| 2003-06-16 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-PROVIDE COMPLETE BULDING SECTION THRU |
| | FRAMED WALLS AT SECOND FLOOR. SPECIFY |
| | ALL FASTENERS TOP AND BOTTOM. |
| | **NOTE: STUCCO TO BE 7/8" MIN. AS PER |
| | ASTM C-926. |
| | 2-GLASS BLOCK AT BATH TUB AREA TO BE |
| | SAFETY GLASS IF FACE THICKNESS IS LESS |
| | THAN 0.25". SEC. 2405.2 FBC 2001. |
| | 3-PROVIDE GENERAL SPECIFICATIONS FOR |
| | FIREBLOCKING AT ALL CONCEALED SPACES, |
| | NOT JUST THE UNDERSIDE OF STAIRS. SEE |
| | SEC. 2305 FBC 2001. |
| | 4-REVISE ENERGY CALCULATIONS: A)OWNER |
| | INFORMATION IS NOT CORRECT. |
| | B)COMPLETE HOUSE ADDRESS. ETC. |
| | |
| | 5-PRODUCT APPROVAL FOR ALUMINUM MULLIONS |
| | IS EXPIRED. RESUBMIT CURRENT ONE. |
| | 6-PROVIDE SOIL TEST REPORT PRIOR TO |
| | CONTRUCTION. |
| | 7-SPECIFY CONNECTOR FOR TRUSS ON DETAIL |
| | 1/S2. SEC. 104.2.1.2 CITY AMENDMENTS |
| | 8-CLARIFY EXTERIOR STUCCO SOOFIT SPECS. |
| | ON SHEET A-5. NOTES ARE NOT CLEAR AND |
| | SOME ARE REPETITIVE. REVISE AS REQ'D. |
| | SEE ASTM C-926 AND ASTM C-1063. |
| | 9-THERE ARE SOME CONNECTORS MISSING. SEE |
| | COMMENTS ON PLANS. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 10-UPDATE ALL TRUSS ANCHOR AND DETAILS |
| | THAT ARE AFFECTED BY SEC. 1609.4.3 |
| | FBC 2001, WHICH DOESN'T ALLOW THE |
| | ALLOWABLE STRESS INCREASE TO BE USED. |