Plan Review Details - Permit 03041995
Plan Review Stops For Permit 03041995
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-08-05 Cont ID  
Sent By jgomez Date 2003-08-05 Time 15:47 Rev Time 1.00
Received By jgomez Date 2003-08-05 Time 15:47 Sent To PC
Notes
2003-08-05 00:00:00SUBMITTAL CHECKLIST:
 1-STORM SHUTTERS: DRAWINGS ARE FOR ONE
 PERMIT ONLY AS REQUIRED BY THE
 ENGINEER. NEED TO PROVIDE ORIGINAL
 SIGNED AND SEALED DRAWINGS.
 2-ENTRY DOOR IS NOT MISSILE IMPACT
 RATED. HOW IS THE GLASS GOING TO BE
 PROTECTED FROM MISSILE IMPACT?.
 3-NEED SITE SPECIFIC ENGINEERING FOR
 WINDOW AT DINING AREA. PRODUCT
 APPROVAL SUBMITTED DOESN'T COVER THIS
 SPECIAL WINDOW. SEE DRAWINGS.
 4-ARCHITECT TO SIGN, SEAL AND DATE
 SITE SPECIFIC FORM FOR WINDOW AT
 BREAKFAST AREA. HE HAS THE REVIEW
 STAMP, NOT THE SEAL. ALSO, SITE
 SPECIFIC FORM DOESN'T HAVE THE ADDRESS
 OF THE JOB REQUIRED FOR SITE SPECIFIC
 INFORMATION.
 5-GARAGE DOOR PRODUCT APPROVAL IS NOW
 MISSING THE APPROVED DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-06-20 Cont ID  
Sent By alange Date 2003-07-30 Time 13:54 Rev Time 4.00
Received By jgomez Date 2003-06-20 Time 16:13 Sent To PC
Notes
2003-06-20 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-GARAGE DOOR STRUCTURAL BUCK DETAIL:
 PROVIDE COMPLETE SPECIFICATIONS FOR
 ANCHOR EMBEDMENT AND WASHER. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 2-PROVIDE ATTIC ACCESS AT FAMILY ROOM
 WING AREA. SEC. 2309.6 FBC 2001.
 3-SHEET A-3: A)REVISE HANDRAIL HEIGHT.
 SEE SEC. 1007.5.1 FBC 2001.
 B)PROVIDE COMPLETE DRAWINGS FOR CIRCULAR
 STAIR SHOWING COMPLIANCE WITH THE
 DIMENSION REQUIREMENTS OF SECTION
 1007.8.3 FBC 2001.
 C)SHOW HOW IS THE WATER RUNNING OFF THE
 FLAT ROOF AREA. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 4-AS PER BUILDING OFFICIAL: NEED TO
 PROVIDE STORM PANELS ORIGINAL DRAWINGS
 SINCE ENGINEER LIMITED DRAWINGS TO BE
 FOR ONE PERMIT ONLY.
 5-PROVIDE PRODUCT APPROVAL FOR:
 A)COMPLETE FLAT ROOF SYSTEM REPORT WITH
 THE SPECIFIC INSTALLATION SYSTEM TO BE
 USED IN THIS PROJECT.
 B)WINDOW AT DINING ROOM AREA.
 C)ENTRY DOOR WITH SIDELITE ASSEMBLY AS
 SHOWN ON PLANS. BROWARD COUNTY INFO.
 IS NOT GOOD. NEED DADE COUNTY, SBCCI
 OR SITE SPECIFIC COMPLETE ENGINEERING
 WITH ENGINEER'S AND ARCHITECT SEAL.
 D)BREAKFAST WINDOW SITE SPECIFIC INFO.
 NEED ARCHITECT'S SEAL, SIGNATURE AND
 DATE ON THE FORM AND THE SPECIFIC
 ADDRESS FOR THIS JOB.
 E)PROVIDE COMPLETE PRODUCT APPROVAL FOR
 GARAGE DOORS. MISSING SBCCI REPORT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-02 Cont ID  
Sent By shernand Date 2003-06-13 Time 16:33 Rev Time 4.00
Received By jgomez Date 2003-05-30 Time 18:53 Sent To  
Notes
2003-05-30 00:00:00BUILDING REVIEW CHECKLIST:
 1-PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND RECEIPT.
 2-LEFT ELEVATION SHOWS THE PRIVACY WALL,
 BUT IT NOT SHOWN ON FOUNDATION PLAN.
 3-GLASS BLOCK AT BATHROOM AREAS TO BE
 SAFETY GLASS IF FACE THICKNESS IS LESS
 THAN 0.25". SEC. 2405.2 FBC 2001.
 4-PROVIDE COMPLETE DETAILS AND FASTENER
 SPECIFICATIONS FOR INSTALLATION OF
 HANGING AIR HANDLING UNIT.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-PROVIDE DETAIL FOR GARAGE STRUCTURAL
 BUCK DETAIL. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 6-UPDATE TRUSS ANCHOR SCHEDULE, DETAIL
 3/A14, 2/A14 AND ALL DETAILS THAT NEED
 TO REVISE THE LOADS TO COMPLY W/ SEC.
 1609.4.3 FBC 2001, WHICH DOES NOT
 ALLOW 33% ALLOWABLE STRESS INCREASE
 TO BE USED. SEE USP 2003 CATALOGUE FOR
 REVISED LOADS.
 7-REVISE DETAIL 4/14. NEED 2X BUCK TO
 SUPPORT WINDOW. SEE PRODUCT APPROVAL.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-ENERGY CALCULATIONS: PROVIDE COMPLETE
 INFORMATION ON TOP OF FORM INCLUDING
 CORRECT OWNER.
 9-NEED TO UPDATE WORKERS COMPENSATION.
 10-DESIGN CRITERIA SPECIFIED ON SHEET
 C-1 CALLS FOR EXPOSURE "D", BUT DESIGN
 PRESSURES SHOWN ON ELEVATIONS DON,T
 MATCH. REVISE AS REQUIRED.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 11-PROVIDE ATTIC ACCESS AT FAMILY ROOM
 WING, MASTER BATH AREA AND AT MASTER
 BEDROOM AREA. (ONE SHON ON MASTER BED-
 ROOM CLOSET DOESN'T WORK BECAUSE THE
 2ND FLOOR IS ABOVE THIS CLOSET). SEC.
 2309.6 FBC 2001.
 12-SPECIFY SAFETY GLASS AT LIVING ROOM
 AREA. SECTION 2405.2 FBC 2001.
 13-SHEET A-3: REVISE HANDRAIL HEIGHT.SEE
 SEC. 1007.5.1 FBC 2001. **HANDRAIL AND
 GUARDRAIL ARE NOT THE SAME.
 14-PROVIDE COMPLETE 2 STORY WALL SECTION
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 15-PROVIDE SPECS FOR FIREBLOCKING AT ALL
 CONCEALED SPACES. INCLUDING AT STAIRS.
 SEE SEC. 2305 FBC 2001.
 16-STUCCO ON FRAMED WALL TO BE 7/8" MIN.
 SEE ASTM C-926.
 17-WHERE ARE DETAILS 13/A14 AND 14/A14
 SHOWN ON FRAMING PLANS.
 18-REVISE MEAN ROOF HEIGHT. MEAN ROOF HT
 IS TAKEN FROM GRADE, NOT FROM FINISH
 FLOOR. SEC. 104.2.1.2 CITY AMENDMENTS.
 19-REVISE DIAPHRAGM SCHEDULE. NEED 8D
 RING SHANK NAILS WHEN MEAN ROOF HEIGHT
 IS HIGHER THAN 25'. SEE SEC. 2306 OF
 CITY AMENDMENTS TO FBC 2001.
 20-PROVIDE COMPLETE DETAIL/SPECS FOR
 BOLLARD FOR PROTECTION OF EQUIPMENT IN
 GARAGE. SEC. 104.2.1.2 CITY AMENDMENTS
 21-FLAT ROOF ABOVE GARAGE. SPECIFY HOW
 IS WATER RUNNING OFF. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 22-PROVIDE COMPLETE FRAMING DETAILS FOR
 CURVED STAIRS. SEE SEC. 1007.8.3 FBC
 FOR REQUIRED MIN. DIMENSIONS.
 23-PROVIDE COMPLETE FRAMING PLAN & SPECS
 AT SECOND FLOOR AREA BY THE STAIRS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 24-HOW ARE THE 2X STUDS ON DETAIL 8/A14
 CONNECTED AT THE BASE?. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 25-PROVIDE PRODUCT APPROVAL FOR: A)FLAT
 ROOF SYSTEM. B)WINDOW AT LIVING ROOM
 AREA. C)HORIZONTAL SLIDER WINDOW.
 D)ENTRY DOOR WITH SIDELITE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 E)SITE SPECIFIC ENGINEERING FOR WINDOW
 AT BREAKFAST AREA: DESIGN PRESSURES
 DON'T MATCH THOSE SHOWN ON PLANS.
 ARCHITECT TO SIGN & SEAL SITE SPECIFIC
 FORM AS REQ'D BY THE BLDG OFFICIAL.
 FORM NEEDS TO HAVE THE SITE SPECIFIC
 ADDRESS.
 PROVIDE THE PRODUCT APPROVAL FOR THE
 4500 SERIES WINDOWS.
 FORM AND DRAWINGS DON'T MATCH. EG: SEE
 GLASS THICKNESS.
 26-SEE REVIEWED SET FOR ADDITIONAL
 COMMENTS AND PLEASE RETURN REVIEWED
 SET TO EXPEDITE REVIEW PROCESS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-10 Cont ID  
Sent By btrobaug Date 2003-11-10 Time 12:02 Rev Time 0.50
Received By btrobaug Date 2003-11-10 Time 11:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-13 Cont ID  
Sent By csiegber Date 2003-11-05 Time 14:14 Rev Time 0.50
Received By btrobaug Date 2003-05-13 Time 14:17 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-11-05 Cont ID  
Sent By csiegber Date 2003-11-05 Time 14:14 Rev Time 0.00
Received By csiegber Date 2003-11-05 Time 14:14 Sent To E
Notes
2003-11-05 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 13:54 Rev Time 0.00
Received By alange Date 2003-07-30 Time 13:53 Sent To B
Notes
2003-07-30 00:00:00TO JG DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-13 Cont ID  
Sent By shernand Date 2003-06-13 Time 16:33 Rev Time 0.00
Received By shernand Date 2003-06-13 Time 16:33 Sent To B
Notes
2003-06-13 00:00:00JGOMEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-25 Cont ID  
Sent By shernand Date 2003-04-25 Time 09:13 Rev Time 0.00
Received By shernand Date 2003-04-25 Time 09:13 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-22 Cont ID  
Sent By kstevens Date 2003-05-17 Time 06:12 Rev Time 0.25
Received By pkrauss Date 2003-05-22 Time 08:51 Sent To B
Notes
2003-05-22 00:00:00PROVISO:MECHANICAL PERMIT 03042005
  
 PROVIDE FRESH AIR CALCULATIONS AT ROUGH
 INSPECTION:
 NATURAL - 2001 FBC(M) 402.2
 MECHANICAL - 2001 FBC(M) TABLE 403.3
  
 PLEASE NOTE, AHU SHALL HAVE A MINIMUM OF
 4" CLEARANCE AS PER 2001 FBC(M) 603.1.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-05-17 Cont ID  
Sent By btrobaug Date 2003-05-13 Time 15:02 Rev Time 0.25
Received By kstevens Date 2003-05-17 Time 06:12 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-25 Time 09:13 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***