Plan Review Details - Permit 03050148
Plan Review Stops For Permit 03050148
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-10-13 Cont ID  
Sent By shill Date 2004-10-13 Time 12:03 Rev Time 0.50
Received By shill Date 2004-10-13 Time 12:03 Sent To  
Notes
2004-10-13 00:00:00REVISED ADT1

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-07-27 Cont ID  
Sent By shill Date 2004-07-27 Time 17:29 Rev Time 0.50
Received By shill Date 2004-07-27 Time 17:08 Sent To  
Notes
2004-07-27 00:00:00REVISED A-T3.4 ADDRESSING PROVISO RE
 FASTENERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-06-23 Time 11:14 Rev Time 1.00
Received By shill Date 2004-03-01 Time 15:34 Sent To  
Notes
2004-03-01 00:00:00**PROVISO**
 1. PROVIDE ENGINEERING FOR JAMERCO
 FASTENERS.
 2. SEPARATE PERMIT REQUIRED FOR SHUTTERS
 WINDOWS & DOORS.
 FOR PRODUCT APPROVALS SEE 03050145
 SEE CBAA CASE #1239

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-02-28 Cont ID  
Sent By shill Date 2004-02-28 Time 12:58 Rev Time 4.00
Received By shill Date 2004-02-27 Time 14:42 Sent To P
Notes
2004-02-28 00:00:00SEE COMMENTS FOR 03050145

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-02 Cont ID  
Sent By shill Date 2004-01-02 Time 16:48 Rev Time 1.00
Received By shill Date 2004-01-02 Time 16:48 Sent To  
Notes
2004-01-02 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 SAME CORRECTIONS AS #03050145, SEE
 ATTACHED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-08 Cont ID  
Sent By csiegber Date 2003-12-01 Time 11:26 Rev Time 1.50
Received By shill Date 2003-12-03 Time 16:39 Sent To Z
Notes
2003-12-03 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 1.)THE FOLLOWING PAGES ARE NOT IN THE
 MASTER:
 ET3.3A
 MES 1
 MS 1
  
 THE FOLLOWING PAGES DO NOT MATCH THE
 MASTER:
 SP2.1
 SP5
 ES1
 EU2
 EU4
 EU6
 E T3.2
 E T3.3
 PU4
 PU5
 FP2
 FP3
 FP4
  
 SUBMIT PLANS WHICH MATCH THE MASTER OR
 THE PLANS WILL REQUIRE PLAN REVIEW.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.)THE NOTICE OF COMMENCEMENT WILL
 EXPIRE ON 12/19/03.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-25 Cont ID  
Sent By dpalmer Date 2004-02-25 Time 16:47 Rev Time 1.50
Received By dpalmer Date 2004-02-25 Time 15:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-17 Cont ID  
Sent By dpalmer Date 2003-12-17 Time 06:32 Rev Time 2.00
Received By dpalmer Date 2003-12-17 Time 06:31 Sent To  
Notes
2003-12-17 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE SEE WIND LOADING ON POLES
 SHOWN AT 120 MPH, SHOULD BE 140.
 PLEASE SEE FBC.
  
 2)NOTE: PLEASE SEE THAT PLANS ARE REQ'D
 TO BE SIGNED WITH FULL SIGNATURE FROM
 ENGINEER OF RECORD.FS 471.025 AND FAC
 61G15-23.002.
 THIS OFFICE HAS BEEN NOTIFIED THAT
 INITIALS ARE NOT ACCEPTABLE AND MUST
 HAVE SIGNATURE AS LICENSED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-12-08 Cont ID  
Sent By mamini Date 2003-12-08 Time 15:16 Rev Time 1.00
Received By mamini Date 2003-12-08 Time 15:16 Sent To  
Notes
2003-12-08 00:00:00PASSED:
 1. SEE PERMIT # 03101018 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-13 Cont ID  
Sent By mcarsill Date 2004-02-13 Time 14:14 Rev Time 0.00
Received By mcarsill Date 2004-02-13 Time 14:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-12-12 Cont ID  
Sent By mcarsill Date 2003-12-12 Time 14:17 Rev Time 0.00
Received By mcarsill Date 2003-12-12 Time 14:17 Sent To  
Notes
2003-12-12 00:00:001) FIRE SPRINKLERS SHALL BE INSTALLED
 IN ELECTRIC AND CABLE TV CLOSETS.
  
 2) FDC SHALL BE 2 1/2" NOT 1 1/2" AS
 SHOWN FOR BUILDINGS 1 AND 2 FDC DETAIL
 SHOWN ON FP-2.
  
 3) THE FLOW TEST NOTED WITH PLANS
 IS OVER ONE YEAR OLD. 11.7.02.
  
 4) BREEZEWAY WALLS ARE TWO HOUR FIRE
 RATED WITH C LABEL FIRE DOORS. PLEASE
 EXPLAIN RATIONALE.
  
 5) THE BUILDING PLAN REVIEWER NOTED
 SOME MISSING PAGES TO THE PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-06-23 Time 11:14 Rev Time 0.00
Received By csiegber Date 2004-06-23 Time 11:14 Sent To B
Notes
2004-06-23 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-12 Cont ID  
Sent By csiegber Date 2004-02-12 Time 16:11 Rev Time 0.00
Received By csiegber Date 2004-02-12 Time 16:11 Sent To  
Notes
2004-02-12 00:00:00TO COMM BD #28/PLANS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-11 Cont ID  
Sent By csiegber Date 2003-12-11 Time 15:10 Rev Time 0.00
Received By csiegber Date 2003-12-11 Time 15:10 Sent To  
Notes
2003-12-11 00:00:00TO COMM BD#38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-01 Cont ID  
Sent By mmclean Date 2003-12-11 Time 09:11 Rev Time 0.00
Received By csiegber Date 2003-12-01 Time 11:26 Sent To B
Notes
2003-12-01 00:00:00TO ST DESK/SUBMITTAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-25 Cont ID  
Sent By pkrauss Date 2004-02-25 Time 10:49 Rev Time 0.55
Received By pkrauss Date 2004-02-25 Time 09:46 Sent To  
Notes
2004-02-25 00:00:00PROVISO:
 THE FOLLOWING ITEMS HAVE CHANGED WITH
 THE REVISED 2001 FBC(M), EFFECTIVE JUNE
 30, 2003:
  
 1.PER 2001 FBC(M) 403.3, VENTILATION
 SYSTEMS OTHER THAN R-3(ONE/TWO FAMILY),
 SHALL COMPLY WITH THE MINIMUM
 REQUIREMENTS SET FORTH IN TABLE 403.3.
 PLEASE REVISE PLANS TO REFLECT THIS
 REQUIREMENT.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-17 Cont ID  
Sent By pkrauss Date 2003-12-17 Time 16:49 Rev Time 1.20
Received By pkrauss Date 2003-12-17 Time 16:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-03-01 Cont ID  
Sent By shill Date 2004-02-28 Time 12:59 Rev Time 2.50
Received By kstevens Date 2004-02-20 Time 16:39 Sent To  
Notes
2004-02-20 00:00:00 
  
  
  
 PASSED/PROVISO
 ACCORDING TO SIZING FORMULA FOR WATTS
 EXPANSION TANKS, THE SIZE FOR THE EX-
 PANSION TANK IS INSUFFICIENT FOR THE
 AMOUNT OF GALLONS TOTALED FOR ALL W/H'S
 (SEE ATTACHED SHEETS). THIS SHALL BE
 ADDRESSED BY PLUMBING FINAL.
  
  
  
  
  
  
  
  
  
 Z

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-16 Cont ID  
Sent By kstevens Date 2003-12-16 Time 09:46 Rev Time 1.50
Received By kstevens Date 2003-12-16 Time 09:46 Sent To  
Notes
2003-12-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) SHTS P-U1 THRU P-U6 WATER RISER DIA-
 GRAMS, A WATER HAMMER ARRESTOR IS REQ-
 UIRED FOR THE ICE MAKER LINE TO THE REF-
 RIDGEERATOR. (NOT IN CEILING-PDI-WH 201
 AND MANUF. INSTALL. INSTRUCT. 604.9)
 2) SHT P-T3.3 THERMAL EXPANSION CONTROL
 NOT PROPERLY ADDRESSED WITH THE 3/4"
 VALVE AT THE BACKFLOW. 607.3.2
 3) ENGINEERS SHALL SUBMIT SIGNATURE ON
 SEAL. FAC 61G15-23.002(1) & FS 471.025.
 INITIALS NOT ACCEPTABLE PER FBPE AND
 BLDG OFFICIAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2004-03-01 Cont ID  
Sent By shill Date 2004-03-01 Time 15:35 Rev Time 1.00
Received By shill Date 2004-03-01 Time 15:35 Sent To  
Notes
2004-03-01 00:00:00PER E.SCHNEIDER

Review Stop Z ZONING
Rev No 2 Status F Date 2004-02-27 Cont ID  
Sent By shill Date 2004-02-27 Time 14:31 Rev Time 0.50
Received By shill Date 2004-02-27 Time 14:31 Sent To  
Notes
2004-02-27 00:00:00PER E.SCHNEIDER
  
 NEEDS TO SHOW BUILDING SETBACKS.

Review Stop Z ZONING
Rev No 1 Status F Date 2003-12-11 Cont ID  
Sent By shill Date 2003-12-08 Time 11:56 Rev Time 0.00
Received By mmclean Date 2003-12-11 Time 09:11 Sent To I
Notes
2003-12-11 00:00:00DENIED, NEED UNITY OF TITLE PER ERIC
 SCHNEIDER SENIOR PLANNER EXT 8463 MM