Plan Review Details - Permit 03050069
Plan Review Stops For Permit 03050069
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-12 Cont ID  
Sent By sthyng Date 2003-06-12 Time 17:50 Rev Time 4.00
Received By sthyng Date 2003-06-11 Time 17:47 Sent To  
Notes
2003-06-12 00:00:00******CORRECTIONS********
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE AWNING IS NOT ON THE SITE PLAN,
 ONLY ON THE ELEVATIONS.PROVIDE A
 DETAIL AND ALL DIMENSIONS FOR THE
 AWNING, PROVIDE ON THE SITE PLAN.THIS
 REQUIRES ZONING APPROVAL.
  
 2.)REGARDING THE CONVERSION OF THE
 HOBBY ROOM TO A BEDROOM, THE HEIGHT OF
 THE WINDOW APPEARS TO BE 51" HIGH.A
 51" HIGH SINGLE HUNG WINDOW DOES NOT
 MEET EGRESS REQUIREMENTS, FBC1005.4.
  
 3.)THIS ADDITION IS AN IMPROVEMENT OF
 GREATER THAN 25% OF THE EXISTING
 SQUARE FOOTAGE AND MUST COMPLY WITH
 FBC 3401.7.1.2.SHOW EGRESS AND SMOKE
 DETECTORS FOR EXISTING BEDROOMS AND A
 BATHROOM WITH A 29" DOORWAY CLEARANCE,
 FBC 1005.4, FBC11-11(1).
  
 4.)WHEN RESUBMITTING, NUMBER EACH
 PAGE AND SUBMIT A LISTING OF THE
 CORRECTIONS.INDICATE HOW EACH ITEM
 WAS ADDRESSED, REFERRING TO A PAGE
 NUMBER.CLEARLY CLOUD ALL CHANGES.
  
 5.)ADDITIONAL PERMITS REQUIRED; SEE
 ATTACHED WORKSHEET REGARDING VALUE
 ADJUSTMENT; $1102.29.
  
 6.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 7.)ENERGY CALCS REQUIRED FBC13-101.2.
  
 8.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE ORIGINAL PLANS MUST
 BE STAMPED AND THE RECEIPT ATTACHED.
 233-5025
  
 9.)SPECIFY SLOPE OF THE FLAT DECK.
  
 10.) SHOW CRAWL SPACE VENTILATION.
  
 11.)DESIGN INFORMATION REQUIRED TO BE
 ON THE PLAN; FBC 1606.1.7.
  
 12.)SHOW ATTIC ACCESS SIZE FBC 2309.
  
 13.)PROVIDE WALL HEIGHT DIMENSIONS.
  
 14.)PROVIDE CALCULATIONS TO SHOW
 COMPLIANCE WITH TABLE 600 WHERE THE TWO
 BUILDINGS ARE 14'7" APART.
  
 15.)PROVIDE TWO LEGIBLE, COMPLETE
 COPIES OF PRODUCT APPROVALS FOR:
 WINDOWS
 SINGLE DOOR
 LOUVERED DOOR
 DOUBLE DOORS
 IMPACT PROTECTION
 ROOF SHINGLES
  
 16.)IMPACT PROTECTION REQUIRED FOR
 WINDOWS FBC 1606.1.4.ALSO PROVIDE A
 HURRICANE SHUTTER INSTALLATION SCHEDULE,
 ATTACHED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-10 Cont ID  
Sent By shernand Date 2003-06-09 Time 15:05 Rev Time 0.75
Received By btrobaug Date 2003-06-10 Time 10:19 Sent To P
Notes
2003-06-10 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 1} SHOW HOW THE NEW PANEL COMPLIES WITH
 250-32,225-31 NEC,AND 230-70 CWPB
 AMMENDMENTS.
  
 2} THE LOAD CALCULATIONS ARE INCOMPLETE.
 ON THE PLAN THERE ARE 2 AIR
 CONDITIONERS AND A WELDER THAT DO NOT
 APPEAR IN THE CALCULATION.PLEASE
 PROVIDE PANEL SCHEDULES FOR THE SERVICE
 EQUIPMENT.
  
 3} THE APPLICATION INDCATES THERE IS TO
 BE A HOBBY ROOM CHANGED INTO A BEDROOM.
 PLEASE CLARIFY THAT AREA ON THE PLAN.
 ALSO INDICATE COMPLIANCE WITH 210-12.
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.GFI PER 210-8.
  
 5} PLEASE NOTE THAT AN ELECTRICAL PERMIT
 IS REQUIRED FOR THIS PROJECT AND NONE
 WAS APPLIED FOR.AN ELECTRICAL PERMIT
 MUST BE OBTAINED PRIOR TO COMMENCING
 ANY ELECTRICAL WORK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-09 Cont ID  
Sent By shernand Date 2003-06-09 Time 15:03 Rev Time 0.00
Received By shernand Date 2003-06-09 Time 15:03 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-02 Cont ID  
Sent By mmclean Date 2003-06-09 Time 12:26 Rev Time 0.00
Received By shernand Date 2003-06-02 Time 13:34 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 11:44 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 11:44 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By btrobaug Date 2003-06-10 Time 10:51 Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-06-09 Cont ID  
Sent By mmclean Date 2003-06-09 Time 12:25 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-05-06 Cont ID  
Sent By shernand Date 2003-06-02 Time 13:34 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-05-06 00:00:00DENIED, NEED A CLEAR SITE PLAN SHOWING
 ALL ADDITIONS TO SCALE