Plan Review Details - Permit 03042121
Plan Review Stops For Permit 03042121
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-07-16 Cont ID  
Sent By rmcdouga Date 2003-07-16 Time 11:37 Rev Time 3.00
Received By rmcdouga Date 2003-07-16 Time 11:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-07-08 Cont ID  
Sent By kstevens Date 2003-07-12 Time 16:10 Rev Time 3.00
Received By rmcdouga Date 2003-07-08 Time 10:35 Sent To  
Notes
2003-07-08 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SUBSURFACE SOIL BORING TEST
 REPORT FROM A FL LICENSED SOIL ENGINEER
 AS REQUIRED BY CITY AMENDMENTS TO
 FBC 1804.2.2.
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 INDICATE THE IMPORTANCE FACTOR (1.00) &
 THE BUILDING CATEGORY ON THE PLANS (II).
 THE INTERNAL PRESSURE COEFFICENT DOES
 NOT HAVE THE +/- IN FRONT OF IT WHICH
 INDICATES POSITIVE AND NEGATIVE PRESSURE
  
 5) BECAUSE A FULL BATHROOM IS PROVIDE AT
 HABITABLE GRADE LEVEL, ONE OF THE FULL
 BATHROOMS IS REQUIRED TO HAVE A DOOR
 WITH A 29" CLEAR OPENING.
 SEE FBC 11-4.23.
  
 6) SOME OF THE VALUES LISTED IN THE
 TRUSS ANCHOR SCHEDULE ARE INCORRECT.
 PLEASE INDICATE VALUES FROM THE 2003 USP
 CATALOG WHICH DO NOT INCLUDE THE ONE-
 THIRD INCREASE ON THE STEEL CALCULATIONS
 PER FBC 1609.4.
  
 7) PLEASE UPDATE THE HUGHES AND SEMCO
 CONNECTORS SPECIFIED ON THE SECTIONS ON
 A6 TO CURRENT USP CONNECTORS. HUGHES AND
 SEMCO WERE PURCHASED BY USP.
  
 8) THE CALCULATIONS FOR THE ENERGY
 FORM ARE BASED ON CONDITIONED SPACE
 AREA WHICH DOES NOT CORRESPOND WITH THE
 CONDITIONED AREA LISTED ON THE PLANS.
 PLEASE SUBMIT NEW ENERGY CALCULATIONS
 WITH THE CORRECT CONDITIONED FLOOR AREA.
  
 9)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - CASEMENT WINDOWS
 - IN ADDITION TO THE DRAWING FOR THE
 GARAGE DOOR THE SBCCI REPORT #9606C IS
 REQUIRED.
  
 10) THE PRODUCT APPROVAL FOR THE WINDOW
 MULLIONS DO NOT MEET THE WINDLOAD
 REQUIREMENTS AT THE LIVING ROOM WINDOW.
 THE PRODUCT APPROVAL LIMITS THE NUMBER
 OF WINDOWS THAT CAN BE MULLED TOGETHER
 TO FIVE (5). THE LIVING ROOM WINDOW HAS
 SIX (6). SUBMIT A PRODUCT APPROVAL FOR
 MULLIONS THAT WILL MEET WINDLOADS FOR
 THIS OPENING OR PROVIDE DETAIL ON THE
 PLAN FOR AN ENGINEERED MULLION OR A
 LINTEL BETWEEN THE TOP AND BOTTOM
 WINDOWS.
  
 11) SUBMIT THE MANUFACTURER'S SPECS. AND
 UL LISTING INFORMATION FOR THE OPTIONAL
 BBQ IF IT WILL BE INSTALLED.
  
 12) THE NEW SHEETS ARE REQUIRED TO HAVE
 THE WET SIGNATURE OF THE ARCHITECT. A
 SIGNATURE STAMP IS NOT ACCEPTABLE.
 SEE FAC 61G1-16.003
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-04 Cont ID  
Sent By rmcdouga Date 2003-06-04 Time 11:07 Rev Time 4.00
Received By rmcdouga Date 2003-06-04 Time 11:07 Sent To  
Notes
2003-06-04 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY CITY AMEND. TO FBC 1804.2.2.
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 INDICATE THE ABOVE ON THE PLANS.
  
 5) THE SITE PLAN DOES NOT INDICATE THE
 DISTANCE TO THE BUILDING LINES TO THE
 PROPERTY LINES. THE PLAN WAS SCALED TO
 DETERMINE THE DISTANCE FROM THE PROPERTY
 LINE TO THE WALL AT THE LEFT ELEVATION.
 IT WAS DETERMINED TO BE OVER 20' FOR
 TABLE 600 CALCULATIONS.
  
 6) REVISE WINDLOAD SCHEDULE ON A1 TO
 REFERENCE THE CURRENT CODE WHICH IS THE
 2001 FBC. ALSO THE NEGATIVE PRESSURES
 ARE GIVEN WITH POSITIVE SIGNS.
  
 7) SOME TEXT ON A2 IS UPSIDE DOWN.
  
 8) THE FOUNDATION PLAN DOES NOT INDICATE
 THE AMOUNT OF RECESS FOR THE MASTER BATH
 SHOWER OR THE SHOWER IN BATH #4. PLEASE
 CLARIFY.
  
 9) PROVIDE A FULL BATH WITH A DOOR THAT
 HAS A 29" CLEAR OPENING. SEE FBC CHAPTER
 11.
  
 10) SAFETY GLAZING IS REQUIRED IN THE
 MASTER BATH WINDOW PER FBC 2405.2.
  
 11) REVISE BUCK DETAILS ON A4. THE S.G.D
 AND WINDOW FRAMES ARE REQUIRED TO BE
 FASTENED THROUGH THE 1X BUCKS INTO THE
 COCRETE SUBSTRATE. THE 2X DOOR BUCKS ARE
 REQUIRED TO EXTEND TO THE INTERIOR FACE
 OF THE DOOR JAMB. SEE FBC 1707.4.2.2.
  
 12) THE 2' WIDE CASEMENT WINDOWS IN
 BEDROOM #2 ON A4 DO NOT COMPLY WITH THE
 EGRESS REQUIREMENTS OF FBC 1005.4.
  
 13) INDICATE ON PLANS THAT LIBRARY IS
 NOT TO BE USED AS A SLEEPING ROOM OR
 PROVIDE WINDOWS THAT COMPLY WITH FBC
 1005.4.
  
 14) THE ADJACENT WALL IN THE GARAGE IS
 REQUIRED TO BE INSULATED AND THE DOOR TO
 CONDITIONED SPACE IS REQUIRED TO BE
 SOLID CORE OR INSULATED. INDICATE THIS
 ON A3 OF PLANS.
  
 15) UPDATE THE TRUSS ANCHOR SCHEDULE ON
 A5. HUGHES WAS PURCHASED BY USP SOMETIME
 AGO AND ARE NO LONGER BEING PRODUCED.
 NOTE: THE 2001 FBC NO LONGER ALLOWS THE
 ONE THIRD INCREASE IN STEEL CALCULATIONS
 THEREFORE, THE VALUES FOR SOME TRUSS
 CONNECTORS ARE LOWER. SEE THE 2003 USP
 CATALOG OR THE 2002 SIMPSON HIGH WIND
 CATALOG FOR CORRECTED VALUES.
  
 16) THE TIE BEAMS FOR THE GOLF CART
 GARAGE DOOR AND THE LIBRARY WINDOWS ARE
 NOT INDICATED ON THE ROOF PLAN ON A5.
 TB-8 IS INDICATED IN THE MIDDLE OF THE
 LIBRARY.
  
 17) SPECIFY THE LENGTH/EMBED DEPTH OF
 THE #5 STUDS FOR THE EMBED CONNECTOR AND
 THE WEDGE ANCHORS AND EXPANSION BOLTS
 FOR THE TRUSS ANCHORS AND HOLD DOWNS ON
 A5.
  
 18) THE ROOF/FLOOR TRUSS ANCHOR NOTES ON
 A5 INCORRECTLY STATES THAT THE LOAD
 VALUES OF A STRAP INCREASES IN MULTIPLES
 OF THE NUMBER OF STRAPS. THE CONE PULL
 OUT OF THE CONCRETE BEAM LIMITS THE LOAD
 VALUES FOR MULTIPLE STRAPS. SEE TRUSS
 CATALOGS FOR LOAD VALUES OF MULTIPLE
 STRAPS.
  
 19) PROVIDE A ROOF SHEATHING NAILING
 SCHEDULE. SEE CITY AMENDMENTS TO 2001
 FBC TABLE 2306.1.
  
 20) INDICATE THE CEILING FINISHES FOR
 THE ENTRY AND COVERED PATIO.
  
 21)UPDATE THE TRUSS CONNECTORS SPECIFIED
 ON A6.
  
 22)THE SECTIONS ON A6 ARE NOT IDENTIFIED
 BY NUMBER AND SOME OF THE TEXT IS
 UPSIDE DOWN.
  
 23) THE DIMENSIONS AT THE LIVING ROOM
 WINDOW ON THE REAR ELEVATION INDICATES
 1' BETWEEN THE WINDOWS. PLEASE CLARIFY.
  
 24) THE CONDITIONED FLOOR AREA ON THE
 ENERGY CALCULATIONS DOES NOT MATCH THE
 A/C AREA LISTED ON A4 OF THE PLANS.
  
 25) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - CASEMENT WINDOWS
 - NEED SBCCI REPORT 9606C IN ADDITION TO
 THE DRAWING FOR THE OVERHEAD GARAGE DOOR
 - THE MULLIONS DO NOT MEET THE WINDLOAD
 PRESSURES FOR THE OPENING AT THE LIVING
 ROOM WINDOW. THE PRODUCT APPROVAL ALSO
 LIMITS THE NUMBER OF WINDOWS MULLED
 TOGETHER TO 5 UNITS.
  
 26) SUBMIT THE MANUFACTURER'S SPECS. AND
 UL LISTING INFORMATION FOR THE OPTIONAL
 BBQ IF IT IS TO BE INSTALLED.
  
 27) REFER TO NOTES WRITTEN ON PLANS.
 SUBMIT THE OLD PAGES ALONG WITH NEW,
 WHEN RESUBMITTING.
  
 28) 1803.1.3 EXCAVATION FOR ANY PURPOSE
 SHALL NOT EXTEND WITHIN 1 FT OF THE
 ANGLE OF REPOSE OR NARURAL SLOPE OF THE
 SOIL UNDER ANY FOOTING OR FOUNDATION,
 UNLESS SUCH FOOTING OR FOUNDATION IS
 FIRST PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT. PLEASE BE AWARE OF
 THIS WHEN EXCAVATING FOR POOL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-01-20 Cont ID  
Sent By btrobaug Date 2004-01-20 Time 13:26 Rev Time 0.50
Received By btrobaug Date 2004-01-20 Time 13:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-01-15 Cont ID  
Sent By btrobaug Date 2004-01-20 Time 13:26 Rev Time 0.33
Received By btrobaug Date 2004-01-15 Time 14:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-13 Cont ID  
Sent By csiegber Date 2004-01-13 Time 14:42 Rev Time 0.50
Received By btrobaug Date 2003-05-13 Time 15:27 Sent To P
Notes
2003-05-13 00:00:00PROVISO
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE CORRECT THE FOLLOWING FOR CODE
 COMPLIANCE AND RESUBMIT FOR
 REVIEW,PRIOR TO ROUGH INSPECTION.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST BE #2 PER 250-66 & MUST BE
 CONTINUOUS PER 250-64(C).
  
 2} RECEPTACLES NEED TO BE ADDED IN THE
 LIBRARY TO COMPLY WITH 210-52(A)(1).
  
 3} THE RECEPTACLE SPACING IN THE LIVING
 ROOM DOES NOT MEET 210-52 AND ARE SHOWN
 OFF THE WALL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-01-20 Cont ID  
Sent By btrobaug Date 2004-01-20 Time 13:25 Rev Time 0.00
Received By btrobaug Date 2004-01-20 Time 13:25 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-01-13 Time 14:42 Rev Time 0.00
Received By csiegber Date 2004-01-13 Time 14:42 Sent To E
Notes
2004-01-13 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-06 Cont ID  
Sent By alange Date 2003-08-06 Time 15:59 Rev Time 0.00
Received By alange Date 2003-08-06 Time 15:59 Sent To P
Notes
2003-08-06 00:00:00TO KS DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 16:51 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 16:51 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-25 Cont ID  
Sent By shernand Date 2003-06-25 Time 10:57 Rev Time 0.00
Received By shernand Date 2003-06-25 Time 10:57 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-28 Cont ID  
Sent By shernand Date 2003-04-28 Time 10:38 Rev Time 0.00
Received By shernand Date 2003-04-28 Time 10:38 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-04 Cont ID  
Sent By kstevens Date 2003-06-30 Time 09:27 Rev Time 0.00
Received By rmcdouga Date 2003-06-04 Time 14:28 Sent To  
Notes
2003-06-04 00:00:00OK PER P. KRAUSS 5-24-03

Review Stop P PLUMBING
Rev No 5 Status P Date 2003-08-12 Cont ID  
Sent By kstevens Date 2003-08-12 Time 08:16 Rev Time 0.50
Received By kstevens Date 2003-08-12 Time 08:13 Sent To  
Notes
2003-08-12 00:00:00REVISION OK - SANITARY RISER DIAGRAM -
 CHANGED LOCATION OF LAUNDRY TRAY.

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-07-14 Cont ID  
Sent By alange Date 2003-08-06 Time 15:59 Rev Time 0.25
Received By kstevens Date 2003-07-14 Time 15:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-07-12 Cont ID  
Sent By kstevens Date 2003-07-12 Time 16:10 Rev Time 0.50
Received By kstevens Date 2003-07-12 Time 16:10 Sent To B
Notes
2003-07-12 00:00:00DENIED
 REFERENCE: FLORIDA STATUTES
  
 G1G1-16.004 TITLE BLOCK...
 A TITLE BLOCK MUJST APPEAR ON ALL
 ARCHITECTURAL DRAWINGS AND SPECIFICATION
 SHEETS. THE TITLE BLOCK MUST, AT A MINI-
 MUM, CONTAIN THE FOLLOWING INFORMATION.
 1) FIRM NAME, ADDRESS AND TELEPHONE NO.
 2) FIRM LICENSE NUMBER
 ECT. - SEE ATTACHED SHEET
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-06-30 Cont ID  
Sent By shernand Date 2003-07-11 Time 16:51 Rev Time 0.50
Received By kstevens Date 2003-06-30 Time 09:13 Sent To M
Notes
2003-06-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS. CHAPTER
 1, ADMIN. CODE
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS NOR DOES RISER REFLECT
 THE FLOOR PLAN.
 2) NO LOOP PIPING IN MASTER BATH. BIDET
 REQUIRES A TRAP.
 3) W/M REQUIRES A TRAP AND A STANDPIPE.
 4) SHOWER MISSING BATH #2
 5) TUB MISSING BATH #3
 6) IS THE FIXTURE BY THE KITCHEN A BAR
 SINK OR A LAV?
 7) PIPE SIZING MISSING.
 SECTIONS 104.2.1, 802.4, 706.3
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-17 Cont ID  
Sent By shernand Date 2003-06-25 Time 10:57 Rev Time 0.33
Received By kstevens Date 2003-05-17 Time 09:02 Sent To M
Notes
2003-05-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN.
 2) 909.1 WASH MACHINE & LAUNDRY SINK
 SHALL NOT DRAIN INTO THE HORIZONTAL WET
 VENT OF THE BATHROOM GROUP. W/M & L/T
 SHALL TIE IN DOWNSTREAM OF THE BATHROOM
 GROUP.
 3) VERTICAL RISE ON AN ISOMETRIC INDICAT
 ES A SECOND FLOOR.
 4) 905.3 NO HORIZONTAL DRY VENTS.
 5) KITCHEN SINK MISLABLED AS LAVS.
 6) BIDET NOT VENTED
 7) PIPE SIZES MISSING
 (SEE SHEET ATTACHED TO PERMIT #03041590
 FOR AN EXAMPLE OF APPROVED SANT. RISER
 DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-28 Time 10:38 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***