Plan Review Details - Permit 03042249
Plan Review Stops For Permit 03042249
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-30 Cont ID  
Sent By shernand Date 2003-06-30 Time 09:44 Rev Time 1.00
Received By sthyng Date 2003-06-30 Time 10:57 Sent To  
Notes
2003-06-30 00:00:00*******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 WHEN RESUBMITTING, ALL CHANGES SHOULD
 BE MARKED ON THE PLAN.SUBMIT A COPY
 OF THE OLD SHEETS.
  
 1.)SEE PREVIOUS CORRECTION LIST, #4,
 NAILING OF ROOF SHEATHING IN THE WALL
 SECTION DOES NOT COMPLY WITH CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FBC,
 TABLE 2306.1 (SEE ATTACHED).
  
 2.) SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR THE FRONT DOOR.
  
 3.)R19 INSULATION MIN. IS REQUIRED
 FOR A 2X6 FRAME WALL, FBC602.1.C.1.1.
  
 4.)THE ORIGINAL PLAN SHOWED AN
 EXISTING STUDY.THIS IS NOW SHOWN AS
 AN EXISTING PORCH.ADDITION OF AIR
 CONDITIONED LIVING SPACE REQUIRES:
 ENERGY CALCS FBC13-103.1.2
 IMPACT FEES
  
 5.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE ORIGINAL RECEIPT
 ATTACHED TO THE APPLICATION. 233-5025
  
 6.)BEFORE RESUBMITTING, COMPARE THE
 MINIMUM INSULATION R VALUES ON THE
 ENERGY CALC TO THE PLAN.
  
 7.)THERE IS A HOLD ON THIS PROPERTY
 (SEE ATTACHED).SEE ATTACHED.
  
 8.)THE NAME OF THE DESIGNER IS
 REQUIRED TO BE ON THE PLAN, FBC104.2.1.
  
 9.)ADDITIONAL PERMITS REQUIRED.
  
 10.) HOW WILL THE PROPOSED NEW ROOF
 TRUSSES BE ATTACHED TO THE EXISTING
 HOUSE?GIVE UPLIFT VALUES FOR ALL
 CONNECTORS.
  
 11.)DESIGN INFORMATION IS REQUIRED
 TO BE ON THE PLAN, FBC1606.1.7.
  
 12.)AREA CALCULATIONS ARE REQUIRED
 TO BE ON THE PLAN (EXISTING, PROPOSED,
 NEW TOTALS).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-07 Cont ID  
Sent By shernand Date 2003-06-26 Time 08:30 Rev Time 1.00
Received By sthyng Date 2003-05-07 Time 19:19 Sent To  
Notes
2003-05-07 00:00:00**********CORRECTIONS************
  
 1.)AS DISCUSSED, THE CARPORT IS NOT
 A PART OF THIS PERMIT APPLICATION.
 ELIMINATE THE CARPORT FROM THE PLAN (YOU
 MAY PUT AN X OVER IT AND INDICATE THAT
 IT IS NOT A PART OF THIS PERMIT).
  
 2.)THE SCALED DRAWINGS HAVE BEEN
 REDUCED, MAKING THEM DIFFICULT TO READ.
 SUBMITDRAWINGS WHICH HAVE NOT BEEN
 REDUCED.
  
 3.)YOUR SCOPE OF WORK AT THE EXISTING
 STUDY IS TO TEAR OFF THE ROOF AND WALLS,
 AND TO REBUILD IN THE SAME LOCATION.
 INCLUDE THE DEMOLITION OF THE ROOF
 ON THE FLOOR PLAN.
  
 4.)NAILING OF SHEATHING IN THE WALL
 SECTION IS TO BE 4" AT EDGES IN ZONE
 3, NOT 6" THROUGHOUT AS INDICATED.
  
 5.)ROOF IN WALL SECTION IS MISSING
 THE LAYER BETWEEN THE 30# FELT AND THE
 ROOF TILE.
  
 6.)WINDOWS REQUIRE HURRICANE
 PROTECTION, FBC 1606.1.4.
  
 7.)SUBMIT PRODUCT APPROVALS (2 COPIES
 EACH) FOR:
 ROOF COVERING
 SINGLE HUNG WINDOWS
 FIXED ARCHITECTURAL WINDOWS
 WINDOW MULLIONS
 HURRICANE SHUTTERS
 EXTERIOR DOOR
  
 8.)HUGHES STRAPS ARE NO LONGER MADE.
 REVISE THE WALL SECTION.
  
 9.)THE APPLICATION SAYS THAT THE WORK
 IS TO BE DONE AT THE FRONT PORCH; THE
 PLAN SHOWS THAT THIS AREA IS AN
 EXISTING STUDY.PLEASE CLARIFY.
  
 10.)THE WALL SECTION SHOWS TWO
 DIFFERENT SIZES OF PLYWOOD AND TWO
 DIFFERENT EXTERIOR FINISHES.CLARIFY.
  
 11.)FIREBLOCK REQUIRED FBC 705.3.1.
  
 12.)A NOTICE OF COMMENCEMENT MUST BE
 RECORDED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED.
  
 13.)IT APPEARS THAT YOU WILL NEED AN
 ELECTRIC PERMIT.THIS MAY BE APPLIED
 FOR SEPARATELY.
  
 14.)IF THIS ROOM IS AIR CONDITIONED,
 A MECHANICAL PERMIT WILL BE REQUIRED TO
 REPLACE THE DUCT.THIS MAY BE APPLIED
 FOR SEPARATELY.
  
 WHEN RESUBMITTING PLANS, PLEASE INCLUDE
 ONE COPY OF THE OLD SHEETS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-30 Cont ID  
Sent By shernand Date 2003-06-30 Time 09:44 Rev Time 0.00
Received By shernand Date 2003-06-30 Time 09:44 Sent To B
Notes
2003-06-30 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-26 Cont ID  
Sent By shernand Date 2003-06-26 Time 08:30 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 08:30 Sent To B
Notes
2003-06-26 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 08:17 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 08:17 Sent To B
Notes
2003-05-05 00:00:00MISC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-28 Cont ID  
Sent By shernand Date 2003-04-28 Time 14:48 Rev Time 0.00
Received By shernand Date 2003-04-28 Time 14:48 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By shernand Date 2003-04-28 Time 14:49 Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***