Plan Review Details - Permit 03050122
Plan Review Stops For Permit 03050122
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-08-13 Cont ID  
Sent By pkrauss Date 2003-08-14 Time 07:38 Rev Time 1.50
Received By sthyng Date 2003-08-13 Time 13:49 Sent To  
Notes
2003-08-13 00:00:00PINK SLIP ON FRONT OF PKG, NEEDS CITY
 COPY OF ENERGY CALC SIGNED ON OWNER/
 AGENT LINE
  
 SENT TO DP DESK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-07-18 Cont ID  
Sent By alange Date 2003-08-13 Time 08:52 Rev Time 1.50
Received By sthyng Date 2003-07-12 Time 17:21 Sent To M
Notes
2003-07-12 00:00:00*****CORRECTIONS******
  
 1.)MECHANICAL WORK WAS ADDED TO THE
 PLAN IN INK.ALL CHANGES TO A SEALED
 DRAWING MUST BE INITALED AND DATED BY
 THE ENGINEER.
  
 2.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 3.)FIRESTOP REQUIRED, FBC 705.3.
  
 4.)INSULATION WAS PUT ON THE PLAN
 WITH WHITE OUT.ALL CHANGES TO THE
 PLAN MUST BE INITIALED AND DATED BY
 THE ENGINEER.
  
 5.)THE CONNECTION SPECIFIED FROM THE
 TIE BEAM TO THE WOOD BEAM SPECIFIES
 16-10DX1.ACCORDING TO THE SIMPSON
 2003 CATALOG, THE NAIL LENGTH IS
 REQUIRED TO BE 1 1/2.
  
 6.)SEE THE PREVIOUS CORRECTION LIST,
 #7.GIVE EXISTING ATTACHMENTS WITH
 UPLIFT INFORMATION.
  
 7.)THE INTERNAL PRESSURE COEFFICIENT
 IN THE WIND INFORMATION SECTION OF THE
 PLAN IS INCORRECT.A COEFFICIENT IS
 A NUMBER.
  
 8.)THE ROOF TRUSS LOAD (WIND
 INFORMATION) STATES "PER TRUSS
 ENGINEERING".THERE AREN'T ANY
 TRUSSES IN THIS DESIGN.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-05-31 Cont ID  
Sent By shernand Date 2003-07-11 Time 15:11 Rev Time 0.25
Received By sthyng Date 2003-05-31 Time 19:39 Sent To  
Notes
2003-05-31 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 SEE THE PREVIOUS CORRECTION NOTICE.
 IMPACT FEES WERE PAID, A NOC IS IN THE
 PACKAGE, BUT THE STRUCTURAL COMMENTS
 WERE NOT ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-23 Cont ID  
Sent By shernand Date 2003-05-30 Time 14:21 Rev Time 1.50
Received By sthyng Date 2003-05-23 Time 19:29 Sent To  
Notes
2003-05-23 00:00:00******CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE ORIGINAL RECEIPT
 ATTACHED TO THE APPLICATION.233-5025
  
 3.)SEPARATE PERMITS REQUIRED.
  
 4.)ADDITIONAL FEES REQUIRED.
  
 5.)ENERGY CALCS REQUIRED FBC 13-101.2.
  
 6.)SPECIFY INSULATION.
  
 7.)HOW WILL THE WALL SECTION BE
 STRUCTURALLY CONTINUOUS?NO ATTACHMENTS
 ARE SHOWN.GIVE EXISTING ATTACHMENTS
 WITH UPLIFT INFORMATION, AND PROPOSED
 ATTACHMENTS.IS THE WOOD BEAM PRESSURE
 TREATED?HOW WILL THE TIE BEAM UNDER
 THE WOOD BEAM, WITH NO WEIGHT BEARING
 ON THE TIE BEAM, BE STRUCTURALLY
 CONTINUOUS?
  
 8.)SEMCO ATTACHMENTS ARE NOT
 AVAILABLE.SPECIFY ANOTHER BRAND WITH
 UPLIFT.ALL ATTACHMENTS SHOWN SHOULD
 SHOW UPLIFT.
  
 9.)SHOW THE 12" BELOW GRADE, 4" ABOVE
 GRADE FOR THE FOUNDATION REQUIRED BY
 CODE ON THE WALL SECTION, FBC1804.1.3.
  
 10.) GIVE A SOFFIT VENT SCHEDULE.
 CANNOT "MATCH EXISTING" AS THE EXISTING
 MIGHT NOT COMPLY WITH FBC 2309.7.
  
 11.) SUBMIT PRODUCT APPROVALS FOR
 THE SINGLE HUNG WINDOWS, IMPACT
 PROTECTION, AND THE DOOR (2 LEGIBLE
 COPIES EACH).

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-14 Cont ID  
Sent By dpalmer Date 2003-08-14 Time 05:59 Rev Time 0.25
Received By dpalmer Date 2003-08-14 Time 05:59 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-06 Cont ID  
Sent By dpalmer Date 2003-05-06 Time 18:57 Rev Time 0.25
Received By dpalmer Date 2003-05-06 Time 18:57 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-08-13 Cont ID  
Sent By alange Date 2003-08-13 Time 08:52 Rev Time 0.00
Received By alange Date 2003-08-13 Time 08:52 Sent To B
Notes
2003-08-13 00:00:00TO STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-11 Cont ID  
Sent By dbaxter Date 2003-08-11 Time 16:25 Rev Time 0.00
Received By dbaxter Date 2003-08-11 Time 16:25 Sent To B
Notes
2003-08-11 00:00:00TO STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 15:11 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 15:11 Sent To B
Notes
2003-07-11 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-30 Cont ID  
Sent By shernand Date 2003-05-30 Time 14:21 Rev Time 0.00
Received By shernand Date 2003-05-30 Time 14:21 Sent To B
Notes
2003-05-30 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-05 Cont ID  
Sent By sgraham Date 2003-05-06 Time 10:30 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 11:46 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-08-14 Cont ID  
Sent By pkrauss Date 2003-08-14 Time 07:38 Rev Time 0.15
Received By pkrauss Date 2003-08-14 Time 07:38 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-17 Cont ID  
Sent By dpalmer Date 2003-08-14 Time 05:59 Rev Time 0.20
Received By pkrauss Date 2003-07-17 Time 11:12 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-06 Cont ID  
Sent By shernand Date 2003-05-05 Time 11:46 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***