| Plan Review Stops For Permit 03042197 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2003-08-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-08-26 |
Time |
16:40 |
Rev Time |
1.00 |
| Received By |
sthyng |
Date |
2003-08-22 |
Time |
09:00 |
Sent To |
E |
|
| Notes |
| 2003-08-22 00:00:00 | TO DP DESK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2003-08-22 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-08-22 |
Time |
08:47 |
Rev Time |
1.00 |
| Received By |
sthyng |
Date |
2003-07-16 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2003-08-22 00:00:00 | NOTE IN REGARDS TO PREVIOUS CORRECTIONS- | | | PERMIT WOULD HAVE BEEN ISSUED WITH A | | | PROVISO BUT HAD FAILED ELECTRIC | | 2003-07-16 00:00:00 | ******CORRECTIONS****** | | | | | | 1.)ADDITIONAL FEES DUE, $85.08. | | | | | | 2.)SEE PREVIOUS CORRECTION LIST, | | | ITEM #7, SIGN THE OWNER/AGENT LINE OF | | | THE ENERGY CALC. | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2003-06-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-07-16 |
Time |
09:50 |
Rev Time |
2.00 |
| Received By |
sthyng |
Date |
2003-06-27 |
Time |
17:42 |
Sent To |
|
|
| Notes |
| 2003-06-27 00:00:00 | ******CORRECTIONS****** | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THE NAILING FOR THE ROOF SHEATHING | | | DOES NOT COMPLY WITH CITY OF WEST PALM | | | BEACH AMENDMENTS TO THE FBC, TABLE | | | 2306.1. | | | | | | 2.)WHEN RESUBMITTING, SUBMIT THE | | | OLD SHEETS, MARKED. | | | | | | 3.)SHOW THE FIRESTOP REQUIRED ON THE | | | BLOCK WALL DETAIL FBC 705.3. | | | | | | 4.)THE BUILDING SECTION REFERS TO | | | "WIRE LATH" ON THE BLOCK WALL.CLARIFY. | | | | | | 5.)ADDITIONAL FEES REQUIRED. | | | | | | 6.)THE SOILS REPORT PROVIDED WAS FOR | | | THE POOL.A SOILS INVESTIGATION REPORT | | | IS REQUIRED FOR THE STRUCTURE. | | | | | | 7.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALCS. | | | | | | 8.)THE BUILDING SECTION (3-3) SHOWS A | | | 2' FOOTER WIDTH, THE WALL SECTION SHOWS | | | A 3' WIDTH (2-4). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-05-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-06-27 |
Time |
12:46 |
Rev Time |
2.00 |
| Received By |
sthyng |
Date |
2003-05-21 |
Time |
17:34 |
Sent To |
|
|
| Notes |
| 2003-05-21 00:00:00 | *******CORRECTIONS******** | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE | | | A PERMIT CAN BE ISSUED. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION.233-5025. | | | | | | 3.)SEPARATE PERMITS REQUIRED. | | | | | | 4.)THIS LOT IS IN A FLOOD ZONE.THE | | | FINISHED FLOOR ELEVATION MUST BE 6" | | | ABOVE BASE FLOOD ELEVATION OF 7';CITY OF | | | WEST PALM BEACH MUNICIPAL CODE 94-546. | | | | | | 5.)ENERGY CALCS REQUIRED FBC13-101.2. | | | | | | 6.)PROVIDE A SOILS INVESTIGATION | | | REPORT. | | | | | | 7.)NOTE ON THE RETAINING WALL DETAIL | | | THAT THE FOOTER IS NOT TO ENCROACH UPON | | | THE PROPERTY LINE. | | | | | | 8.)THE STEEL REINFORCEMENT IS NOT | | | SHOWN ON THE TYPICAL BEAM DIAGRAM, END | | | BEAM ELEVATOIN, OR BUILDING SECTION. | | | | | | 9.)THE LANGUAGE FOR WINDOW BUCK, 1X3, | | | MUST COMPLY WITH FBC 1707.4.4.2. | | | | | | 10.)THE NAILING FOR THE T&G CONFLICTS; | | | ROOF FRAMING PLAN (16D) AND BUILDING | | | SECTION (20D). | | | | | | 11.)ARE THE BLOCK WALLS TO HAVE | | | DRYWALL AND INSULATION?IF THEY ARE, | | | SHOW ON THE BUILDING SECTION. | | | | | | 12.)FIRESTOPPING REQUIRED, FBC 705.3. | | | | | | 13.)THE SINGLE HUNG WINDOW APPEARS TO | | | BE IN A HAZARDOUS LOCATION FBC 2405.2. | | | | | | 14.)PROVIDE A HURRICANE ANCHOR | | | SCHEDULE (SEE ATTACHED). | | | | | | 15.)PROVIDE AREA CALCULATIONS. | | | | | | 16.)THE DESIGN PRESSURE FOR THE 6068 | | | AND 8068 SLIDING GLASS DOORS EXCEED THE | | | LOADS ON THE PRODUCT APPROVAL.THE | | | 1068 SLIDING GLASS DOOR IS NOT ON THE | | | PRODUCT APPROVAL. | | | | | | 17.)PROVIDE PRODUCT APPROVALS FOR: | | | SLIDING GLASS DOORS (CHECK PRESSURES) | | | SINGLE HUNG WINDOW | | | 2668 DOOR | | | BARREL TILE ROOF |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2003-08-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-08-26 |
Time |
16:40 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-08-26 |
Time |
16:35 |
Sent To |
B |
|
| Notes |
| 2003-08-26 00:00:00 | PLEASE SEE REVISED RISER DIAGRAM, PANEL | | | SCHEDULES AND LOADS CALCS DONE BY | | | CONTRACTOR. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2003-07-16 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-08-22 |
Time |
10:11 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-07-16 |
Time |
09:31 |
Sent To |
B |
|
| Notes |
| 2003-07-16 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE NOTES FROM FIRST TWO | | | REVIEWS. | | | NOTES NOT ALL ADDRESSED AND PLANS STILL | | | HAVE CODE ITEMS THAT DO NOT MEET NEC. | | | | | | 2)NOTE: PLEASE SEE ATTACHED LETTER FROM | | | FS 553.80(2)(B) WITH RESPECT TO DESIGN | | | PROFESSIONALS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-06-13 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-11 |
Time |
16:11 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-06-13 |
Time |
15:29 |
Sent To |
P |
|
| Notes |
| 2003-06-13 00:00:00 | ****************** UNSAT *********** | | | | | | PLEASE NOTE, NOW A RISER DIAGRAM AND | | | LOAD CALCULATIONS HAVE BEEN SUBMITTED | | | FOR REVIEW. PLEASE SEE THE FOLLOWING | | | COMMENTS. | | | | | | 1)NOTE; PLEASE SEE RISER, MISSING | | | CONDUCTORS FROM 200A MAIN PANEL TO NEW | | | 125A SUB-PANEL? AS PREVIOUSLY NOTED. | | | 215-5 | | | 2)NOTE; PLEASE PROVIDE OCP SIZE AT MAIN | | | PANEL FOR SUB-FEED.215-5 | | | | | | 3)NOTE: PLEASE SEE LOAD CALCULATIONS. | | | LOAD IS AT 285A. PLANS NOTE THAT SERVICE | | | IS 400A`S?? PLEASE SEE RISER MAIN PANEL | | | IS SHOWN AS 200A`S?? | | | PLEASE INCREASE SERVICE,TO INCLUDE NEW | | | CONDUIT/WIRE ETC | | | | | | 4)NOTE: PLEASE SEE 225-31 FOR MISSING | | | MEANS OF DISC AT DETACHED STRUCTURE. | | | | | | 5)NOTE: PLEASE SEE MISSING GROUNDING | | | ELECTRODE SYSTEM AT DETACHED BLDG AND | | | EQUIPMENT GROUNDING CONDUCTOR FROM MAIN | | | PANEL TO NEW SUB PANEL.250-30 | | | PLEASE INCLUDE COLD WATER LINE. | | | | | | 6)NOTE: PLEASE CLARIFY SERVICE RISER, | | | NOTES TO EXISTING PANEL IN GARAGE? | | | IF 200A PANEL SHOWN ON RISER IS ALL NEW? | | | IS PANEL IN GARAGE BEING INCLUDED IN | | | ENTIRE SERVICE? PLEASE SEE 230-72 FOR | | | GROUPING OF MAINS. ONE MAIN CAN NOT BE | | | OUTSIDE AND OTHER INSIDE? | | | | | | 7)NOTE: PLEASE SUBMIT AIC RATING(S) FOR | | | ALL NEW ELECTRICAL SERVICE EQUIPMENT | | | BEING INSTALLED. MAINS/PANELS/BRKRS ALL | | | MUST BE RATED FOR THE AVAILABLE FAULT | | | CURRENT. 110-9 | | | | | | PLEASE NOTE, DUE TO SERVICE NOT BEING | | | COMPLETE AT THIS TIME, A COMPLETE REVIEW | | | CAN NOT BE DONE. | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-05-15 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-12 |
Time |
15:04 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-05-15 |
Time |
16:55 |
Sent To |
P |
|
| Notes |
| 2003-05-15 00:00:00 | **************** UNSAT *********** | | | | | | 1)NOTE: PLEASE SHOW HOW NEW PANEL SHOWN | | | IS BEING FED? | | | 225-31,250-31, 215-5 ETC | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | FOR FEED TO NEW PANEL AND EXISTING. | | | 220-3 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2003-08-22 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-08-22 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-08-22 |
Time |
08:42 |
Sent To |
B |
|
| Notes |
| 2003-08-22 00:00:00 | TO ST DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2003-08-12 |
|
|
Cont ID |
|
| Sent By |
dbaxter |
Date |
2003-08-12 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
dbaxter |
Date |
2003-08-12 |
Time |
15:53 |
Sent To |
B |
|
| Notes |
| 2003-08-12 00:00:00 | TO STHYNG DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2003-07-11 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-11 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-11 |
Time |
16:11 |
Sent To |
E |
|
| Notes |
| 2003-07-11 00:00:00 | DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2003-06-20 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-20 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-20 |
Time |
16:05 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-06-12 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-12 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-12 |
Time |
15:03 |
Sent To |
E |
|
| Notes |
| 2003-06-12 00:00:00 | DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-05-15 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-05-15 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-05-15 |
Time |
15:52 |
Sent To |
E |
|
| Notes |
| 2003-05-15 00:00:00 | TO DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-05-05 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-05 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-05 |
Time |
14:13 |
Sent To |
B |
|
| Notes |
| 2003-05-05 00:00:00 | MISC BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-04-28 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2003-05-01 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-28 |
Time |
12:31 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-08-07 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2004-08-07 |
Time |
09:44 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2004-08-07 |
Time |
09:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2003-05-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-05-17 |
Time |
16:10 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2003-05-20 |
Time |
10:18 |
Sent To |
B |
|
| Notes |
| 2003-05-20 00:00:00 | NO MECHANICAL INFORMATION SUBMITTED | | | FOR REVIEW. PLEASE PROVIDE THE FOLLOWING | | | INFORMATION WITH MECHANICAL PERMIT | | | APPLICATION. | | | | | | 1.ENERGY & MANUAL J CALCS. | | | 2.EQUIPMENT INFORMATION (MAKE, MODEL, | | | BTU OF AHU & SEER OF C.U.) | | | 3.EXHAUST FAN REQUIRED IN THE BATHROOM | | | AREA AS PER 2001 FBC(M) 402.3.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-06-27 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-20 |
Time |
16:05 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2003-06-19 |
Time |
18:02 |
Sent To |
B |
|
| Notes |
| 2003-06-27 00:00:00 | PROVISO - 607.3.2 THERMAL EXPANSION CON- | | | TROL REQUIRED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-05-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-06-13 |
Time |
15:31 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-05-17 |
Time |
15:59 |
Sent To |
M |
|
| Notes |
| 2003-05-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) MINIMUM DISTANCE FROM CENTER OF W/C | | | TO CENTER OF ADJACENT FIXTURE. IT APP- | | | EARS THAT THE MEASURMENT FROM THE CENTER | | | OF THE WATER CLOSET AND THE LAV IS LESS | | | THAN REQUIRED. PLEASE INDICATE MEASUR- | | | MENT FROM SHOWER CURB TO EDGE OF DOORWAY | | | SECTION 405.3.1 (30") | | | 2) PLEASE PROVIDE MANUF. INFORMATION FOR | | | STEAM UNIT. MUST BE LISTED. | | | 3) EMERGENCY PAN REQUIRED FOR WATER | | | HEATER, AND THERMAL EXPANSION CONTROL IS | | | REQUIRED FOR WATER HEATER. PLEASE PRO- | | | VIDE WATER HEATER DETAIL. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2003-05-01 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-28 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
I |
|
| Notes |
|
|