| Plan Review Stops For Permit 03042107 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2003-05-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-05-19 |
Time |
14:42 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2003-05-19 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2003-05-19 00:00:00 | BUILDING PROVISO: | | | STOREFRONT @ LOUNGE BE SAFETY GLASS!!! | | | FL BLD CODE 2405.2 HAZARDOUS LOCATION | | | PROVIDE SAFETY GLASS FOR THIS LOCATION: | | | STOREFRONT @ LOUNGE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-08-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-08-04 |
Time |
15:08 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-08-04 |
Time |
15:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2003-05-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-05-06 |
Time |
12:59 |
Rev Time |
1.25 |
| Received By |
dpalmer |
Date |
2003-05-06 |
Time |
11:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-08-11 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-08-11 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-08-11 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2003-08-11 00:00:00 | REVISION DATED 8-01-03 NAM |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2003-05-27 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-05-27 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-05-27 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2003-05-27 00:00:00 | **************PROVISO******************* | | | SEPARATE PLAN AND PERMIT APPLICATION | | | WILL BE REQUIRED FOR FIRE ALARM SYSTEM | | | REMODEL. | | | | | | NATE MCCRAY, CAPTAIN | | | 805-6722 OR 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-08-01 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-08-01 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2003-08-01 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2003-08-01 00:00:00 | TO COMM BD. # 51 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-06-04 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-04 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-04 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2003-06-04 00:00:00 | COMM BOARD #8 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-04-28 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-28 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-28 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2003-04-28 00:00:00 | COMM BOARD #4 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2003-06-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-06-10 |
Time |
12:18 |
Rev Time |
0.15 |
| Received By |
pkrauss |
Date |
2003-06-10 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2003-06-10 00:00:00 | PLANS APPROVED 5-10-03 PHK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-05-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-05-30 |
Time |
09:23 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2003-05-30 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2003-05-30 00:00:00 | PER CONVERSATION W/GORDEN SCOTT (KAMM | | | ENG) - TRANSFER GRILLE IS FOR ADDITIONAL | | | AIR MAKE UP FOR THE AMOUNT OF EXHAUST | | | AIR.GRILLE TO HAVE DAMPER, SUBMITTAL | | | LTR TO FOLLOW. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2003-05-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-05-10 |
Time |
10:44 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-05-10 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2003-05-10 00:00:00 | PROVISO: | | | | | | PLANS SHEET M2.1, INDICATE A TRANSFER | | | GRILLE FROM THE MENS BATHROOM TO THE | | | OPEN OFFICE SPACE AS PER 2001 FBC(M) | | | 403.2.2 AIR TRANSFER SHALL BE MAKE-UP | | | AIR FOR THE EXHAUST AIR.AIR FROM THE | | | BATHROOM SHALL NOT BE RECIRCULATED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-06-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-06-21 |
Time |
18:29 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2003-06-21 |
Time |
18:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-05-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-05-23 |
Time |
15:08 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-05-23 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2003-05-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT P0.1 WATER HEATER DETAIL, THERMAL | | | EXPANSION CONTROL IS REQUIRED. PLEASE | | | PROVIDE ON DETAIL. SECTION 607.3.2 | | | 2) SHT P5.1 WATER RISER DIAGRAM. WATER | | | HAMMER ARRESTORS REQUIRED BY SECTION | | | 604.9 SHALL BE LOCATED NEAR THE FIXTURE, | | | IN AN "EFFECTIVE RANGE" NOT AT THE TOP | | | OF THE DROP IN THE CEILING. PDI-WH 201 | | | AND MANUF. INSTALLATION INSTRUCTIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|