Plan Review Details - Permit 03042048
Plan Review Stops For Permit 03042048
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-09 Cont ID  
Sent By hpiskura Date 2003-07-09 Time 07:15 Rev Time 0.00
Received By hpiskura Date 2003-07-08 Time 16:29 Sent To  
Notes
2003-07-09 00:00:00PLANS DATED 6/10/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-05-29 Cont ID  
Sent By hpiskura Date 2003-05-29 Time 08:10 Rev Time 0.00
Received By hpiskura Date 2003-05-29 Time 08:10 Sent To  
Notes
2003-05-29 00:00:00PLAN REVIEW NOT A PERMIT APPLICATION.
  
 AT THE TIME OF PERMIT APPLICATION
 INCLUDE A BRIEF DESCRIPTION OF THE
 QUANTITY, NATURE, CHARACTERISTICS,
 PACKAGING AND METHODS OF THE MATERIALS
 TO BE STORED.SEE FBC 104.2.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-08-15 Cont ID  
Sent By btrobaug Date 2003-08-15 Time 10:42 Rev Time 0.50
Received By btrobaug Date 2003-08-15 Time 10:40 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-07-23 Cont ID  
Sent By dpalmer Date 2003-07-23 Time 10:04 Rev Time 0.33
Received By dpalmer Date 2003-07-23 Time 10:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-01 Cont ID  
Sent By dpalmer Date 2003-07-01 Time 12:47 Rev Time 0.50
Received By dpalmer Date 2003-07-01 Time 12:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-06 Cont ID  
Sent By dpalmer Date 2003-05-06 Time 17:18 Rev Time 0.50
Received By dpalmer Date 2003-05-06 Time 17:18 Sent To  
Notes
2003-05-06 00:00:00********** UNSAT *********
  
 1)NOTE: PLEASE CLARIFY/ SHOW ALL CONTIN-
 -UOUS LOADS AT 125%. 230-42/215-3
  
 PLANS ARE ONLY SUBMITTED FOR PLAN REVIEW
 PLEASE ALSO SEE ANY COMMENTS FROM OTHER
 REVIEWS THAT MAY AFFECT ELECTRICAL PLANS
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE TAKE OUT OLD SHEET AND
 INSERT NEW SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2003-05-29 Cont ID  
Sent By hpiskura Date 2003-05-29 Time 08:13 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-07-23 Cont ID  
Sent By lmartine Date 2003-07-23 Time 13:51 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2003-07-23 00:00:00 
 SEE PLAN FOR APPROVAL BY NATE MCCRAY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-07-09 Cont ID  
Sent By nmccray Date 2003-07-09 Time 13:41 Rev Time 0.00
Received By nmccray Date 2003-07-09 Time 13:41 Sent To  
Notes
2003-07-09 00:00:001) WILL THERE BE ANY CUTTING OR WELDING
 OPERATIONS INSIDE THE WAREHOUSE. IF SO
 SHOW LOCATION OF OPERATION.
  
 2) PLEASE INDICATE THE LOCATION WHERE
 THE FREON AND OXEACETALINE GAS CYLINDERS
 ARE GOING TO STORED.
  
 3) "NO SMOKING" SIGNS MUST BE POSTED.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-05-27 Cont ID  
Sent By nmccray Date 2003-05-27 Time 14:03 Rev Time 0.00
Received By nmccray Date 2003-05-27 Time 14:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-18 Cont ID  
Sent By shernand Date 2003-07-18 Time 14:49 Rev Time 0.00
Received By shernand Date 2003-07-18 Time 14:49 Sent To  
Notes
2003-07-18 00:00:00COMM BOARD #23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-16 Cont ID  
Sent By shernand Date 2003-06-16 Time 14:23 Rev Time 0.00
Received By shernand Date 2003-06-16 Time 14:23 Sent To  
Notes
2003-06-16 00:00:00COMM BOARD #56

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-28 Cont ID  
Sent By shernand Date 2003-04-28 Time 14:00 Rev Time 0.00
Received By shernand Date 2003-04-28 Time 14:00 Sent To  
Notes
2003-04-28 00:00:00COMM BOARD #44

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-08-18 Cont ID  
Sent By pkrauss Date 2003-08-18 Time 06:29 Rev Time 0.35
Received By pkrauss Date 2003-08-18 Time 06:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-07-23 Cont ID  
Sent By btrobaug Date 2003-08-15 Time 10:42 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2003-07-23 00:00:00 
 SEE APPROVAL ON PLANS BY PATTY.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2003-07-22 Cont ID  
Sent By pkrauss Date 2003-07-22 Time 08:04 Rev Time 1.22
Received By pkrauss Date   Time   Sent To  
Notes
2003-07-22 00:00:00 
  
 1.PLEASE SUBMIT CUT SHEETS ON THE
 SELF CONTAINED OSHA APPROVED EYE WASH
 STATION.
  
 2.COMMENTS FROM CAPT N. MCCRAY (FIRE
 DEPT) WERE NOT ADDRESSED.
 A) WILL ANY CUTTING OR WELDING BE
 DONE AT THIS FACILITY.
 B) INDICATE LOCATION OF FREON &
 OXEACETALINE GAS CYLINDERS ARE
 STORED.
 C) "NO SMOKING" SIGNS MUST BE POSTED.
  
 3.COMMENTS FROM P. KRAUSS THAT WERE
 NOT ADDRESSED.
 A) INDICATE HOW FREON IS TO BE STORED
 B) INDICATE ANY LEAK DETECTORS THAT
 MAY BE INSTALLED.
 C) PROVIDE CUT SHEETS FOR OSHA
 APPROVED WIRE CASES ON JOBSITE
 FOR INSPECTION.
  
 4.WILL THE EXHAUST FANS RUN
 CONTINUOUSLY.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-07-07 Cont ID  
Sent By pkrauss Date 2003-07-07 Time 08:25 Rev Time 0.50
Received By pkrauss Date 2003-07-07 Time 08:25 Sent To  
Notes
2003-07-07 00:00:00DENIED:
 PLANS FOR THE OFFICE AREA ARE APPROVED.
 PLEASE PROVIDE ADDITIONAL INFORMATION
 AS REQUESTED BY HAROLD PISKURA ON HIS
 REVIEW DATED 5/29/03.
  
 1.INDICATE HOW FREON & OXEACETALINE
 GAS ARE TO BE STORED.
  
 2.PROVIDE SEPARATION BETWEEN GAS &
 FREON.
  
 3.PROVIDE HOW MANY POUNDS OF EACH
 ITEM TO BE STORED.INDICATING THE
 NUMBER OF CYLINDERS DOES NOT GIVE AN
 ACCURATE AMOUNT IN POUNDS.
  
 4.INDICATE ANY LEAK DETECTORS THAT
 MAY BE REQURIED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-05-10 Cont ID  
Sent By pkrauss Date 2003-05-10 Time 13:21 Rev Time 0.40
Received By pkrauss Date 2003-05-10 Time 13:21 Sent To  
Notes
2003-05-10 00:00:00DENIED:
  
 PROVIDE INFORMATION ON THE CONDENSATE.
 INDICATE TERMINATION (STORM DRAIN OR
 APPROVED DRY WELL).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-07-23 Cont ID  
Sent By kstevens Date 2003-07-23 Time 17:20 Rev Time 2.50
Received By kstevens Date 2003-07-23 Time 17:19 Sent To  
Notes
2003-07-23 00:00:00PASSED/PROVISO
  
 EYEWASH TO BE INSTALLED PER MANUFACTUR'S
 INSTALLATION INSTRUCTIONS

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-07-02 Cont ID  
Sent By kstevens Date 2003-07-02 Time 10:57 Rev Time 1.00
Received By kstevens Date 2003-07-01 Time 14:36 Sent To  
Notes
2003-07-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS, CHAPTER
 1, ADMIN. CODE
  
 1) THERE ARE NO PROVISIONS IN THE FBC-
 2001 PLUMBING CODE FOR REDUCTION OF
 FACILITIES STRICTLY ON THE BASIS OF THE
 NUMBER OF EMPLOYEES. 2 W/C'S AND 2 LAVS
 SHALL BE REQUIRED PER TABLE 403.1.
 2) SUBMIT THE MSDS SHEETS FOR THE R-22
 FREON AND THE R410A FREON TO DETERMINE
 IF AN EMERGENCY EYE WASH AND SHOWER WILL
 BE REQUIRED. SEC 411.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-23 Cont ID  
Sent By kstevens Date 2003-05-23 Time 14:44 Rev Time 1.50
Received By kstevens Date 2003-05-23 Time 14:44 Sent To  
Notes
2003-05-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) PER TABLE 403.1, 2 W/C'S AND 2 LAVS
 ARE REQUIRED. 1 EACH W/C FOR OFFICE AND
 FOR WAREHOUSE.
 2) PLEASE INDICATE THE NATURE OF THE
 MATERIAL THAT WILL BE WAREHOUSED. MSDS
 SHEETS MAY INDICATE THAT AN EYEWASH -
 EMERGENCY SHOWER MIGHT BE REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status N Date 2003-05-29 Cont ID  
Sent By hpiskura Date 2003-05-29 Time 08:13 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***