Plan Review Details - Permit 03050054
Plan Review Stops For Permit 03050054
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-02-23 Cont ID  
Sent By rbrown Date 2005-02-23 Time 11:37 Rev Time 0.00
Received By rbrown Date 2005-02-23 Time 11:37 Sent To  
Notes
2005-02-23 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 THE WINDOW SCHEDULE DOES NOT STATE THAT
 THE FIXED GLASS WINDOW MARK G (ADJACENT
 DOOR 137A) IS TO BE IMPACT RATED.THIS
 WINDOW SHALL BE IMPACT RATED, OR STORM
 SHUTTERS (WITH PRODUCT APPROVAL) SHALL
 BE PROVIDED.
  
 --PROVISO--
 FOR ACCESSIBILITY, THE WALKWAY LEVEL
 LEADING TO EACH OF THE BUILDING
 ENTRANCES/EXITS SHALL BE RAISED TO MATCH
 THE PATIO SLAB LEVEL.THIS SHALL BE
 ACHIEVED WITH A WALKWAY SLOPE OF 1 IN 20
 OR BETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-17 Cont ID  
Sent By rbrown Date 2003-10-17 Time 16:01 Rev Time 0.00
Received By rbrown Date 2003-10-17 Time 16:01 Sent To  
Notes
2003-10-17 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 THE WINDOW SCHEDULE DOES NOT STATE THAT
 THE FIXED GLASS WINDOW MARK G (ADJACENT
 DOOR 137A) IS TO BE IMPACT RATED.THIS
 WINDOW SHALL BE IMPACT RATED, OR STORM
 SHUTTERS (WITH PRODUCT APPROVAL) SHALL
 BE PROVIDED.
  
 --PROVISO--
 FOR ACCESSIBILITY, THE WALKWAY LEVEL
 LEADING TO EACH OF THE BUILDING
 ENTRANCES/EXITS SHALL BE RAISED TO MATCH
 THE PATIO SLAB LEVEL.THIS SHALL BE
 ACHIEVED WITH A WALKWAY SLOPE OF 1 IN 20
 OR BETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-10 Cont ID  
Sent By rbrown Date 2003-06-10 Time 15:42 Rev Time 0.00
Received By rbrown Date 2003-06-10 Time 15:42 Sent To  
Notes
2003-06-10 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 COTTAGE #13
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEWS (FOR ORIGINAL PERMIT# 02102207)
 ON 1/3/03 AND 4/24/03:
  
 1) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC* 104.2.4SITE SURVEY.A SIGNED AND
 SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES). THE SUBMITTED
 SURVEY SHEET IS FOR A DELRAY BEACH
 LOCATION (???).SUBMIT TWO COPIES OF AN
 APPROPRIATE SURVEY DRAWING FOR THIS SITE
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PLANS STAMPED BY THEM
 AND A COPY OF THE RECEIPT SUBMITTED TO
 THE CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 5) FBC 11-4.1.2EACH OF THE BUILDINGS
 SHALL BE SERVED BY AT LEAST ONE
 ACCESSIBLE ROUTE FROM THE ACCESSIBLE
 PARKING AND THE BUS STOP.ACCEPTABILITY
 OF THIS APPLICATION IS CONTINGENT UPON
 THE CIVIL/SITE PLANS, PERMIT# 02102208,
 BEING PERMITTED. NOTE THAT THE SUBMITTED
 SITE PLAN (SHEET A6-1.1) DOES NOT SHOW
 A PATH TO THE ENTRANCE OF COTTAGE #8.
  
 6) FBC 13-103.1.1.1 AND 103.1.2SHEET 2
 OF THE SUBMITTED ENERGY CODE COMPLIANCE
 FORMS SHALL BE SIGNED BY THE OWNER (OR
 THE PROJECT ARCHITECT, OR OTHER
 AUTHORIZED AGENT DESIGNATED BY THE
 OWNER) TO CERTIFY COMPLIANCE WITH THE
 CODE.ALSO, THE ARCHITECT'S NAME AND
 REGISTRATION NUMBER SHALL BE ADDED ABOVE
 THOSE OF THE OTHER SYSTEM DESIGNERS.ON
 SHEET 1, COMPLETE THE PROJECT DETAILS
 INCLUDING NAME OF OWNER, PROJECT ADDRESS
 (4838 N. HAVERHILL RD), ZIP (33417) AND
 PERMIT NUMBER (03050054).
  
 7) PRODUCT APPROVALS: THE PREVIOUS
 COMMENTS ON PRODUCT APPROVALS HAVE NOT
 BEEN ADDRESSED, ALSO THE PRODUCT
 APPROVAL SHEETS SHALL BE MARKED, AS
 APPROPRIATE TO IDENTIFY WHICH PRODUCT
 OPTIONS/MATERIALS ARE TO BE USED:
 (A) THIS COMMENT HAS NOT BEEN ADDRESSED.
 ASPHALT SHINGLE PRODUCT APPROVAL
 NOA# 00-0105.02 EXPIRED ON 4/22/03.
 SUBMIT A VALID PRODUCT APPROVAL.
 (B) THE PREVIOUSLY SUBMITTED COPY OF
 STEELCRAFT MANUF. 98/99 RIM EXIT STEEL
 DOOR PRODUCT APPROVAL NOA# 01-1203.11
 HAS BEEN OMITTED FROM THIS LATEST
 RE-SUBMITTAL.IS THIS INTENTIONAL?
 (C) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE SUBMITTED COPY OF STEELCRAFT MANUF.
 F, M FRAME STEEL DOOR PRODUCT APPROVAL
 NOA# 01-0129.12 IS MISSING TEXT
 SHEETS 2 AND 3 (SPECIFIC AND GENERAL
 CONDITIONS), AND SOME OF THE DRAWING
 SHEETS.SUBMIT A COMPLETE PRODUCT
 APPROVAL.
 (D) NOT USED
 (E) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE DRAWING SHEETS OF THE SUBMITTED
 COPIES OF ARCH ALUMINUM STOREFRONT DOOR
 PRODUCT APPR. NOA# 01-0919.02 ARE POORLY
 REPRODUCED.SUBMIT LEGIBLE COPIES.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
 (F) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE SUBMITTED 2 PAGE COPY EXTRACT OF THE
 48 PAGE GAF MODIFIED BITUMEN ROOF
 PRODUCT APPROVAL NOA# 00-0331.09 DOES
 NOT INCLUDE A STATEMENT OF THE MAXIMUM
 DESIGN PRESSURE AND STATES THAT "ALL
 GENERAL AND SYSTEM LIMITATIONS SHALL
 APPLY".SUBMIT COPIES OF THE SHEETS
 WHICH STATE THE GENERAL AND SYSTEM
 LIMITATIONS AND THE MAX DESIGN PRESSURE.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
  
 16) CONVERSION FROM PLAN CHECK TO PERMIT
 APPLICATION.SUBMIT TWO COPIES OF THE
 PLANS FOR EACH COTTAGE BUILDING.
  
 17) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-10-03 Cont ID  
Sent By dpalmer Date 2003-10-03 Time 15:16 Rev Time 0.50
Received By dpalmer Date 2003-10-03 Time 15:16 Sent To  
Notes
2003-10-03 00:00:00************** UNSAT ****************
  
 1)NOTE: RESPONSE LETTER MENTIONS THE
 REASON FOR SIZE OF CONDUCTORS ARE DUE TO
 THE DISTANCE OF 260' AWAY. PLEASE SEE
 THAT THE MIN SIZE WOULD BE 3/0'S. THE
 SIZE HAS BEEN INCREASED TO (TWO) SETS
 OF 250MCM. IT IS UNDERSTANDABLE TO
 INCREASE TO 250MCM DUE TO VOLTAGE DROP,
 HOWEVER TWO-SETS OF 250MCM IS NOT CLEAR.
 PLEASE SEE NOTE FROMLAST REVIEW.
 IF INDEED 2-SETS OF 250MCM IS INSTALLED,
 PLEASE PROVIDE A NOTE ON PLAN ON HOW
 THESE WILL TERMINATE INTO A SINGLE 200A
 BRKR THAT WILL NOT ACCOMADATE 2-SETS
 OF 250MCM.
  
 2)NOTE: PLEASE SEE BLDG PLAN REVIEW
 NOTES. PLEASE CORRELATE PLANS/PAPERWORK
 FOR COTTAGES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-15 Cont ID  
Sent By dpalmer Date 2003-05-15 Time 13:32 Rev Time 0.00
Received By dpalmer Date 2003-05-15 Time 13:32 Sent To  
Notes
2003-05-15 00:00:00NOTES UNDER MAIN 02102207

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-07-22 Cont ID  
Sent By mamini Date 2003-07-22 Time 11:17 Rev Time 0.50
Received By mamini Date 2003-07-22 Time 11:17 Sent To  
Notes
2003-07-22 00:00:00PASSED:
 1. SEE PERMIT # 02102208 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-11-03 Cont ID  
Sent By nmccray Date 2003-11-03 Time 09:43 Rev Time 0.00
Received By nmccray Date 2003-11-03 Time 09:43 Sent To  
Notes
2003-11-03 00:00:00************PROVISO*********************
 PLEASE SEE COMMENTS ON PERMIT #03050050

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-06-24 Cont ID  
Sent By nmccray Date 2003-06-24 Time 10:59 Rev Time 0.00
Received By nmccray Date 2003-06-24 Time 10:59 Sent To  
Notes
2003-06-24 00:00:00 
 ************DENIED***************
 PLEASE SEE COMMENTS FOR PERMIT 03050050.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-12 Cont ID  
Sent By csiegber Date 2003-09-12 Time 11:34 Rev Time 0.00
Received By csiegber Date 2003-09-12 Time 11:34 Sent To  
Notes
2003-09-12 00:00:00COMM BD#42/PLANS ON RACK SHELF 4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 09:10 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 09:10 Sent To  
Notes
2003-05-05 00:00:00COMM BOARD #12,POLANS NEXT TO CONF ROOM

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-28 Cont ID  
Sent By pkrauss Date 2003-10-28 Time 07:46 Rev Time 0.35
Received By pkrauss Date 2003-10-28 Time 07:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-10 Cont ID  
Sent By pkrauss Date 2003-05-10 Time 12:15 Rev Time 0.35
Received By pkrauss Date 2003-05-10 Time 12:15 Sent To  
Notes
2003-05-10 00:00:00MECHANICAL PERMIT 06050434

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-06-07 Cont ID  
Sent By kstevens Date 2003-06-07 Time 15:46 Rev Time 0.33
Received By kstevens Date 2003-06-07 Time 15:46 Sent To  
Notes
2003-06-07 00:00:00SEE PERMIT #02102207 - SEE PROVISO

Review Stop Z ZONING
Rev No 1 Status P Date 2003-11-06 Cont ID  
Sent By mmclean Date 2003-11-06 Time 10:09 Rev Time 0.00
Received By mmclean Date 2003-11-06 Time 10:09 Sent To  
Notes
2003-11-06 00:00:0011/6/03 OK PER JOSH LONG MM