Plan Review Details - Permit 03050029
Plan Review Stops For Permit 03050029
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-06-01 Cont ID  
Sent By lmartine Date 2003-06-01 Time 12:00 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-05-20 Cont ID  
Sent By shernand Date 2003-05-30 Time 16:03 Rev Time 0.00
Received By hpiskura Date 2003-05-20 Time 14:23 Sent To Z
Notes
2003-05-20 00:00:00SHEETS A4.1.1, A4.1.2 AND A4.1.3 PROVIDE
 LITTLE IF ANY "INTERIOR FINISH"
 DETAILS AS DECLARED ON THE PERMIT
 APPLICATION AND THE PROJECT MANAGER'S
 5/14/03 LETTER.
  
 SHEET S-5 SHOWS THE CHANGE TO THE
 BALCONY.IS THERE ANY OTHER STRUCTURAL
 WORK INTENDED TO BE ACCOMPLISHED UNDER
 THIS PERMIT?PROVIDE DETAILS AND
 SPECIFICATIONS FOR THE GUARD RAILS ON
 THE "NEW" BALCONY THAT WAS DENIED AS A
 REVISION ON 3/09/03 UNDER PERMIT
 #01030147 FOR INSUFFICIENT INFORMATION.
  
 THE RC ALUMINUM PLANS SHOW WORK IN
 UNITS E AND G THAT ARE NOT SHOWN ON
 THESE PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-13 Cont ID  
Sent By shernand Date 2003-05-16 Time 15:15 Rev Time 0.00
Received By hpiskura Date 2003-05-13 Time 10:21 Sent To  
Notes
2003-05-13 00:00:00THE PLANS ARE NOT CLEAR AS TO WHAT IS
 EXISTING AND WHAT IS TO BE ACCOMPLISHED
 WITH THIS PERMIT APPLICATION.PLEASE
 CLEARLY DEFINE THE WORK TO BE
 ACCOMPLISHED.
  
 THE AL-FAROOQ CORP. WINDOW DOOR
 INFORMATION REFERENCES THE 1997
 STANDARD BUILDING CODE.THE STATE OF
 FLORIDA CURRENTLY INVOKES THE 2001
 FLORIDA BUILDING CODE. PLEASE REVISE
 AND INSURE COMPLIANCE AS NECESSARY.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-08 Cont ID  
Sent By dpalmer Date 2003-05-08 Time 14:09 Rev Time 0.50
Received By dpalmer Date 2003-05-08 Time 14:08 Sent To  
Notes
2003-05-12 00:00:00REDLINED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-05-09 Cont ID  
Sent By mcarsill Date 2003-05-09 Time 11:25 Rev Time 0.00
Received By mcarsill Date 2003-05-09 Time 11:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-30 Cont ID  
Sent By shernand Date 2003-05-30 Time 16:03 Rev Time 0.00
Received By shernand Date 2003-05-30 Time 16:03 Sent To B
Notes
2003-05-30 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-16 Cont ID  
Sent By shernand Date 2003-05-16 Time 15:15 Rev Time 0.00
Received By shernand Date 2003-05-16 Time 15:15 Sent To B
Notes
2003-05-16 00:00:00HP DESK, RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 09:22 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 09:22 Sent To  
Notes
2003-05-05 00:00:00COMM BOARD #37

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-08 Cont ID  
Sent By pkrauss Date 2003-05-08 Time 12:01 Rev Time 0.35
Received By pkrauss Date 2003-05-08 Time 11:51 Sent To  
Notes
2003-05-08 00:00:00MECHANICAL PERMIT 03050075

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-05-12 Cont ID  
Sent By kstevens Date 2003-05-12 Time 17:17 Rev Time 2.00
Received By kstevens Date 2003-05-12 Time 17:17 Sent To  
Notes
2003-05-12 00:00:00REVISION AS BUILT - ROUGHS COMPLETE
 KSTEVENS

Review Stop Z ZONING
Rev No 1 Status N Date 2003-05-20 Cont ID  
Sent By sgraham Date 2003-05-20 Time 16:05 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***