Plan Review Details - Permit 03042731
Plan Review Stops For Permit 03042731
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-30 Time 09:20 Rev Time 0.00
Received By shernand Date 2003-04-30 Time 09:20 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-17 Cont ID  
Sent By kstevens Date 2003-07-17 Time 17:39 Rev Time 0.50
Received By kstevens Date 2003-07-17 Time 17:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-30 Time 09:20 Rev Time 0.50
Received By kstevens Date 2003-04-30 Time 16:53 Sent To  
Notes
2003-04-30 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) FOLLOWING INFORMATION REQUIRED FOR
 GAS PERMIT.
 A. TYPE OF GAS, (LP OR NATURAL)
 B. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692