Plan Review Details - Permit 03050050
Plan Review Stops For Permit 03050050
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-06-22 Cont ID  
Sent By rbrown Date 2006-06-22 Time 19:32 Rev Time 0.00
Received By rbrown Date 2006-06-22 Time 19:32 Sent To  
Notes
2006-06-22 00:00:00STRUCTURAL REVISION SUBMITTED 6/19/06
 FOR SHEETS S-7.02 AND S-7.03

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-06-11 Cont ID  
Sent By rbrown Date 2006-06-11 Time 15:04 Rev Time 0.00
Received By rbrown Date 2006-06-11 Time 15:04 Sent To  
Notes
2006-06-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 ARCHITECTURAL/STRUCTURAL REVISION FOR
 SHEETS A6-2.1, A6-4.2, A6-5.2, A6-6.1,
 A6-11.1, S-7.02 AND S-7.03
  
 1) THE ARCHITECTURAL SHEETS HAVE BEEN
 SEPARATED AND STAMPED SEPARATELY BECAUSE
 THE SCHEDULE ON STRUCTURAL SHEET S-7.02
 HAS AN INCORRECT TRUSS CONNECTOR/HANGER
 REFERENCE.THE CAPACITIES STATED ON THE
 PLAN ARE FOR A HHDO212-2 HANGER BUT THE
 PLAN REFERS TO HDO212-2 WHICH HAS LOWER
 CAPACITIES.AMEND THE SCHEDULE ON SHEET
 S-7.02 AND RESUBMIT BOTH STRUCTURAL
 SHEETS.THE ARCHITECTURAL SHEETS ARE OK
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-02-19 Cont ID  
Sent By rbrown Date 2006-02-19 Time 14:16 Rev Time 0.00
Received By rbrown Date 2006-02-19 Time 14:16 Sent To  
Notes
2006-02-19 00:00:00ROOF TRUSS DRAWING SUBMITTAL ON 1/20/06.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-02-23 Cont ID  
Sent By rbrown Date 2005-02-23 Time 11:34 Rev Time 0.00
Received By rbrown Date 2005-02-23 Time 08:40 Sent To  
Notes
2005-02-23 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 THE WINDOW SCHEDULE DOES NOT STATE THAT
 THE FIXED GLASS WINDOW MARK G (ADJACENT
 DOOR 137A) IS TO BE IMPACT RATED.THIS
 WINDOW SHALL BE IMPACT RATED, OR STORM
 SHUTTERS (WITH PRODUCT APPROVAL) SHALL
 BE PROVIDED.
  
 --PROVISO--
 FOR ACCESSIBILITY, THE WALKWAY LEVEL
 LEADING TO EACH OF THE BUILDING
 ENTRANCES/EXITS SHALL BE RAISED TO MATCH
 THE PATIO SLAB LEVEL.THIS SHALL BE
 ACHIEVED WITH A WALKWAY SLOPE OF 1 IN 20
 OR BETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-03-04 Cont ID  
Sent By rbrown Date 2004-03-04 Time 14:59 Rev Time 0.00
Received By rbrown Date 2004-03-04 Time 14:59 Sent To  
Notes
2004-03-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 61G1-16.004FL. ADMIN. CODE.ADD, TO
 EACH ARCHITECTURAL SHEET, THE PRINTED
 NAME AND LICENSE NUMBER OF JORGE GARCIA
 AS THE ARCHITECT WHO SEALED THE PLANS.
 THIS MAY BE DONE BY STAMP OR HANDWRITTEN
  
 THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 --PROVISO--
 THE WINDOW SCHEDULE DOES NOT STATE THAT
 THE FIXED GLASS WINDOW MARK G (ADJACENT
 DOOR 137A) IS TO BE IMPACT RATED.THIS
 WINDOW SHALL BE IMPACT RATED, OR STORM
 SHUTTERS (WITH PRODUCT APPROVAL) SHALL
 BE PROVIDED.
  
 --PROVISO--
 FOR ACCESSIBILITY, THE WALKWAY LEVEL
 LEADING TO EACH OF THE BUILDING
 ENTRANCES/EXITS SHALL BE RAISED TO MATCH
 THE PATIO SLAB LEVEL.THIS SHALL BE
 ACHIEVED WITH A WALKWAY SLOPE OF 1 IN 20
 OR BETTER.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-17 Cont ID  
Sent By rbrown Date 2003-10-17 Time 09:08 Rev Time 0.00
Received By rbrown Date 2003-10-17 Time 09:08 Sent To  
Notes
2003-10-17 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 THE WINDOW SCHEDULE DOES NOT STATE THAT
 THE FIXED GLASS WINDOW MARK G (ADJACENT
 DOOR 137A) IS TO BE IMPACT RATED.THIS
 WINDOW SHALL BE IMPACT RATED, OR STORM
 SHUTTERS (WITH PRODUCT APPROVAL) SHALL
 BE PROVIDED.
  
 --PROVISO--
 FOR ACCESSIBILITY, THE WALKWAY LEVEL
 LEADING TO EACH OF THE BUILDING
 ENTRANCES/EXITS SHALL BE RAISED TO MATCH
 THE PATIO SLAB LEVEL.THIS SHALL BE
 ACHIEVED WITH A WALKWAY SLOPE OF 1 IN 20
 OR BETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-10 Cont ID  
Sent By rbrown Date 2003-06-10 Time 12:57 Rev Time 0.00
Received By rbrown Date 2003-06-10 Time 12:57 Sent To  
Notes
2003-06-10 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 COTTAGE #10
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEWS (FOR ORIGINAL PERMIT# 02102207)
 ON 1/3/03 AND 4/24/03:
  
 1) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC* 104.2.4SITE SURVEY.A SIGNED AND
 SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES). THE SUBMITTED
 SURVEY SHEET IS FOR A DELRAY BEACH
 LOCATION (???).SUBMIT TWO COPIES OF AN
 APPROPRIATE SURVEY DRAWING FOR THIS SITE
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PLANS STAMPED BY THEM
 AND A COPY OF THE RECEIPT SUBMITTED TO
 THE CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 5) FBC 11-4.1.2EACH OF THE BUILDINGS
 SHALL BE SERVED BY AT LEAST ONE
 ACCESSIBLE ROUTE FROM THE ACCESSIBLE
 PARKING AND THE BUS STOP.ACCEPTABILITY
 OF THIS APPLICATION IS CONTINGENT UPON
 THE CIVIL/SITE PLANS, PERMIT# 02102208,
 BEING PERMITTED. NOTE THAT THE SUBMITTED
 SITE PLAN (SHEET A6-1.1) DOES NOT SHOW
 A PATH TO THE ENTRANCE OF COTTAGE #8.
  
 6) FBC 13-103.1.1.1 AND 103.1.2SHEET 2
 OF THE SUBMITTED ENERGY CODE COMPLIANCE
 FORMS SHALL BE SIGNED BY THE OWNER (OR
 THE PROJECT ARCHITECT, OR OTHER
 AUTHORIZED AGENT DESIGNATED BY THE
 OWNER) TO CERTIFY COMPLIANCE WITH THE
 CODE.ALSO, THE ARCHITECT'S NAME AND
 REGISTRATION NUMBER SHALL BE ADDED ABOVE
 THOSE OF THE OTHER SYSTEM DESIGNERS.ON
 SHEET 1, COMPLETE THE PROJECT DETAILS
 INCLUDING NAME OF OWNER, PROJECT ADDRESS
 (4826 N. HAVERHILL RD), ZIP (33417) AND
 PERMIT NUMBER (03050050).
  
 7) PRODUCT APPROVALS: THE PREVIOUS
 COMMENTS ON PRODUCT APPROVALS HAVE NOT
 BEEN ADDRESSED, ALSO THE PRODUCT
 APPROVAL SHEETS SHALL BE MARKED, AS
 APPROPRIATE TO IDENTIFY WHICH PRODUCT
 OPTIONS/MATERIALS ARE TO BE USED:
 (A) THIS COMMENT HAS NOT BEEN ADDRESSED.
 ASPHALT SHINGLE PRODUCT APPROVAL
 NOA# 00-0105.02 EXPIRED ON 4/22/03.
 SUBMIT A VALID PRODUCT APPROVAL.
 (B) THE PREVIOUSLY SUBMITTED COPY OF
 STEELCRAFT MANUF. 98/99 RIM EXIT STEEL
 DOOR PRODUCT APPROVAL NOA# 01-1203.11
 HAS BEEN OMITTED FROM THIS LATEST
 RE-SUBMITTAL.IS THIS INTENTIONAL?
 (C) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE SUBMITTED COPY OF STEELCRAFT MANUF.
 F, M FRAME STEEL DOOR PRODUCT APPROVAL
 NOA# 01-0129.12 IS MISSING TEXT
 SHEETS 2 AND 3 (SPECIFIC AND GENERAL
 CONDITIONS), AND SOME OF THE DRAWING
 SHEETS.SUBMIT A COMPLETE PRODUCT
 APPROVAL.
 (D) NOT USED
 (E) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE DRAWING SHEETS OF THE SUBMITTED
 COPIES OF ARCH ALUMINUM STOREFRONT DOOR
 PRODUCT APPR. NOA# 01-0919.02 ARE POORLY
 REPRODUCED.SUBMIT LEGIBLE COPIES.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
 (F) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE SUBMITTED 2 PAGE COPY EXTRACT OF THE
 48 PAGE GAF MODIFIED BITUMEN ROOF
 PRODUCT APPROVAL NOA# 00-0331.09 DOES
 NOT INCLUDE A STATEMENT OF THE MAXIMUM
 DESIGN PRESSURE AND STATES THAT "ALL
 GENERAL AND SYSTEM LIMITATIONS SHALL
 APPLY".SUBMIT COPIES OF THE SHEETS
 WHICH STATE THE GENERAL AND SYSTEM
 LIMITATIONS AND THE MAX DESIGN PRESSURE.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
  
 16) CONVERSION FROM PLAN CHECK TO PERMIT
 APPLICATION.SUBMIT TWO COPIES OF THE
 PLANS FOR EACH COTTAGE BUILDING.
  
 17) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2006-11-16 Cont ID  
Sent By dpalmer Date 2006-11-16 Time 08:07 Rev Time 0.00
Received By dpalmer Date 2006-11-16 Time 07:59 Sent To PC
Notes
2006-11-16 08:08:28REDLINED
 2002 NEC.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-06-20 Cont ID  
Sent By dpalmer Date 2006-06-20 Time 19:24 Rev Time 0.00
Received By dpalmer Date 2006-06-20 Time 19:12 Sent To  
Notes
2006-06-20 00:00:00*** REV FOR COTTAGE #10,
  
 THIS REVISION WAS FOR POWER PLANS AND
 PANEL SCHEDULE REV'S ONLY , NO LIGHTING
 SUBMITTED FOR REVISIONS.
 ALL CIRCUITING PER 2002 NEC WAS REDLINED
 ON PLANS.
 ANY CHANGES SHALL BE SUBMITTED FOR
 REVIEW BEFORE ROUGH ELECTRICAL
 INSPECTION.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-05-18 Cont ID  
Sent By dpalmer Date 2006-05-18 Time 16:30 Rev Time 0.00
Received By dpalmer Date 2006-05-18 Time 16:30 Sent To PC
Notes
2006-05-18 00:00:00** UNSAT **
  
 1) NOTE: PLEASE VERIFY CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE(S).
 PLEASE SEE SOME CIRCUITING AS SHOWN ON
 PLANS FOR RECEPTS DO NOT CORRELATE WITH
 AFCI BREAKERS IN PANELS.
 210.12B
  
 2) NOTE: PLEASE VERIFY SD'S AS
 CIRCUITING IS NOT SHOWN FOR THESE. IF
 THESE ARE LV AND FED FROM A FA SYSTEM,
 PLEASE NOTE ON PLANS.
 IF NOT PLEASE CIRCUIT AND AFCI.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-04-24 Cont ID  
Sent By dpalmer Date 2006-04-24 Time 14:09 Rev Time 0.00
Received By dpalmer Date 2006-04-24 Time 14:04 Sent To  
Notes
2006-04-24 00:00:00******* UNSAT ************
  
 1) NOTE: PLEASE SEE NOTES BELOW AS THE
 "PROVISO" WHICH WAS SET UP IN ORDER TO
 ISSUETHE BUILDING PERMIT HAS NOT BEEN
 ADDRESSED TO DATE.
 THIS WAS A CONDITION AS PERMITS HAD
 EXPIRED AND EXTENSION WAS GRANTED BY THE
 AHJ AND BUILDING OFFICAL THAT ALL
 ELECTRICAL BE BROUGHT UP TO THE 2002
 NEC. THIS WAS REQUIRED TO BE DONE BEFORE
 ROUGH ELECTRICAL INSPECTION AND TO DATE
 PLANS MEETING THIS HAVE NOT BEEN
 SUBMITTED.
 PLEASE COMPLETE ROOMAND AREA
 DESIGNATIONS ON PLANS, AND CORRELATE ALL
 CIRCUTING TO PANEL SCHEDULES TO BE
 SUBMITTED.
 PLEASE SEE NOTES.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 DPALMER2WPB.ORG.
  
  
  
  
  
  
 ******NOTES REDLINED/ PROVISO *********
  
  
  
 PURSUANT TO DECISION BY THE AHJ AND
 BUILDING OFFICAL, CIRCUITING FOR "ALL"
 BEDROOOM "OUTLETS ARE TO BE BROUGHT UP
 TO THE 2002 NEC FOR ARC FAULT
 PROTECTION. PER 210.12
  
 PLANS WILL BE REQUIRED TO BE REVISED IN
 ORDER TO ADD AF PROTECTION.
  
 PLEASE SEE ALL OUTLETS: INCLUSIVE OF
 SD'S , LTS, RECEPTS, FANS ETC.
  
 PLEASE REVISE AND SUBMIT FOR REVIEW
 BEFORE ROUGH ELECTRICAL INSPECTION.
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-02-25 Cont ID  
Sent By dpalmer Date 2005-02-25 Time 14:45 Rev Time 0.50
Received By dpalmer Date 2005-02-25 Time 14:43 Sent To  
Notes
2005-02-25 00:00:00******NOTES REDLINED/ PROVISO *********
  
  
  
 PURSUANT TO DECISION BY THE AHJ AND
 BUILDING OFFICAL, CIRCUITING FOR "ALL"
 BEDROOOM "OUTLETS ARE TO BE BROUGHT UP
 TO THE 2002 NEC FOR ARC FAULT
 PROTECTION. PER 210.12
  
 PLANS WILL BE REQUIRED TO BE REVISED IN
 ORDER TO ADD AF PROTECTION.
  
 PLEASE SEE ALL OUTLETS: INCLUSIVE OF
 SD'S , LTS, RECEPTS, FANS ETC.
  
 PLEASE REVISE AND SUBMIT FOR REVIEW
 BEFORE ROUGH ELECTRICAL INSPECTION.
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-03-02 Cont ID  
Sent By dpalmer Date 2004-03-02 Time 07:06 Rev Time 0.50
Received By dpalmer Date 2004-03-02 Time 07:06 Sent To  
Notes
2004-03-02 00:00:00***UNSAT ***
 ** COTTAGE #10**
  
 1)NOTE: PLEASE SEE E6-4.01, SHEET HAS
 CERTICATE OF AUTHORIZATION # ADDED TO
 TITLE BLOCK AS REQ'D UNDER FS 471.023
 NAME AND LICENSE # OF ENGINEER AS REQ'D
 UNDER FAC 61G15-23.002 HAS ALSO BEEN
 ADDED TO SAME SHEET.
 THIS IS REQ'D ON ALL SHEETS AND HAS NOT
 BEEN A PREVIOUS REVIEW COMMENT.
 THIS INFORMATION MAY BE ADDED BY HAND.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
 THIS INFORMATION IS REQ'D ON ALL SHEETS
 AND FOR ALL TRADES
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-10-03 Cont ID  
Sent By dpalmer Date 2003-10-03 Time 15:09 Rev Time 1.00
Received By dpalmer Date 2003-10-03 Time 15:09 Sent To  
Notes
2003-10-03 00:00:00************** UNSAT ****************
  
 1)NOTE: RESPONSE LETTER MENTIONS THE
 REASON FOR SIZE OF CONDUCTORS ARE DUE TO
 THE DISTANCE OF 260' AWAY. PLEASE SEE
 THAT THE MIN SIZE WOULD BE 3/0'S. THE
 SIZE HAS BEEN INCREASED TO (TWO) SETS
 OF 250MCM. IT IS UNDERSTANDABLE TO
 INCREASE TO 250MCM DUE TO VOLTAGE DROP,
 HOWEVER TWO-SETS OF 250MCM IS NOT CLEAR.
 PLEASE SEE NOTE FROMLAST REVIEW.
 IF INDEED 2-SETS OF 250MCM IS INSTALLED,
 PLEASE PROVIDE A NOTE ON PLAN ON HOW
 THESE WILL TERMINATE INTO A SINGLE 200A
 BRKR THAT WILL NOT ACCOMADATE 2-SETS
 OF 250MCM.
  
 2)NOTE: PLEASE SEE BLDG PLAN REVIEW
 NOTES. PLEASE CORRELATE PLANS/PAPERWORK
 FOR COTTAGES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-15 Cont ID  
Sent By dpalmer Date 2003-05-15 Time 13:08 Rev Time 0.00
Received By dpalmer Date 2003-05-15 Time 13:08 Sent To  
Notes
2003-05-15 00:00:00NOTES UNDER MAIN 02102207

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-07-22 Cont ID  
Sent By mamini Date 2003-07-22 Time 09:47 Rev Time 0.50
Received By mamini Date 2003-07-22 Time 09:47 Sent To  
Notes
2003-07-22 00:00:00PASSED:
 1. SEE PERMIT # 02102208 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-05-31 Cont ID  
Sent By mwennerg Date 2006-05-31 Time 10:08 Rev Time 0.00
Received By mwennerg Date 2006-05-31 Time 10:08 Sent To  
Notes
2006-05-31 00:00:00***PROVISO***
  
 REVISIONS
  
 1) DUCT SMOKE DETCTOR INSTALLATIONS
 SHALL INITIATE A GENERAL FIRE ALARM IN
 ACCORDANCE WITH LOCAL REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-09-19 Cont ID  
Sent By mcarsill Date 2003-09-19 Time 16:08 Rev Time 0.00
Received By mcarsill Date 2003-09-19 Time 16:08 Sent To  
Notes
2003-09-19 00:00:00APPROVED PROVISO:
  
 PLEASE PROVIDE THIS OFFICE A LETTER
 HOW THE COTTAGES WILL BE LICENSED UNDER
 STATE, COUNTY, AND CITY REQUIREMENTS.
  
 PLEASE INDICATE HOURS OF OPERATION FOR
 THE COTTAGES. (FULL OR PART TIME)
  
 WILL THERE BE ANY COOKING PLANNED AT
 THE COTTAGE THAT WOULD CREATE SMOKE
 OR GREASE LADEN VAPORS.
  
 THE SAME COMMENTS APPLY TO PERMIT
 NUMBERS 03050050, 03050051, 03050052,
 03050053, 03050054, 03050055, 03050056,
 03050057, AND MASTER PERMIT # 021002207.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-06-24 Cont ID  
Sent By nmccray Date 2003-06-24 Time 10:27 Rev Time 0.00
Received By nmccray Date 2003-06-24 Time 10:27 Sent To  
Notes
2003-06-24 00:00:00***********DENIED***********
 1) AGAIN HOW WILL THE COTTAGES BE
 LICENSED UNDER STATE, COUNTY AND CITY
 REQUIREMENTS.
  
 2) PLEASE INDICATE HOURS OF OPERATION
 FOR THE COTTAGES. (FULL TIME OR PART
 TIME)
  
 3) WILL THERE BE ANY COOKING PLANNNED AT
 THE COTTAGES THAT WOULD CREATE SMOKE OR
 GREASE LADEN VAPORS.
  
 4) ABOVE COMMENTS ARE ALSO FOR PERMITS
 (03050050; 03050051; 03050052; 03050053;
 03050054; 03050055; 03050056; 03050057
 MASTER PERMIT # 021002207).
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-11-09 Cont ID  
Sent By adarroug Date 2006-11-09 Time 17:52 Rev Time 0.00
Received By adarroug Date 2006-11-09 Time 17:52 Sent To E
Notes
2006-11-09 17:52:56TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-11-04 Cont ID  
Sent By adarroug Date 2006-11-04 Time 19:17 Rev Time 0.00
Received By adarroug Date 2006-11-04 Time 19:17 Sent To P
Notes
2006-11-04 19:17:59TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 13:51 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 13:51 Sent To M
Notes
2006-08-14 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-06-20 Cont ID  
Sent By adarroug Date 2006-06-20 Time 08:17 Rev Time 0.00
Received By adarroug Date 2006-06-20 Time 08:16 Sent To M
Notes
2006-06-20 00:00:00TO "PKRAUSS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-05-16 Cont ID  
Sent By adarroug Date 2006-05-16 Time 15:49 Rev Time 0.00
Received By adarroug Date 2006-05-16 Time 15:49 Sent To E
Notes
2006-05-16 00:00:00TO "DPALMER' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-03-28 Cont ID  
Sent By adarroug Date 2006-03-28 Time 15:41 Rev Time 0.00
Received By adarroug Date 2006-03-28 Time 15:41 Sent To  
Notes
2006-06-09 00:00:006/8/06-TAKEN FROM "COMM" BD#51 TO
 "RBROWN" DESK
2006-04-18 00:00:00TO "COMM" BD#51-REV
2006-03-28 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-01-23 Cont ID  
Sent By adarroug Date 2006-01-23 Time 16:08 Rev Time 0.00
Received By adarroug Date 2006-01-23 Time 16:08 Sent To B
Notes
2006-01-23 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-23 Cont ID  
Sent By adarroug Date 2006-01-23 Time 16:01 Rev Time 0.00
Received By adarroug Date 2006-01-23 Time 16:01 Sent To B
Notes
2006-01-23 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-24 Cont ID  
Sent By rbrown Date 2005-02-03 Time 08:40 Rev Time 0.00
Received By rbrown Date 2005-02-03 Time 08:40 Sent To  
Notes
2005-02-24 00:00:00PLANS ON RACK (COMMERCIAL BOARD #17)

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 15:53 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 15:53 Sent To  
Notes
2004-02-06 00:00:00TO COMM BD#45

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-12 Cont ID  
Sent By csiegber Date 2003-09-12 Time 11:31 Rev Time 0.00
Received By csiegber Date 2003-09-12 Time 11:31 Sent To  
Notes
2003-09-12 00:00:00COMM BD#42/PLANS ON RACK SHELF 4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 09:12 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 09:12 Sent To  
Notes
2003-05-05 00:00:00COMM BOARD #12,PLANS NEXT TO CONF ROOM

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-09-11 Cont ID  
Sent By pkrauss Date 2006-09-11 Time 07:31 Rev Time 0.00
Received By pkrauss Date 2006-09-11 Time 07:23 Sent To  
Notes
2006-09-11 00:00:00PROVISO:
 GENERAL NOTES: REVISION ADDED NOTE #4
 WHICH INDICATES THE HVAC CLOSET WILL NOW
 SERVE AS A PLENUM AND ALL DEVICES
 LOCATED IN THE SPACE SHALL BE PLENUM
 RATED.PLEASE NOTE, THIS SHALL INCLUDE
 THE DOOR AND DOOR FRAME.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-28 Cont ID  
Sent By pkrauss Date 2003-10-28 Time 07:45 Rev Time 0.35
Received By pkrauss Date 2003-10-28 Time 07:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-10 Cont ID  
Sent By pkrauss Date 2003-05-10 Time 12:18 Rev Time 0.35
Received By pkrauss Date 2003-05-10 Time 12:18 Sent To  
Notes
2003-05-10 00:00:00MECHANICAL PERMIT 03050406

Review Stop P PLUMBING
Rev No 3 Status   Date 2006-11-07 Cont ID  
Sent By pschmitz Date 2006-11-07 Time 14:29 Rev Time 0.00
Received By pschmitz Date 2006-11-07 Time 14:29 Sent To  
Notes
2006-11-07 14:29:55AS BUILT REVISIION FOR DWVU/G

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-03-05 Cont ID  
Sent By kstevens Date 2005-03-05 Time 06:13 Rev Time 1.25
Received By kstevens Date 2005-03-05 Time 06:13 Sent To  
Notes
2005-03-05 00:00:00PASSED/PROVISO
  
  
 PLUMBING APPROVAL ONLY.SEPARATE PERMIT
 REQUIRED FOR GAS. MORE INFORMATION WILL
 BE REQUIRED WHEN APPLYING FOR PERMIT.
 - SPECIFICATION SHEET FOR ADA ACCESSIBLE
 SLIDING DOOR HARDWARE FOR DOOR AT ROOM
 #104A REQUIRED AT TIME OF FINAL INSPECT-
 ION.
  
  
 PLUMBING PROVISO
  
 SHT P6-3.01 WATER HAMMER ARRESTORS ARE
 REQUIRED ON THE WATER SUPPLY PIPING FOR
 THE WASH MACHINES. SECTION 604.9 LOCATED
 PER PDI-WH 201 NEAR THE FIXTURES.
  
 SHT P6-3.01 FULL OPEN VALVES ARE
 REQUIRED ON THE TOP OF ALL WATER
 DOWN-FEED PIPES PER SECTION 606.1(4)
  
 SHT P6-3.02 CLEANOUTS ARE REQUIRED AT
 THE WASH MACHINES MINIMUM 4' ABOVE THE
 FLOOR FOR ACCESS. SECTION 708.10
  
  
  
 .

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-06-07 Cont ID  
Sent By kstevens Date 2003-06-07 Time 15:40 Rev Time 0.33
Received By kstevens Date 2003-06-07 Time 15:40 Sent To  
Notes
2003-06-07 00:00:00SEE PERMIT #02102207 - SEE PROVISO

Review Stop Z ZONING
Rev No 1 Status P Date 2005-05-12 Cont ID  
Sent By mmclean Date 2003-11-06 Time 08:56 Rev Time 0.00
Received By mmclean Date 2003-11-06 Time 08:55 Sent To  
Notes
2005-05-12 00:00:00OK PER JOSH LONG, PLANNER MM