| 2003-06-03 00:00:00 | BULDING REVIEW CHECKLIST: |
| | 1-REVISE ENERGY CALCULATIONS: A)A/C AREA |
| | DON'T MATCH ARCHITECT'S DRAWINGS. |
| | B)INSULATION SPECIFIED ON EXTERIOR CONC. |
| | BLOCK WALL DOESN'T MATCH ARCHITECT'S |
| | PLANS. REVISE EITHER ONE AS REQUIRED. |
| | C)COMPLETE ALL INFORMATION ON TOP OF |
| | FORM. EG: OWNER, ETC. |
| | D)PROVIDE ORIGINAL SIGNATURES ON BOTTOM |
| | OF FORM. SEC. 103.0 CHAPTER 13 FBC/01. |
| | |
| | 2-SOIL TEST REPORT PROVIDED IS FOR LOT |
| | 21. THIS IS LOT 4. REVISE AS REQ'D. |
| | 3-IF EGRESS FROM BEDROOM IS THRU ZERO |
| | LOT WALL, THEN NEED RECORDED PLAT |
| | SHOWING EASEMENT TO ALLOW FOR EGRESS |
| | THRU NEIGHBOR'S PROPERTY AS REQUIRED |
| | BY THE BUILDING OFFICIAL. |
| | 4-PROVIDE SPECS FOR WWM SUPPORTS IN CONC |
| | SLAB. SEE SEC. 1909.3 FBC 2001. |
| | 5-GLASS BLOCK BY TUB AREA TO BE SAFETY |
| | GLASS IF FACE THICKNESS IS LESS THAN |
| | 0.25". SEE SEC. 2405.2 FBC 2001. |
| | 6-ENERGY CALCULATIONS TAKE THE CEILING |
| | FAN CREDIT, THEN, SPECIFY SIZE AND # |
| | OF CEILING FANS IN ALL ROOMS AS REQ'D |
| | BY TABLE 6-6 CHAPTER 13 FBC 2001. |
| | **NOTE: WHEN TAKING THIS CREDIT, CEILING |
| | FANS SHALL BE INSTALLED. THEY ARE NOT |
| | OPTIONAL AS CALLED FOR DEN ROOM. |
| | 7-STORM PANELS EXCEED THE MAXIMUM PANEL |
| | SPAN ALLOWED BY TABLE 1 OF ENGINEERED |
| | DRAWINGS ACCORDING TO THE DESIGN |
| | PRESSURES CALCULATED BY THE ENGINEER |
| | OF RECORD. REVISE INSTALLATION SCHED. |
| | AS REQUIRED. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 8-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| | ENTRY DOORS AS REQUIRED BY THE PRODUCT |
| | APPROVAL SUBMITTED. |
| | 9-OWES $38.46 FOR UPDATED VALUATION AND |
| | RADON FEES. |
| | 10-UPDATE THE TRUSS ANCHOR SCHEDULE AND |
| | ALL DETAILS THAT ARE AFFECTED BY SEC. |
| | 1609.4.3 FBC 2001, WHICH DOES NOT |
| | ALLOW THE 33% INCREASE IN THE ALLOWA- |
| | BLE STRESS OF THE STEEL. |