| 2003-05-13 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03050044 |
| | ADD: 527 CLEMATIS ST |
| | CONT: WHITING-TURNER |
| | TEL: (954)776-0800 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION : DENIED |
| | |
| | 1) THE FRONT DOOR DOES NOT MEET THE |
| | REQUIREMENTS OF TABLE 1004, 32" CLEAR |
| | OPENING OF EXIT DOORS. |
| | |
| | 2) 1003.2.7 CHANGES IN GRADE, NO INDICAT |
| | ION AS TO THE DIFFERENCE IN GRADE AND |
| | THE INTERIOR, 11-4.8.3 IF RAMPS ARE RE- |
| | QUIRED, THE MINIMUM WIDTH OF 44". |
| | |
| | 3) IF THE FRONT DOOR STAYS IN THE SAME |
| | LOCATION & INSWING THE NEW INSTALLATION |
| | WILL NEED TO KEEP THE REQUIRED MANEUVER- |
| | ING CLEARENCES ON THE PUSH / PULL SIDES |
| | 11-4.13.6 |
| | |
| | 4) THIS DOOR WILL ALSO NEED APPROVAL |
| | FROM THE HISTORICAL BOARD. |
| | |
| | 5)1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | |
| | 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST.FOR GLAZED DOORS! |
| | |
| | 6) THE NEW RESTROOM DOOR WILL NEED TO |
| | MEET THE 18" CLEAR : |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)659-8096 X 8412 |
| | FAX: (561)659-8026 |