.)PROVIDE A COPY OF THE SURVEY
 REFERRED TO ON THE PLAN WITH ELEVATIONS,
 IF AVAILABLE.
  
 3.)THE AREA TABULATIONS (A2) SHOULD
 INCLUDE EXISTING AREAS, PROPOSED, AND
 NEW TOTALS.
  
 4.)THIS PROPERTY IS IN A FLOOD ZONE.
 THE FINISHED FLOOR ELEVATION IS
 REQUIRED TO BE 6" ABOVE THE BASE FLOOD
 ELEVATION (7'), CITY OF WEST PALM BEACH
 MUNICIPAL CODE 95-546.
  
 5.)ADDITIONAL FEES DUE, $543.97.
  
 6.)THE WINDOW AT THE SHOWER MUST
 COMPLY WITH FBC 2405.2.
  
 7.)THE ROOF SHEATHING (FOYER SECTION,
 A3, WALL SECTION A5) MUST COMPLY WITH
 CITY OF WEST PALM BEACH AMENDMENT TO
 THE FBC, TABLE 2306.1, ATTACHED.
  
 8.)THE SOFFIT VENTING IS REQUIRED
 TO COMPLY WITH FBC 2309.7, CANNOT
 "MATCH EXISTING" (FOYER SECTION, A3).
  
 9.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 10.) ATTIC ACCESS REQUIRED, FBC2309.
  
 11.)PROVIDE A DETAIL FOR THE NEW
 FRAME WALL (A2 FLOOR PLAN).INSULATION
 IS REQUIRED BETWEEN CONDITIONED AND
 NON-CONDITIONED SPACE.
  
 12.)S2, ROOF FRAMING PLAN, SHOWS
 ATTACHMENT D, TARGET UPLIFT 2230 WHICH
 EXCEEDS THE MAX UPLIFT OF 1845 ON THE
 TRUSS ANCHOR SCHEDULE.
  
 13.)ATTACHMENTS F AND H, ROOF FRAMING
 PLAN (S3), ARE NOT LISTED ON THE
 ANCHOR SCHEDULE.
  
 14.)SHOW THE SOUTH PROPERTY LINE ON
 THE FOUNDATION PLAN.THE FOOTER FOR THE
 PRIVACY WALL CANNOT ENCROACH THE
 PROPERTY LINE.
  
 15.)SUBMIT TWO LEGIBLE COPIES OF THE
 FOLLOWING PRODUCT APPROVALS:
 FIXED GLASS WINDOW
 CASEMENT
 MULLION
 FRENCH DOORS
 SIDELITS
 GARAGE DOOR
 ROOF SHINGLES
 IMPACT PROTECTION

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-07-18 Cont ID  
Sent By dpalmer Date 2003-07-18 Time 06:09 Rev Time 0.33
Received By dpalmer Date 2003-07-18 Time 06:09 Sent To P
Notes
2003-07-18 00:00:00LPLANS REDLINED BY ENG/ARCH FOR RECEPT
 SPACING.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-06-24 Cont ID  
Sent By shernand Date 2003-07-17 Time 11:05 Rev Time 1.00
Received By dpalmer Date 2003-06-24 Time 15:24 Sent To B
Notes
2003-06-24 00:00:00**************** UNSAT ***************
  
 PLEASE SEE NOTES FROM FIRST REVIEW.
 NOTE #`S 4 AND # 5 ARE STILL OUTSTANDING
  
 1)NOTE: PLEASE SEE MISSING RECEPTS PER
 210-52
  
 2)NOTE: PLEASE SEE CHAPTER 34 FBC FOR
 ADDTIONS. 3401.7.1.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-06-18 Time 16:08 Rev Time 0.75
Received By dpalmer Date 2003-05-15 Time 06:47 Sent To P
Notes
2003-05-15 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SEE MEANS OF EGRESS LT
 CONTROL FROM REC RM DOOR TO OUTSIDE
 WALK. S-4? TO BE ADDED? 210-70
  
 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE
 210-12
  
 3)NOTE: PLEASE LIST THE REQ`D BATH CIR-
 -CUIT ON PANEL SCHEDULE 210-52D/210-11C3
 #12,20A
  
 4)NOTE: PLEASE SEE A COUPLE OF RECEPTS
 MISSING TO MEET 210-52/ OFFICE AND NEW
 BEDROOM.
  
 5)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDITIONS TO EXISTING STRUCTURES. THE
 SQ FT BEING ADDED EXCEEDS % 3401.7.1.1
 PLEASE SHOW / CLARIFY ORIG ELECTRICAL
 AS EXISTING AND THAT IT MEETS CURRENT 99
 NEC FOR ELECTRICAL REQ`MENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE TAKE OUT ANY OLD/VOIDED
 SHEETS AND INSERT NEWSHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-06 Time 11:02 Rev Time 0.00
Received By btrobaug Date 2003-05-14 Time 17:14 Sent To P
Notes
2003-05-14 00:00:00SENT TO PLUMBING,ON VACATION./WRT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-17 Cont ID  
Sent By shernand Date 2003-07-17 Time 11:05 Rev Time 0.00
Received By shernand Date 2003-07-17 Time 11:05 Sent To E
Notes
2003-07-17 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-18 Cont ID  
Sent By shernand Date 2003-06-18 Time 16:08 Rev Time 0.00
Received By shernand Date 2003-06-18 Time 16:08 Sent To E
Notes
2003-06-18 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-06 Cont ID  
Sent By shernand Date 2003-05-06 Time 11:02 Rev Time 0.00
Received By shernand Date 2003-05-06 Time 11:02 Sent To E
Notes
2003-05-06 00:00:00BT DESK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-20 Cont ID  
Sent By kstevens Date 2003-05-19 Time 18:33 Rev Time 0.30
Received By pkrauss Date 2003-05-20 Time 13:34 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-23 Cont ID  
Sent By kstevens Date 2003-07-23 Time 18:32 Rev Time 0.33
Received By kstevens Date 2003-07-23 Time 18:32 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-05-19 Cont ID  
Sent By dpalmer Date 2003-07-18 Time 06:16 Rev Time 0.33
Received By kstevens Date 2003-05-19 Time 18:33 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-06 Cont ID  
Sent By sgraham Date 2003-05-06 Time 10:52 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***