Plan Review Details - Permit 03042119
Plan Review Stops For Permit 03042119
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-11-09 Cont ID  
Sent By jgomez Date 2004-11-09 Time 09:54 Rev Time 0.00
Received By jgomez Date 2004-11-09 Time 09:52 Sent To E
Notes
2004-11-09 00:00:00BUILDING PROVISO:
 1-RESUBMIT PRODUCT APPROVAL FOR GARAGE
 DOOR WITH DRAWINGS THAT ARE LEGIBLE.
  
 2-PROVIDE PRODUCT APPROVAL FOR FIXED
 WINDOWS FOR LARGE SIZE WINDOW AS SHOWN
 ON PLANS AT MASTER BEDROOM.
  
 3-PROVIDE UL LISTING AND COMPLETE SPECS
 PACKAGE FOR FIREPLACE AND BBQ AS REQ'D
 BY SECTIONS 2806 & 2808 FBC 2001.
  
 4-PROVIDE COMPLETE FRAMING DETAILS AND
 SPECS FOR COLUMNS BETWEEN FRENCH DOORS
 AT FAMILY ROOM AREA. SEC. 104.2.1.2
 CITY
 AMENDMENTS TO FBC 2001.
  
 5-PROVIDE COMPLETE SPECIFICATIONS FOR
 ROOF TILE SYSTEM FASTENING AS REQUIRED
 BY SEC. 104.2.1.1 CITY AMENDMENTS TO
 FBC
  
 6-ROOF FRAMING PLAN TO INCLUDE 10PSF OR
 30PSF ATTIC LIVE LOAD AS REQ'D BY TABLE
 1604.1 FBC 2001. REVISE AS REQUIRED.
  
 7-REVISE TRUSS ANCHOR SCHEDULE. TA22
 CONNECTOR DON'T PROVIDE 5" MIN.
 EMBEDMENT AND REVISE NUMBER OF FASTENERS
 SPECIFIED FOR TAPL14. SEE USP CATALOGUE
 AND REVISE AS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-07-14 Cont ID  
Sent By jgomez Date 2003-07-14 Time 13:09 Rev Time 3.00
Received By jgomez Date 2003-07-14 Time 13:09 Sent To PC
Notes
2003-07-14 00:00:00SECOND CHECKLIST:
 1-DRAWINGS TO HAVE ORIGINAL SIGNATURE
 (NO RUBBER STAMP) AS REQ'D BY CHAPTER
 481 FLORIDA STATUTES WHEN SUBMITTING
 DRAWINGS FOR PUBLIC RECORDS
 **ALSO, ARCHITECT NEED TO INCLUDE HIS
 LICENSE #. SEE CHAPTER 481 FL. STATUTE
 2-PAY IMPACT FEES AND BRING BACK PAID
 RECEIPT AND STAMPED DRAWINGS.
 3-NEED RECORDED NOTICE OF COMMENCEMENT.
 4-PROVIDE COMPLETE DETAIL AND SPECS FOR
 CONCRETE BOLLARD IN THE GARAGE TO
 PROTECT WATER HEATER. SPECIFY HOW IS
 CONCRETE POST REINFORCED AND SPECIFY
 ANCHORING AT THE BASE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 5-PROVIDE AT LEAST ONE COMPLETE BATHROOM
 (NO THE POWDER ROOM) WITH DOOR THAT
 ALLOWS 29" CLEAR OPENING AS REQUIRED
 BY SECTION 11-11 FBC 2001.
 6-AHU HANGING DETAIL: A)SPECIFY SIZE OF
 HANGING ROD OR CHAIN.
 B)CLARIFY WHY IS UNIT HANGING FROM BOTT.
 CHORD AND NOT THE TOP CHORD. ALSO,
 NEED TO PROVIDE SPECS TO TRUSS ENG'R
 TO DESIGN BOTTOM CHORD TO RECEIVE THIS
 AHU LOAD. SECTION 104.2.1.2 OF CITY
 AMENDMETS TO FBC 2001.
 7-ENERGY CALCULATIONS WERE NOT REVISED:
 A)DON'T MATCH ORIENTATION OF THIS HOUSE.
 IT WAS DONE FOR LOT #6. NEED WORST
 CASE SCENARIO CALCS. OTHERWISE, NEED
 SITE SPECIFIC ENERGY CALCULATIONS.
 B)NEED PREPARER'S ORIGINAL SIGNATURE.
 C)PROVIDE COMPLETE INFORMATION ON TOP OF
 FORM, INCLUDING OWNER.
  
 8-CHIMNEY FRAMING PLAN AND SECTION DON'T
 MATCH. CLARIFY ANCHORS TO BE USED AND
 ATTACHMENT TO TOP CHORD OR BOTTOM
 CHORD OF THE TRUSSES. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 ALSO, DETAIL IS INCOMPLETE. SEE PLANS
 9-PROVIDE COMPLETE STRUCTURAL DETAIL
 FOR ATTACHMENT OF 2X BUCKS TO STEEL
 COLUMN. SPECIFY ALL FASTENERS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 10-CLARIFY DETAIL FOR TOP OF COLUMN CAP.
 THERE ARE 2 DIFFERENT SIZES OF NELSON
 STUDS SPECIFIED ON THE DETAIL.
 11-REVISE SPACING SPECIFIED FOR WWM
 SUPPORTS FOR CONCRETE SLAB. SEE SEC.
 1909.3 FBC 2001.
 12-OWES $442.89 FOR UPDATED VALUATION
 AND RADON FEES. ALSO, THERE WILL BE
 ADDITIONAL RE-SUBMITTAL FEES.
 13-NEED PRODUCT APPROVAL FOR: A)GARAGE
 SIDE DOOR. B)GARAGE DOORS. C)ENTRY
 DOORS WITH TRANSOM ABOVE ASSEMBLY AS
 SHOWN ON PLANS. D)FIXED WINDOWS WITH
 SIZES AS SHOWN ON PLANS. E)WINDOWS AND
 DOORS MULLIONS. F)FRENCH DOORS WITH
 TRANSOM ABOVE AS SHOWN ON PLANS.
 G)FIREPLACE UL LISTING AND COMPLETE
 SPECS. H)BBQ UL LISTING AND SPECS.
 I)ROOF TILE. J)OVAL AND ARCHED WINDOWS
 AS SHOWN ON PLANS.
 **NOTE: PROVIDE IMPACT RESISTANT GLASS
 AND MULLIONS PRODUCT APPROVALS AS
 SPECIFIED ON PLANS. OTHERWISE, PROVIDE
 COMPLETE STORM SHUTTERS INFORMATION.
  
 14-SHEET A2: A)UPDATE SEMCO CONNECTOR
 SPECIFY ON SECTION DETAIL. SEE PLAN.
 B)WHERE IS WOOD LEDGER DETAIL #3. SEE
 PLANS FOR COMMENTS.
 15-SHEET A3: A)SPECIFY COLUMNS BY LIVING
 ROOM. SEE PLANS FOR COMMENTS.
 B)CLARIFY STEEL COLUMN DETAILS. THERE
 ARE DIFFERENT ANCHOR SIZES SPECIFIED.
 REVISE AS REQUIRED.
 16-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEC. 2405.2 FBC 2001. SEE PLANS.
 17-SHEET A5: MISSING SOME CONNECTORS.
 SEE PLANS FOR COMMENTS.
 18-PROVIDE SOIL TEST REPORT.
 19-PROVIDE COMPLETE SPECS FOR CEILING
 CONSTRUCTION AT FRONT AND REAR PORCH.
 SEE ASTM C926 AND ASTM C1063 FOR MIN.
 STUCCO THICKNESS AND MIN. FASTENER
 TYPE AND SPACING.
 20-UPDATE TRUSS ANCHOR SCHEDULE. SEE
 USP 2003 CATALOGUE & SEC. 1609.4.3
  
 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-10 Cont ID  
Sent By pkrauss Date 2003-07-14 Time 07:24 Rev Time 4.00
Received By jgomez Date 2003-06-10 Time 10:39 Sent To  
Notes
2003-06-10 00:00:00BUILDING REVIEW CHECKLIST:
 1-PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND RECEIPT.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-UPDATE WIND LOAD CRITERIA ON SHEET A1.
 SEE FBC 2001, NOT SBC 1997. **REVISE
 THE DESIGN PRESSURES AND PROVIDE ALL
 5 ITEMS REQUIRED BY SEC. 1606.1.7 FBC.
 4-PROVIDE COMPLETE DETAIL AND SPECS FOR
 PROTECTION OF GAS WATER HEATER IN THE
 GARAGE. SEC. 104.2.1.2 CITY AMENDMENTS
 5-PROVIDE AT LEAST ONE COMPLETE BATHROOM
 WITH DOOR THAT PROVIDES 29" CLEAR OP'G
 AS REQUIRED BY SEC. 11-11 FBC 2001.
 6-PROVIDE COMPLETE STRUCTURAL DETAIL AND
 SPECIFICATIONS FOR HANGING AIR HANDLER
 UNIT FROM CEILING. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 7-ENERGY CALCULATIONS: A)THIS ENERGY
 CALCULATIONS DON'T MATCH ORIENTATION
 OF THIS HOUSE. THIS IS NOT A WORST
 CASE CALCULATION. THEREFORE, ENERGY
 CALCS SHALL BE DONE TO THE SPECIFIC
 ORIENTATION OF THE HOUSE. REVISE AS
 REQUIRED. AND, NEED ORIGINAL SIGNATURE
 B)NEED ORIGINAL SIGNATURE BY PREPARER OF
 THE ENERGY CALCULATIONS.
 C)PROVIDE COMPLETE INFORMATION ON TOP OF
 FORM. EG: OWNER, ETC.
 8-PROVIDE COMPLETE FRAMING INFORMATION
 FOR CUPOLAS & CHIMNEY. PROVIDE FRAMING
 PLANS & STRUCTURAL WALL SECTIONS THAT
 SHOW ALL FASTENERS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 9-PROVIDE COMPLETE STRUCTURAL FRAMING
 DETAILS AND SPECS FOR CONNECTIONS OF
 WINDOWS AND STRUCTURAL MULLIONS TO THE
 STEEL COLUMNS AT LIVING ROOM AREA.
 SEE PRODUCT APPROVALS FOR REQUIRED
 INFORMATION. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 10-PROVIDE DETAIL/SPECS FOR CONNECTION
 AT TOP OF STEEL COLUMNS AT LIVING AREA
 WINDOWS AND AT ENTRY PORCH. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 11-PROVIDE SPECS FOR WWM SUPPORTS AS
 REQUIRED BY SEC. 1909.3 FBC 2001.
 12-REVISE STRUCTURAL BUCK DETAIL FOR
 DOORS USING 2X BUCK. SEE SECTION
 1707.4.4.2 FBC 2001.
 13-OWES $442.89 FOR UPDATED VALUATION
 AND RADON FEES.
 14-PROVIDE PRODUCT APPROVAL FOR:
 A)GARAGE SIDE DOOR.
 B)GARAGE DOORS.
 C)ENTRY DOORS W/ TRANSOM ABOVE ASSEMBLY
 AS SHOWN ON PLANS.
 D)FIXED WINDOWS. SIZES AS SHOWN ON PLANS
 E)FRENCH DOORS W/ TRANSOM ABOVE ASSEMBLY
 AS SHOWN ON PLANS.
 F)WINDOW & DOOR MULLION AS SHOWN ON PLAN
 G)FIREPLACE LISTING AND COMPLETE SPECS.
 H)BBQ UL LISTING AND COMPLETE SPECS.
 I)ROOF TILE.
 J)OVAL & ARCHED WINDOWS AS SHOWN ON PLAN
  
 15-SHEET A2: A)UPDATE SEMCO CONNECTOR
 SPECIFIED ON SECTION. ALSO, WHERE IS
 WOOD LEDGER DETAIL 3?. SEE PLAN.
 B)TYP. WALL SECTION: UPDATE HUGHES
 CONNECTOR SPECIFIED (NOT IN BUSINESS).
  
 16-SHEET A3: A)SPECIFY COLUMN BY FAMILY
 ROOM AREA. SEE PLAN.
 B)THERE ARE DIFFERENT SPECS FOR STEEL
 COLUMNS. CLARIFY. SEE COMMENTS ON PLAN
  
 17-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE SHEET A4 AND SEC. 2405.2 FBC 2001.
 18-SHEET A5: MISSING SOME CONNECTORS AND
 SEE PLAN FOR ADDITIONAL COMMENTS.
 19-PROVIDE SOIL TEST REPORT.
 20-PROVIDE SPECIFICATIONS FOR CEILING
 CONSTRUCTION AT REAR AND FRONT PORCH.
 SPECIFY ALL FASTENERS. SEE ASTM C-926
 AND ASTM C-1063.
 **ALSO, SPECIFY STUCCO THICKNESS OF 7/8"
 AT FRAMED WALLS AS REQ'D BY ASTM C-926
 21-UPDATE TRUSS ANCHOR SCHEDULE TO
 COMPLY WITH SECTION 1606.4.3 FBC 2001
 WHICH DOESN'T ALLOW THE ALLOWABLE
 STRESS INCREASE TO BE USED. SEE USP
 CATALOGUE THAT HAS UPDATED VALUES.
 22-PROVIDE ROOF SHEATHING NAILING
 DIAPHRAGM SHOWING FASTENERS & SPACING
 AND SHOWING NAILING ZONES. SEE SECTION
 2306 CITY AMENDMENTS TO FBC 2001.
 23-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS. INCLUDING KEY PLAN,
 INSTALLATIONSCHEDULE, AND CLEARLY
 MARK ON ENGINEERED DRAWINGS SPECIFIC
 MOUNTING CONDITIONS, ANCHOR TYPE AND
 SPACING TO BE USED ACCORDING TO THE
 EDGE DISTANCE, CONNECTION TYPE, PANEL
 SPAN, DESIGN PRESSURES & STRUCTURE TO
 BE ATTACHED TO.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-11-09 Cont ID  
Sent By btrobaug Date 2004-11-09 Time 18:33 Rev Time 0.50
Received By btrobaug Date 2004-11-09 Time 18:07 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-13 Cont ID  
Sent By btrobaug Date 2003-05-13 Time 17:13 Rev Time 0.75
Received By btrobaug Date 2003-05-13 Time 16:51 Sent To P
Notes
2003-05-13 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO ROUGH INSPECTION.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST BE #2 PER 250-66 AND CONTINUOUS
 PER 250-64(C).
  
 2} THE SMOKE DETECTORS AT THE MASTER BED
 ROOM MUST BE INSIDE THE ROOMS TO COMPLY
 WITH 8-1.4.2 NFPA-72.
 A) BEDROOM #4 AS WELL.
  
 3} ADD RECEPTACLES IN THE LIBRARY TO
 COMPLY WITH 210-52(A)(1).
  
 4} ADD A RECEPTACLE IN THE LIVING ROOM
 TO COMPLY WITH 210-52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-11-05 Cont ID  
Sent By csiegber Date 2004-11-05 Time 16:35 Rev Time 0.00
Received By csiegber Date 2004-11-05 Time 16:35 Sent To B
Notes
2004-11-05 00:00:00TO JG DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-07 Time 09:17 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 09:17 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-28 Cont ID  
Sent By shernand Date 2003-04-28 Time 10:51 Rev Time 0.00
Received By shernand Date 2003-04-28 Time 10:51 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-14 Cont ID  
Sent By kstevens Date 2003-07-12 Time 06:38 Rev Time 0.10
Received By pkrauss Date 2003-07-14 Time 07:24 Sent To B
Notes
2003-07-14 00:00:00PLANS APPROVED 5/24/03 BY PHK

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-12 Cont ID  
Sent By kstevens Date 2003-07-12 Time 06:38 Rev Time 0.33
Received By kstevens Date 2003-07-12 Time 06:37 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-17 Cont ID  
Sent By shernand Date 2003-07-07 Time 09:17 Rev Time 0.33
Received By kstevens Date 2003-05-17 Time 08:01 Sent To M
Notes
2003-05-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. WASH MACHINE SHALL
 TIE IN DOWNSTREAM OF LAUNDRY SINK, (NOT
 ON L/SINK WASTE ARM), AND REQUIRES A
 TRAP AND A STANDPIPE. - LABLE LAUNDRY
 SINK, (NOT LAV), - CLEAN OUT SHALL BE
 LOCATED 4' ABOVE FINISHED FLOOR ABOVE
 WASH MACHINE. - BIDET MISSING FROM RISER
 - SHOWER FOR CABANA MISSING FROM RISER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-28 Time 10:51 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***