Plan Review Details - Permit 03042197
Plan Review Stops For Permit 03042197
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-08-22 Cont ID  
Sent By dpalmer Date 2003-08-26 Time 16:40 Rev Time 1.00
Received By sthyng Date 2003-08-22 Time 09:00 Sent To E
Notes
2003-08-22 00:00:00TO DP DESK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-08-22 Cont ID  
Sent By csiegber Date 2003-08-22 Time 08:47 Rev Time 1.00
Received By sthyng Date 2003-07-16 Time 12:38 Sent To  
Notes
2003-08-22 00:00:00NOTE IN REGARDS TO PREVIOUS CORRECTIONS-
 PERMIT WOULD HAVE BEEN ISSUED WITH A
 PROVISO BUT HAD FAILED ELECTRIC
2003-07-16 00:00:00******CORRECTIONS******
  
 1.)ADDITIONAL FEES DUE, $85.08.
  
 2.)SEE PREVIOUS CORRECTION LIST,
 ITEM #7, SIGN THE OWNER/AGENT LINE OF
 THE ENERGY CALC.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-27 Cont ID  
Sent By dpalmer Date 2003-07-16 Time 09:50 Rev Time 2.00
Received By sthyng Date 2003-06-27 Time 17:42 Sent To  
Notes
2003-06-27 00:00:00******CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE NAILING FOR THE ROOF SHEATHING
 DOES NOT COMPLY WITH CITY OF WEST PALM
 BEACH AMENDMENTS TO THE FBC, TABLE
 2306.1.
  
 2.)WHEN RESUBMITTING, SUBMIT THE
 OLD SHEETS, MARKED.
  
 3.)SHOW THE FIRESTOP REQUIRED ON THE
 BLOCK WALL DETAIL FBC 705.3.
  
 4.)THE BUILDING SECTION REFERS TO
 "WIRE LATH" ON THE BLOCK WALL.CLARIFY.
  
 5.)ADDITIONAL FEES REQUIRED.
  
 6.)THE SOILS REPORT PROVIDED WAS FOR
 THE POOL.A SOILS INVESTIGATION REPORT
 IS REQUIRED FOR THE STRUCTURE.
  
 7.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS.
  
 8.)THE BUILDING SECTION (3-3) SHOWS A
 2' FOOTER WIDTH, THE WALL SECTION SHOWS
 A 3' WIDTH (2-4).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-21 Cont ID  
Sent By kstevens Date 2003-06-27 Time 12:46 Rev Time 2.00
Received By sthyng Date 2003-05-21 Time 17:34 Sent To  
Notes
2003-05-21 00:00:00*******CORRECTIONS********
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.233-5025.
  
 3.)SEPARATE PERMITS REQUIRED.
  
 4.)THIS LOT IS IN A FLOOD ZONE.THE
 FINISHED FLOOR ELEVATION MUST BE 6"
 ABOVE BASE FLOOD ELEVATION OF 7';CITY OF
 WEST PALM BEACH MUNICIPAL CODE 94-546.
  
 5.)ENERGY CALCS REQUIRED FBC13-101.2.
  
 6.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 7.)NOTE ON THE RETAINING WALL DETAIL
 THAT THE FOOTER IS NOT TO ENCROACH UPON
 THE PROPERTY LINE.
  
 8.)THE STEEL REINFORCEMENT IS NOT
 SHOWN ON THE TYPICAL BEAM DIAGRAM, END
 BEAM ELEVATOIN, OR BUILDING SECTION.
  
 9.)THE LANGUAGE FOR WINDOW BUCK, 1X3,
 MUST COMPLY WITH FBC 1707.4.4.2.
  
 10.)THE NAILING FOR THE T&G CONFLICTS;
 ROOF FRAMING PLAN (16D) AND BUILDING
 SECTION (20D).
  
 11.)ARE THE BLOCK WALLS TO HAVE
 DRYWALL AND INSULATION?IF THEY ARE,
 SHOW ON THE BUILDING SECTION.
  
 12.)FIRESTOPPING REQUIRED, FBC 705.3.
  
 13.)THE SINGLE HUNG WINDOW APPEARS TO
 BE IN A HAZARDOUS LOCATION FBC 2405.2.
  
 14.)PROVIDE A HURRICANE ANCHOR
 SCHEDULE (SEE ATTACHED).
  
 15.)PROVIDE AREA CALCULATIONS.
  
 16.)THE DESIGN PRESSURE FOR THE 6068
 AND 8068 SLIDING GLASS DOORS EXCEED THE
 LOADS ON THE PRODUCT APPROVAL.THE
 1068 SLIDING GLASS DOOR IS NOT ON THE
 PRODUCT APPROVAL.
  
 17.)PROVIDE PRODUCT APPROVALS FOR:
 SLIDING GLASS DOORS (CHECK PRESSURES)
 SINGLE HUNG WINDOW
 2668 DOOR
 BARREL TILE ROOF

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-08-26 Cont ID  
Sent By dpalmer Date 2003-08-26 Time 16:40 Rev Time 0.50
Received By dpalmer Date 2003-08-26 Time 16:35 Sent To B
Notes
2003-08-26 00:00:00PLEASE SEE REVISED RISER DIAGRAM, PANEL
 SCHEDULES AND LOADS CALCS DONE BY
 CONTRACTOR.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-07-16 Cont ID  
Sent By sthyng Date 2003-08-22 Time 10:11 Rev Time 1.00
Received By dpalmer Date 2003-07-16 Time 09:31 Sent To B
Notes
2003-07-16 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST TWO
 REVIEWS.
 NOTES NOT ALL ADDRESSED AND PLANS STILL
 HAVE CODE ITEMS THAT DO NOT MEET NEC.
  
 2)NOTE: PLEASE SEE ATTACHED LETTER FROM
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-06-13 Cont ID  
Sent By shernand Date 2003-07-11 Time 16:11 Rev Time 1.00
Received By dpalmer Date 2003-06-13 Time 15:29 Sent To P
Notes
2003-06-13 00:00:00****************** UNSAT ***********
  
 PLEASE NOTE, NOW A RISER DIAGRAM AND
 LOAD CALCULATIONS HAVE BEEN SUBMITTED
 FOR REVIEW. PLEASE SEE THE FOLLOWING
 COMMENTS.
  
 1)NOTE; PLEASE SEE RISER, MISSING
 CONDUCTORS FROM 200A MAIN PANEL TO NEW
 125A SUB-PANEL? AS PREVIOUSLY NOTED.
 215-5
 2)NOTE; PLEASE PROVIDE OCP SIZE AT MAIN
 PANEL FOR SUB-FEED.215-5
  
 3)NOTE: PLEASE SEE LOAD CALCULATIONS.
 LOAD IS AT 285A. PLANS NOTE THAT SERVICE
 IS 400A`S?? PLEASE SEE RISER MAIN PANEL
 IS SHOWN AS 200A`S??
 PLEASE INCREASE SERVICE,TO INCLUDE NEW
 CONDUIT/WIRE ETC
  
 4)NOTE: PLEASE SEE 225-31 FOR MISSING
 MEANS OF DISC AT DETACHED STRUCTURE.
  
 5)NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE SYSTEM AT DETACHED BLDG AND
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN
 PANEL TO NEW SUB PANEL.250-30
 PLEASE INCLUDE COLD WATER LINE.
  
 6)NOTE: PLEASE CLARIFY SERVICE RISER,
 NOTES TO EXISTING PANEL IN GARAGE?
 IF 200A PANEL SHOWN ON RISER IS ALL NEW?
 IS PANEL IN GARAGE BEING INCLUDED IN
 ENTIRE SERVICE? PLEASE SEE 230-72 FOR
 GROUPING OF MAINS. ONE MAIN CAN NOT BE
 OUTSIDE AND OTHER INSIDE?
  
 7)NOTE: PLEASE SUBMIT AIC RATING(S) FOR
 ALL NEW ELECTRICAL SERVICE EQUIPMENT
 BEING INSTALLED. MAINS/PANELS/BRKRS ALL
 MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT. 110-9
  
 PLEASE NOTE, DUE TO SERVICE NOT BEING
 COMPLETE AT THIS TIME, A COMPLETE REVIEW
 CAN NOT BE DONE.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-06-12 Time 15:04 Rev Time 0.33
Received By dpalmer Date 2003-05-15 Time 16:55 Sent To P
Notes
2003-05-15 00:00:00**************** UNSAT ***********
  
 1)NOTE: PLEASE SHOW HOW NEW PANEL SHOWN
 IS BEING FED?
 225-31,250-31, 215-5 ETC
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR FEED TO NEW PANEL AND EXISTING.
 220-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-08-22 Cont ID  
Sent By csiegber Date 2003-08-22 Time 08:42 Rev Time 0.00
Received By csiegber Date 2003-08-22 Time 08:42 Sent To B
Notes
2003-08-22 00:00:00TO ST DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-08-12 Cont ID  
Sent By dbaxter Date 2003-08-12 Time 15:53 Rev Time 0.00
Received By dbaxter Date 2003-08-12 Time 15:53 Sent To B
Notes
2003-08-12 00:00:00TO STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 16:11 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 16:11 Sent To E
Notes
2003-07-11 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-06-20 Cont ID  
Sent By shernand Date 2003-06-20 Time 16:05 Rev Time 0.00
Received By shernand Date 2003-06-20 Time 16:05 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-12 Cont ID  
Sent By shernand Date 2003-06-12 Time 15:03 Rev Time 0.00
Received By shernand Date 2003-06-12 Time 15:03 Sent To E
Notes
2003-06-12 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-15 Cont ID  
Sent By sthyng Date 2003-05-15 Time 15:52 Rev Time 0.00
Received By sthyng Date 2003-05-15 Time 15:52 Sent To E
Notes
2003-05-15 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 14:13 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 14:13 Sent To B
Notes
2003-05-05 00:00:00MISC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-28 Cont ID  
Sent By sgraham Date 2003-05-01 Time 09:31 Rev Time 0.00
Received By shernand Date 2003-04-28 Time 12:31 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-08-07 Cont ID  
Sent By hmoser Date 2004-08-07 Time 09:44 Rev Time 0.50
Received By hmoser Date 2004-08-07 Time 09:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-05-20 Cont ID  
Sent By kstevens Date 2003-05-17 Time 16:10 Rev Time 0.35
Received By pkrauss Date 2003-05-20 Time 10:18 Sent To B
Notes
2003-05-20 00:00:00NO MECHANICAL INFORMATION SUBMITTED
 FOR REVIEW. PLEASE PROVIDE THE FOLLOWING
 INFORMATION WITH MECHANICAL PERMIT
 APPLICATION.
  
 1.ENERGY & MANUAL J CALCS.
 2.EQUIPMENT INFORMATION (MAKE, MODEL,
 BTU OF AHU & SEER OF C.U.)
 3.EXHAUST FAN REQUIRED IN THE BATHROOM
 AREA AS PER 2001 FBC(M) 402.3.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-06-27 Cont ID  
Sent By shernand Date 2003-06-20 Time 16:05 Rev Time 1.50
Received By kstevens Date 2003-06-19 Time 18:02 Sent To B
Notes
2003-06-27 00:00:00PROVISO - 607.3.2 THERMAL EXPANSION CON-
 TROL REQUIRED

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-17 Cont ID  
Sent By dpalmer Date 2003-06-13 Time 15:31 Rev Time 0.50
Received By kstevens Date 2003-05-17 Time 15:59 Sent To M
Notes
2003-05-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) MINIMUM DISTANCE FROM CENTER OF W/C
 TO CENTER OF ADJACENT FIXTURE. IT APP-
 EARS THAT THE MEASURMENT FROM THE CENTER
 OF THE WATER CLOSET AND THE LAV IS LESS
 THAN REQUIRED. PLEASE INDICATE MEASUR-
 MENT FROM SHOWER CURB TO EDGE OF DOORWAY
 SECTION 405.3.1 (30")
 2) PLEASE PROVIDE MANUF. INFORMATION FOR
 STEAM UNIT. MUST BE LISTED.
 3) EMERGENCY PAN REQUIRED FOR WATER
 HEATER, AND THERMAL EXPANSION CONTROL IS
 REQUIRED FOR WATER HEATER. PLEASE PRO-
 VIDE WATER HEATER DETAIL.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-01 Cont ID  
Sent By shernand Date 2003-04-28 Time 12:31 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***