Plan Review Details - Permit 03041993
Plan Review Stops For Permit 03041993
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-08-05 Cont ID  
Sent By jgomez Date 2003-08-05 Time 09:34 Rev Time 1.00
Received By jgomez Date 2003-08-05 Time 09:34 Sent To M
Notes
2003-08-05 00:00:00SUBMITTAL CHECKLIST:
 1-EGRESS WINDOW AT GUEST ROOM: ARCHITECT
 SHOWS CASEMENT WINDOWS. IF INSTALLING
 SINGLE HUNG WINDOWS, THEN, NEED TO
 REVISE PLANS (REVISION FEES WILL BE
 CHARGED).
 **NOTE: WINDOWS WERE ORIGINALLY CHANGED
 FROM SINGLE HUNG TO CASEMENT TO
 COMPLY WITH TABLE 600 FBC 2001.
 IN SUMMARY, WINDOWS AT THIS LOCATION
 NEED TO COMPLY WITH TABLE 600 AND THE
 EGRESS REQUIREMENTS.
 **IF USING CASEMENT WINDOWS, THEN, NEED
 TO PROVIDE THE PRODUCT APPROVAL.
 2-OWNER TO SIGN AND DATE THE ENERGY
 CALCULATIONS AT BOTTOM OF FORM.
 3-STORM SHUTTERS NEED TO HAVE ORIGINAL
 DRAWINGS WITH ENGINEER'S ORIGINAL
 SEAL AND SIGNATURE. SUBMITTED DRAWINGS
 ARE LIMITED TO ONE PERMIT ONLY. THERE
 IS NOT MASTER FOR STORM SHUTTERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-06-23 Cont ID  
Sent By alange Date 2003-07-30 Time 13:56 Rev Time 3.50
Received By jgomez Date 2003-06-23 Time 13:13 Sent To P
Notes
2003-06-23 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-EGRESS WINDOW AT GUEST SUITE TO HAVE
 20" MINIMUM CLEAR WIDTH OPENING AND
 5.0 S.F. MINIMUM TOTAL CLEAR OPENING
 AS REQUIRED BY SEC. 1005.4 FBC 2001.
 2-PROVIDE PRODUCT APPROVAL FOR CASEMENT
 WINDOWS.
 3-AS REQUIRED BY THE BUILDING OFFICIAL,
 NEED AMMENDED DECLARATION OF COVENANTS
 RESTRICTIONS AND EASEMENTS SPECIFYING
 EGRESS EASEMENT WHEN HAVING BEDROOMS
 ON THE ZERO LOT LINE SIDE.
 4-REVISE ENERGY CALCULATIONS. A/C AREA
 DOESN'T MATCH A/C AREA SHOWN ON
 ARCHITECT'S PLANS. RE-SUBMIT.
 5-AS REQUIRED BY THE BUILDING OFFICIAL,
 PROVIDE ORIGINAL ENGINEERED DRAWINGS
 FOR STORM PANELS, SINCE THE ENGINEER
 IS LIMITING HIS DRAWINGS TO BE USED
 FOR ONE PERMIT ONLY. SEE STAMP ON
 ENGINEERED DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-29 Cont ID  
Sent By shernand Date 2003-06-13 Time 16:34 Rev Time 4.50
Received By jgomez Date 2003-05-29 Time 13:23 Sent To  
Notes
2003-05-29 00:00:00BUILDING REVIEW CHECKLIST:
 1-PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND RECEIPT.
 2-RIGHT SIDE ELEVATION EXCEEDS THE MAX.
 % OF OPENINGS ALLOWED BY TABLE 600 FBC
 2001. REVISE AS REQUIRED.
 3-GUEST SUITE EGRESS WINDOW DOESN'T HAVE
 THE 24" CLEAR HEIGHT REQUIRED BY SEC.
 1005.4 FBC 2001. PRODUCT APPROVAL
 SUBMITTED IS FOR PGT WINDOWS. PGT DOES
 NOT HAVE A 24+5 SIZE WINDOW. SEE
 PRODUCT APPROVAL. IS THIS A CUSTOM
 MADE WINDOW? IF SO, THEN, PROVIDE THE
 MANUFACTURER CUT SHEETS.
 4-NEED RECORDED DEED SHOWING AT LEAST 3'
 EASEMENT ON NEIGHBOR'S PROPERTY TO
 ALLOW FOR EGRESS, WHEN BEDROOMS ARE
 LOCATED ON THE ZERO LOT LINE SIDE.
 5-SHEET C-1: REVISE FOUNDATION NOTES.
 MINIMUM VAPOR BARRIER TO BE 6 MIL, NOT
 4 MIL. SEC. 1909.2 FBC 2001.
 6-FOOTING FOR PRIVACY WALL AT ZERO LOT
 LINE WALL IS ENCROACHING INTO OTHERS
 PROPERTY. REVISE AS REQUIRED.
 7-GLASS BLOCK AT BATHROOM AREAS TO BE
 SAFETY GLASS IF FACE THICKNESS IS LESS
 THAN 0.25". SEC. 2405.2 FBC 2001.
 8-PROVIDE COMPLETE DETAIL AND FASTENER
 SPECIFICATIONS FOR INSTALLATION OF
 HANGING AIR HANDLING UNIT.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 9-PROVIDE COMPLETE SPECS FOR GARAGE DOOR
 STRUCTURAL BUCK DETAIL. NEED COMPLETE
 SIZE OF ANCHOR AND WASHER.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 10-UPDATE TRUSS ANCHOR SCHEDULE, DETAIL
 3/A5 AND ALL DETAILS THAT NEED TO
 REVISE THE LOADS TO COMPLY W/ SECTION
 1609.4.3 FBC 2001, WHICH DOES NOT
 ALLOW33% ALLOWABLE STRESS INCREASE
 TO BE USED.SEE USP 2003 CATALOGUE
 WHICH HAS THE REVISED VALUES.
 11-REVISE DETAIL 2/A5: NEED 2X BUCK TO
 SUPPORT WINDOW. SEE PRODUCT APPROVAL.
 SEC. 104.2.1.2. CITY AMENDMENTS TO FBC
 12-ENERGY CALCULATIONS: A)PROVIDE
 COMPLETE AND CORRECT INFORMATION ON
 TOP OF FORM. EG: ADDRESS AND OWNER
 INFORMATION.
 B)CONDITIONED FLOOR AREA DOESN'T MATCH
 AREA SHOWN ON ARCHITECT'S DRAWINGS.
 13-STORM SHUTTERS: REVISE MINIMUM AND
 MAXIMUM PANEL SPAN ON INSTALLATION
 SCHEDULE. SEE ENGINEERED DRAWINGS AND
 DESIGN PRESSURES CALCULATED ON PLANS.
 14-SEE ADDITIONAL COMMENTS ON REVIEWED
 SET OF PLANS. PLEASE RETURN REVIEWED
 SET AFTER CORRECTIONS ARE DONE TO THE
 ORIGINAL CAD DRAWINGS TO EXPEDITE THE
 REVIEW PROCESS.
 15-NEED TO UPDATE WORKER'S COMPENSATION
 INSURANCE.
 16-SEE COMMENTS BY PLUMBING.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-03-23 Cont ID  
Sent By btrobaug Date 2004-03-23 Time 17:14 Rev Time 0.50
Received By btrobaug Date 2004-03-23 Time 17:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-13 Cont ID  
Sent By csiegber Date 2004-03-23 Time 15:26 Rev Time 0.50
Received By btrobaug Date 2003-05-13 Time 15:13 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-03-23 Cont ID  
Sent By csiegber Date 2004-03-23 Time 15:26 Rev Time 0.00
Received By csiegber Date 2004-03-23 Time 15:26 Sent To E
Notes
2004-03-23 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 13:56 Rev Time 0.00
Received By alange Date 2003-07-30 Time 13:56 Sent To B
Notes
2003-07-30 00:00:00TO JG DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-13 Cont ID  
Sent By shernand Date 2003-06-13 Time 16:34 Rev Time 0.00
Received By shernand Date 2003-06-13 Time 16:34 Sent To B
Notes
2003-06-13 00:00:00JGOMEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-25 Cont ID  
Sent By shernand Date 2003-04-25 Time 09:22 Rev Time 0.00
Received By shernand Date 2003-04-25 Time 09:21 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-08-09 Cont ID  
Sent By pkrauss Date 2003-08-09 Time 08:57 Rev Time 0.25
Received By pkrauss Date 2003-08-09 Time 08:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-22 Cont ID  
Sent By jgomez Date 2003-08-05 Time 09:34 Rev Time 0.25
Received By pkrauss Date 2003-05-22 Time 09:21 Sent To B
Notes
2003-05-22 00:00:00PROVISO:MECHANICAL PERMIT 03042018
  
 1.PROVIDE FRESH AIR CALCULATIONS AT
 ROUGH INSPECTION:
 NATURAL - 2001 FBC(M) 402.2 OR
 MECHANICAL - 2001 FBC(M) TABLE 403.3
  
 2.SHOULD GAS DRYER BE INSTALLED,
 PROVIDE INFORMATION ON LAUNDRY ROOM.
 IDENTIFY CONFINED OR UNCONFINED FOR
 COMBUSTION AIR. 2001 FBC(M) 702 OR 703.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-06-23 Cont ID  
Sent By kstevens Date 2003-06-23 Time 17:19 Rev Time 0.50
Received By kstevens Date 2003-06-23 Time 17:19 Sent To  
Notes
2003-06-23 00:00:00PASSED/PROVISO
  
  
 LAV MISSING ON SANT. RISER DIAGRAM FOR
 GUEST BATH. - REVISION REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-17 Cont ID  
Sent By jgomez Date 2003-06-23 Time 13:14 Rev Time 0.33
Received By kstevens Date 2003-05-17 Time 06:52 Sent To M
Notes
2003-05-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN - GUEST BATH HAS ONE LAV
 ON FLOOR PLAN AND TWO ON THE RISER DIAG.
 POWDER ROOM IS NOT SHOWN ON RISER DIAG.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-25 Time 09:22 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***