Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-07-10 Cont ID  
Sent By jgomez Date 2003-07-10 Time 16:55 Rev Time 2.50
Received By jgomez Date 2003-07-10 Time 16:54 Sent To PC
Notes
2003-07-10 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS UNDER A SEPARATE
 PERMIT APPLICATION.
 2-REVISE FOOTING AT REAR PORCH COLUMN,
 WHICH IS ENCROACHING INTO NEIGHBOR'S
 PROPERTY.
 3-PROVIDE REVISED DETAIL FOR AIR HANDLER
 UNIT ATTACHED TO WALL. SHOW ALL REQ'D
 CLEARANCES. CLARIFY HOW IS THE UNIT
 REINFORCED TO BE WALL MOUNTED AND HOW
 IS VIBRATION TAKEN CARE OF. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 4-PROVIDE COMPLETE DETAIL/SPECS FOR
 INSTALLATION OF CEILING AT FRONT AND
 REAR PORCH. SPECIFY ALL MATERIALS,
 FASTENERS AND SPACING. SEE ASTM C926
 AND ASTM C1063.
 5-PROVIDE COMPLETE GABLE END DETAIL.
 SPECIFY EMBEDED ANCHOR AND SPACING.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-UPDATE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOESN'T ALLOW
 THE STEEL STRESS TO BE INCREASED.
 **NOTE: SEE SIMPSON HIGH WIND-RESISTANT
 CONSTRUCTION CATALOGUE BECAUSE IS THE
 ONLY ONE THAT HAS BEEN REVISED TO
 REFLECT THIS CHANGE.
 7-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 ENTRY DOORS AND FIXED WINDOWS AS REQ'D
 ON THE PRODUCT APPROVALS. ALSO, SEE
 SECTION 1707.4.4.2 FBC 2001 FOR
 REQUIREMENTS ON BUCK INSTALLATION.
 8-PROVIDE PRODUCT APPROVAL FOR:
 A)FIXED WINDOW WITH SIZES AS SHOWN ON
 PLANS ABOVE SLIDING GLASS DOOR IN THE
 GREAT ROOM AREA.
 B)GLASS BLOCK WITH LEGIBLE DRAWINGS.
 C)LEGIBLE DRAWINGS FOR ENTRY DOOR WITH
 RENEWAL STAMP BY DADE COUNTY.
  
 9-SPECIFY SAFETY GLASS FOR GLASS BLOCK
 AT TUB AREA IF FACE THICKNESS IS LESS
 THAN 0.25". SEC. 2405.2 FBC 2001.
  
 NOTE:
 PLEASE CLOUD ALL REVISIONS TO EXPEDITE
 THE REVIEW PROCESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-07-07 Cont ID  
Sent By jgomez Date 2003-07-07 Time 12:56 Rev Time 3.00
Received By jgomez Date 2003-07-07 Time 12:56 Sent To PC
Notes
2003-07-07 00:00:00BULDING REVIEW 2ND CHECKLIST:
 1-PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND RECEIPT.
 2-WILL NEED TO RECORD A NOTICE OF
 COMMENCEMENT.
 3-FOOTING PAD AT REAR PORCH COLUMN IS
 ENCROACHING INTO NEIGHBOR'S PROPERTY.
 REVISE AS REQUIRED.
 4-AIR HANDLING UNIT HANGING DETAIL:
 A)DOESN'T PROVIDE THE CLEARANCES REQ'D
 BY SEC. 603.1.3 MECHANICAL FLORIDA
 BUILDING CODE 2001.
 B)IS UNIT BUILT TO BE HANGED FROM SIDE
 WALL OF UNIT?. IS IT REINFORCED?.
 PROVIDE MANUFACTURER'S INFORMATION
 THAT SHOWS THIS TYPE OF INSTALLATION.
 C)HOW IS VIBRATION TAKEN CARE OF.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 5-PROVIDE COMPLETE DETAILS/SPECS FOR
 INSTALLATION OF CEILING AT FRONT AND
 REAR PORCH. SPECIFY MATERIALS,FASTENER
 TYPE AND SPACING. SEE ASTM C-926 AND
 ASTM C-1063.
 6-PROVIDE COMPLETE DETAIL FOR GABLE END.
 NEED TO SPECIFY TRUSS ANCHOR & SPACING
 SEE SEC. 2117 FBC 2001.
 7-UPDATE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001. SEE SIMPSON HIGH
 WIND-RESISTANT CONSTRUCTION CATALOGUE
 WHICH HAS THE REVISED VALUES.
 8-PROVIDE STRUCTURAL 2X BUCK DETAIL FOR
 ENTRY DOORS AND FIXED WINDOWS AS REQ'D
 ON THE PRODUCT APPROVALS. ALSO, SEE
 SEC. 1707.4.4.2 FBC 2001 FOR SPECIFIC
 BUCK INSTALLATION REQUIREMENTS.
 9-PROVIDE PRODUCT APPROVAL FOR:
 A)FIXED WINDOW WITH SIZE AS SHOWN ABOVE
 SLIDING GLASS DOORS AND ABOVE WINDOW
 IN THE GREAT ROOM AREA.
 B)GLASS BLOCK WITH LEGIBLE DRAWINGS.
 C)LEGIBLE DRAWINGS FOR ENTRY DOOR WITH
 RENEWAL STAMP BY DADE COUNTY.
  
 10-REVISE STORM SHUTTERS INFORMATION:
 A)REVISE MEAN ROOF HEIGHT AND DESIGN
 PRESSURES.
 B)REVISE MINIMUM AND MAX PANEL SPAN.
 SEE ENGINEERED DRAWINGS.
 C)INSTALLATION SCHEDULE: SPECIFY ANCHOR.
 D)DESIGN PRESSURES ARE MEASURED BY PSF
 NOT PSI.
 E)ADDITIONAL ENGINEERED DRAWINGS ARE NOT
 ALLOWED TO BE USED, UNLESS THEY ARE
 PART OF THE PRODUCT APPROVAL APPROVED
 BY SBCCI.
 F)CLEARLY MARK ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS, AND ANCHOR TYPE
 TO BE USED ACCORDING TO THE DESIGN
 PRESSURES, EDGE DISTANCE, PANEL SPAN,
 CONNECTION TYPE AND STRUCTURE TO BE
 ATTACHED TO. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 11-CONTRACTOR TO UPDATE INSURANCE. SEE
 CLERK TO UPDATE INFORMATION.
 12-SPECIFY SAFETY GLASS FOR GLASS BLOCK
 AT TUB IF FACE THICKNESS IS LESS THAN
 0.25". SEC. 2405.2 FBC 2001.
 13-OWES $104.10 FOR UPDATED VALUATION
 AND RADON FEES.
 14-PLEASE CLOUD ALL CHANGES IN THE
 DRAWINGS IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.
  
  
 PLEASE CALL JULIO GOMEZ IF YOU HAVE ANY
 QUESTIONS OR NEED CLARIFICATION ON ANY
 OF THESE COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-12 Cont ID  
Sent By kstevens Date 2003-07-03 Time 17:38 Rev Time 4.00
Received By jgomez Date 2003-06-12 Time 14:43 Sent To  
Notes
2003-06-12 00:00:00BUILDING REVIEW CHECKLIST:
 1-PAY IMPACT FEES BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-FOOTING PAD AT REAR PORCH COLUMN IS
 ENCROACHING NEIGHBOR'S PROPERTY.
 REVISE AS REQUIRED.
 4-AIR HANDLER UNIT: CLARIFY WHY IS THIS
 UNIT ATTACHED TO THE SIDE WALL AND NOT
 TO TOP OF TRUSSES AS TYPICALLY DONE.
 IS THIS UNIT BUILT/REINFORCED ON THE
 SIDE TO BE MOUNTED THIS WAY. AND, WHAT
 ABOUT VIBRATION OF THE UNIT. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-PROVIDE DETAILS AND SPECIFICATIONS FOR
 INSTALLATION OF CEILING AT FRONT AND
 REAR PORCH. SPECIFY MATERIALS AND
 FASTENER TYPE AND SPACING. SEE ASTM
 C-926 AND ASTM C-1063.
 6-PROVIDE COMPLETE DETAIL FOR GABLE END.
 SEE SEC. 2117 FBC 2001 FOR SPECIAL
 WIND PROVISIONS FOR MASONRY.
 7-UPDATE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOESN'T ALLOW
 THE STREES INCREASE IN STEEL. SEE
 CURRENT CONNECTOR CATALOGUES FOR
 REVISED VALUES.
 8-REVISE DETAIL 1/4-8 FOR FOOTING AREA
 AT GARAGE INTERIOR BEARING WALL. SHOW
 FOOTING WITH 6" RECESS AND DIMENSIONS
 SPECIFIED ON FOUNDATION PLAN.SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 9-PROVIDE STRUCTURAL 2X BUCK DETAIL FOR
 ENTRY DOORS AND FIXED WINDOWS AS REQ'D
 ON THE PRODUCT APPROVALS. ALSO, SEE
 SEC. 1707.4.4.2 FBC 2001 FOR SPECIFIC
 BUCK INSTALLATION REQUIREMENTS.
 10-PROVIDE PRODUCT APPROVAL FOR:
 A)FIXED WINDOW WITH SIZE AS SHOWN ABOVE
 SLIDING GLASS DOORS AND ABOVE WINDOW
 IN THE GREAT ROOM AREA.
 B)WINDOW & DOOR MULLIONS. SEE PLANS.
 C)GLASS BLOCK WITH LEGIBLE DRAWINGS.
 D)UPDATED ROOF TILE. SBCCI REPORT THAT
 WAS SUBMITTED WAS DELETED BY SBCCI.
 E)COMPLETE REPORT FOR GARAGE DOORS.
 F)UPDATED REPORT FOR ENTRY DOORS WITH
 SIDELITE. REPORT TO HAVE DADE COUNTY
 LOGO AT BOTTOM LEFT OF PAGE. ALSO,
 NEED UPDATED LEGIBLE DRAWINGS WITH
 RENEWAL STAMP BY DADE COUNTY.
  
 11-STORM SHUTTERS: A)MEAN ROOF HEIGHT IS
 +/-18'-0" REVISE AS REQUIRED.
 B)SEE ENGINEERED DWGS FOR MAXIMUM AND
 MINIMUM PANEL SPAN ALLOWED AND REVISE
 INSTALLATION SCHEDULE AS REQUIRED.
 C)SEE ENGINEERING DWGS FOR ANCHOR TYPE &
 SPACING TO BE USED AND REVISE INSTALLA
 TION SCHEDULE AS REQUIRED.
 D)DWG 1 OF 1 OF ENGINEERED DWGS: REVISE
 DESIGN PRESSURES ACCORDING TO THE MEAN
 ROOF HEIGHT AND CLEARLY MARK ANCHOR
 TYPE AND SPACING.
  
 12-ENERGY CALCULATIONS BY EARTH SMART
 AND ARCHITECT'S ENERGY CALCS DON'T
 MATCH. REVISE AS REQUIRED.
 13-CONTRACTOR INSURANCE IS EXPIRED.
 UPDATE AS REQUIRED.
 14-SHEET GN AND SHEET A-1: UPDATE CONC.
 GENERAL NOTE. SEE SEC. 1901 FBC 2001
 AND COMMENTS ON DRAWINGS.
 15-SPECIFY SAFETY GLASS FOR GLASS BLOCK
 AT TUB IF FACE THICKNESS IS LESS THAN
 0.25". SEC. 2405.2 FBC 2001.
 16-MEAN ROOF HEIGHT IS TAKEN FROM FINISH
 GRADE, NOT FROM FINISH FLOOR. REVISE
 ELEVATIONS AS REQUIRED.
 17-SHEET A-5A AND A-5B:
 A)UPDATE DETAIL 1/A-5A. HUGHES IS OUT
 OF BUSINESS.
 B)CLARIFY CONSTRUCTION AT ENTRY TOWER.
 IS THERE A LEDGER SUPPORTING TRUSSES
 OR ARE TRUSSES RESTING ON THE WALL?.
 DETAIL 3/A8 DOESN'T SHOW IT.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 C)THERE ARE SOME CONNECTORS MISSING. SEE
 PLANS FOR COMMENTS.
 D)REVISE ROOF NAILING DIAPHRAGM. ZONE
 3 TO BE INCLUDED. SEE FIGURE 1606.2(C)
  
 18-OWES $104.10 FOR UPDATED VALUATION
 AND RADON FEES.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-16 Cont ID  
Sent By mmclean Date 2003-05-15 Time 10:05 Rev Time 0.25
Received By dpalmer Date 2003-05-16 Time 17:57 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-30 Cont ID  
Sent By shernand Date 2003-06-30 Time 08:45 Rev Time 0.00
Received By shernand Date 2003-06-30 Time 08:45 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-27 Cont ID  
Sent By shernand Date 2003-06-27 Time 16:57 Rev Time 0.00
Received By shernand Date 2003-06-27 Time 16:57 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-02 Cont ID  
Sent By shernand Date 2003-05-02 Time 17:39 Rev Time 0.00
Received By shernand Date 2003-05-02 Time 17:39 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-28 Cont ID  
Sent By kstevens Date 2003-05-17 Time 10:48 Rev Time 0.25
Received By pkrauss Date 2003-05-28 Time 14:39 Sent To B
Notes
2003-05-28 00:00:00MECHANICAL PERMIT 03050071

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-03 Cont ID  
Sent By kstevens Date 2003-07-03 Time 17:38 Rev Time 0.33
Received By kstevens Date 2003-07-03 Time 17:38 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-17 Cont ID  
Sent By shernand Date 2003-06-30 Time 08:45 Rev Time 0.25
Received By kstevens Date 2003-05-17 Time 10:42 Sent To M
Notes
2003-05-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM, OPTIONAL
 LAUNDRY TUB SHALL NOT DRAIN INTO THE WET
 VENT FOR THE BATHROOM FIXTURES. SECTION
 909.1 - L/TUB SHALL DRAIN DOWNSTREAM OF
 BATHROOM FIXTURES.
 2) SHT A-6 PLUMBING NOTES #3, PIPES
 2-1/2" AND SMALLER SHALL BE PITCHED AT
 1/4" PER FOOT PER TABLE 704.1. PLEASE
 CHANGE REFERENCE.
 3) SHT A-6 PLUMBING NOTES #7, AIR CHAMB-
 ERS ARE NOT APPROVED. PDI-WH 201.
 PLEASE DELETE REFERENCE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-05-02 Time 17:39 Rev Time 1.00
Received By mmclean Date   Time   Sent To E
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved