| 2003-05-30 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-PAY IMPACT FEES. BRING BACK STAMPED |
| | DRAWINGS AND RECEIPT. |
| | 2-LEFT ELEVATION SHOWS THE PRIVACY WALL, |
| | BUT IT NOT SHOWN ON FOUNDATION PLAN. |
| | 3-GLASS BLOCK AT BATHROOM AREAS TO BE |
| | SAFETY GLASS IF FACE THICKNESS IS LESS |
| | THAN 0.25". SEC. 2405.2 FBC 2001. |
| | 4-PROVIDE COMPLETE DETAILS AND FASTENER |
| | SPECIFICATIONS FOR INSTALLATION OF |
| | HANGING AIR HANDLING UNIT.SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 5-PROVIDE DETAIL FOR GARAGE STRUCTURAL |
| | BUCK DETAIL. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 6-UPDATE TRUSS ANCHOR SCHEDULE, DETAIL |
| | 3/A14, 2/A14 AND ALL DETAILS THAT NEED |
| | TO REVISE THE LOADS TO COMPLY W/ SEC. |
| | 1609.4.3 FBC 2001, WHICH DOES NOT |
| | ALLOW 33% ALLOWABLE STRESS INCREASE |
| | TO BE USED. SEE USP 2003 CATALOGUE FOR |
| | REVISED LOADS. |
| | 7-REVISE DETAIL 4/14. NEED 2X BUCK TO |
| | SUPPORT WINDOW. SEE PRODUCT APPROVAL. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 8-ENERGY CALCULATIONS: PROVIDE COMPLETE |
| | INFORMATION ON TOP OF FORM INCLUDING |
| | CORRECT OWNER. |
| | 9-NEED TO UPDATE WORKERS COMPENSATION. |
| | 10-DESIGN CRITERIA SPECIFIED ON SHEET |
| | C-1 CALLS FOR EXPOSURE "D", BUT DESIGN |
| | PRESSURES SHOWN ON ELEVATIONS DON,T |
| | MATCH. REVISE AS REQUIRED.SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 11-PROVIDE ATTIC ACCESS AT FAMILY ROOM |
| | WING, MASTER BATH AREA AND AT MASTER |
| | BEDROOM AREA. (ONE SHON ON MASTER BED- |
| | ROOM CLOSET DOESN'T WORK BECAUSE THE |
| | 2ND FLOOR IS ABOVE THIS CLOSET). SEC. |
| | 2309.6 FBC 2001. |
| | 12-SPECIFY SAFETY GLASS AT LIVING ROOM |
| | AREA. SECTION 2405.2 FBC 2001. |
| | 13-SHEET A-3: REVISE HANDRAIL HEIGHT.SEE |
| | SEC. 1007.5.1 FBC 2001. **HANDRAIL AND |
| | GUARDRAIL ARE NOT THE SAME. |
| | 14-PROVIDE COMPLETE 2 STORY WALL SECTION |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 15-PROVIDE SPECS FOR FIREBLOCKING AT ALL |
| | CONCEALED SPACES. INCLUDING AT STAIRS. |
| | SEE SEC. 2305 FBC 2001. |
| | 16-STUCCO ON FRAMED WALL TO BE 7/8" MIN. |
| | SEE ASTM C-926. |
| | 17-WHERE ARE DETAILS 13/A14 AND 14/A14 |
| | SHOWN ON FRAMING PLANS. |
| | 18-REVISE MEAN ROOF HEIGHT. MEAN ROOF HT |
| | IS TAKEN FROM GRADE, NOT FROM FINISH |
| | FLOOR. SEC. 104.2.1.2 CITY AMENDMENTS. |
| | 19-REVISE DIAPHRAGM SCHEDULE. NEED 8D |
| | RING SHANK NAILS WHEN MEAN ROOF HEIGHT |
| | IS HIGHER THAN 25'. SEE SEC. 2306 OF |
| | CITY AMENDMENTS TO FBC 2001. |
| | 20-PROVIDE COMPLETE DETAIL/SPECS FOR |
| | BOLLARD FOR PROTECTION OF EQUIPMENT IN |
| | GARAGE. SEC. 104.2.1.2 CITY AMENDMENTS |
| | 21-FLAT ROOF ABOVE GARAGE. SPECIFY HOW |
| | IS WATER RUNNING OFF. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 22-PROVIDE COMPLETE FRAMING DETAILS FOR |
| | CURVED STAIRS. SEE SEC. 1007.8.3 FBC |
| | FOR REQUIRED MIN. DIMENSIONS. |
| | 23-PROVIDE COMPLETE FRAMING PLAN & SPECS |
| | AT SECOND FLOOR AREA BY THE STAIRS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 24-HOW ARE THE 2X STUDS ON DETAIL 8/A14 |
| | CONNECTED AT THE BASE?. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 25-PROVIDE PRODUCT APPROVAL FOR: A)FLAT |
| | ROOF SYSTEM. B)WINDOW AT LIVING ROOM |
| | AREA. C)HORIZONTAL SLIDER WINDOW. |
| | D)ENTRY DOOR WITH SIDELITE SINGLE |
| | ASSEMBLY AS SHOWN ON PLANS. |
| | E)SITE SPECIFIC ENGINEERING FOR WINDOW |
| | AT BREAKFAST AREA: DESIGN PRESSURES |
| | DON'T MATCH THOSE SHOWN ON PLANS. |
| | ARCHITECT TO SIGN & SEAL SITE SPECIFIC |
| | FORM AS REQ'D BY THE BLDG OFFICIAL. |
| | FORM NEEDS TO HAVE THE SITE SPECIFIC |
| | ADDRESS. |
| | PROVIDE THE PRODUCT APPROVAL FOR THE |
| | 4500 SERIES WINDOWS. |
| | FORM AND DRAWINGS DON'T MATCH. EG: SEE |
| | GLASS THICKNESS. |
| | 26-SEE REVIEWED SET FOR ADDITIONAL |
| | COMMENTS AND PLEASE RETURN REVIEWED |
| | SET TO EXPEDITE REVIEW PROCESS. |