Plan Review Details - Permit 03050250
Plan Review Stops For Permit 03050250
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-25 Cont ID  
Sent By jwitmer Date 2003-08-25 Time 14:26 Rev Time 1.75
Received By jwitmer Date 2003-08-25 Time 14:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-06 Cont ID  
Sent By jleech Date 2003-08-20 Time 18:47 Rev Time 1.75
Received By jwitmer Date 2003-08-06 Time 12:52 Sent To  
Notes
2003-08-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03050250
 ADD: 8013 CRANES POINTE WAY
 CONT: SHELDON FRIEFELD INC
 TEL: (561)722-5078
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 NOTE: ABOUT THE FOUNDATION LOCATED NEXT
 TO THE POOL!
 1803.1.3 EXCAVATION FOR ANY PURPOSE
 SHALL NOT EXTEND WITHIN 1 FT OF THE
 ANGLE OF REPOSE OR NARURAL SLOPE OF THE
 SOIL UNDER ANY FOOTING OR FOUNDATION,
 UNLESS SUCH FOOTING OR FOUNDATION IS
 FIRST PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT.
  
 ACTION: DENIED
  
 1FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL I
 S NOT DEFINITEY KNOWN, OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL P
 ROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 3) 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORT:
 A) CASEMENT WINDOW- BEDROOM# 2
  
 5) 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 SHEET A5 TRUSS ANCHOR SCHEDULE:
 SHA6 3 PLY GIRDER GOOD FOR 3580
 RT24T GOOD FOR 1125
  
 SHEET A-6 DELETE ALL NOTES FOR HUGHES &
 SEMCO PRODUCTS, NO LONGER AVAILABLE!!!!
 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
  
 6)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-20 Cont ID  
Sent By dpalmer Date 2003-08-20 Time 16:45 Rev Time 0.25
Received By dpalmer Date 2003-08-20 Time 16:45 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-25 Cont ID  
Sent By csiegber Date 2003-08-20 Time 11:05 Rev Time 0.50
Received By dpalmer Date 2003-07-25 Time 08:06 Sent To P
Notes
2003-07-25 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE SEE ATTACHED COPY OF
 FAC 61G1-16.004. PLEASE INCLUDE ALL
 INFORMATION ON TITLE BLOCK.
  
 2)NOTE: PLEASE SEE SIZING OF GROUNDING
 ELECTRODE CONDUCTOR. IT APPEARS TO HAVE
 CONDUCTOR SIZE REVERSED FOR CWP AND MAIN
 GROUNDING ELECTRODE CONDUCTOR.
 250.66/ 310.15
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-20 Cont ID  
Sent By csiegber Date 2003-08-20 Time 11:05 Rev Time 0.00
Received By csiegber Date 2003-08-20 Time 11:04 Sent To E
Notes
2003-08-20 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-10 Cont ID  
Sent By mmclean Date 2003-07-15 Time 12:58 Rev Time 0.00
Received By shernand Date 2003-07-10 Time 16:53 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-16 Cont ID  
Sent By pkrauss Date 2003-07-16 Time 07:29 Rev Time 0.30
Received By pkrauss Date 2003-07-16 Time 07:11 Sent To E
Notes
2003-07-16 00:00:00MECHANICAL PERMIT 03070701

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-08-20 Cont ID  
Sent By jleech Date 2003-08-20 Time 18:47 Rev Time 0.33
Received By jleech Date 2003-08-20 Time 18:47 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-31 Cont ID  
Sent By dpalmer Date 2003-08-20 Time 16:46 Rev Time 0.50
Received By kstevens Date 2003-07-31 Time 07:04 Sent To B
Notes
2003-07-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA STATUTES
  
 1) WASH MACHINE REQUIRES A TRAP AND A
 STANDPIPE. SECTION 1002.1 SECTION802.4
 2) BATH #4 NOT VENTED ON SANITARY RISER
 DIAGRAM.
 3) TITLE BLOCK FOR ARCHITECTS. SEE
 ATTACHED SHEET FOR REQUIREMENTS PER
 61G1-16.004 - NO LICENSE SHOWN
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-15 Cont ID  
Sent By shernand Date 2003-07-10 Time 16:53 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***