| 2003-05-29 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-PAY IMPACT FEES. BRING BACK STAMPED |
| | DRAWINGS AND RECEIPT. |
| | 2-RIGHT SIDE ELEVATION EXCEEDS THE MAX. |
| | % OF OPENINGS ALLOWED BY TABLE 600 FBC |
| | 2001. REVISE AS REQUIRED. |
| | 3-GUEST SUITE EGRESS WINDOW DOESN'T HAVE |
| | THE 24" CLEAR HEIGHT REQUIRED BY SEC. |
| | 1005.4 FBC 2001. PRODUCT APPROVAL |
| | SUBMITTED IS FOR PGT WINDOWS. PGT DOES |
| | NOT HAVE A 24+5 SIZE WINDOW. SEE |
| | PRODUCT APPROVAL. IS THIS A CUSTOM |
| | MADE WINDOW? IF SO, THEN, PROVIDE THE |
| | MANUFACTURER CUT SHEETS. |
| | 4-NEED RECORDED DEED SHOWING AT LEAST 3' |
| | EASEMENT ON NEIGHBOR'S PROPERTY TO |
| | ALLOW FOR EGRESS, WHEN BEDROOMS ARE |
| | LOCATED ON THE ZERO LOT LINE SIDE. |
| | 5-SHEET C-1: REVISE FOUNDATION NOTES. |
| | MINIMUM VAPOR BARRIER TO BE 6 MIL, NOT |
| | 4 MIL. SEC. 1909.2 FBC 2001. |
| | 6-FOOTING FOR PRIVACY WALL AT ZERO LOT |
| | LINE WALL IS ENCROACHING INTO OTHERS |
| | PROPERTY. REVISE AS REQUIRED. |
| | 7-GLASS BLOCK AT BATHROOM AREAS TO BE |
| | SAFETY GLASS IF FACE THICKNESS IS LESS |
| | THAN 0.25". SEC. 2405.2 FBC 2001. |
| | 8-PROVIDE COMPLETE DETAIL AND FASTENER |
| | SPECIFICATIONS FOR INSTALLATION OF |
| | HANGING AIR HANDLING UNIT.SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 9-PROVIDE COMPLETE SPECS FOR GARAGE DOOR |
| | STRUCTURAL BUCK DETAIL. NEED COMPLETE |
| | SIZE OF ANCHOR AND WASHER.SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 10-UPDATE TRUSS ANCHOR SCHEDULE, DETAIL |
| | 3/A5 AND ALL DETAILS THAT NEED TO |
| | REVISE THE LOADS TO COMPLY W/ SECTION |
| | 1609.4.3 FBC 2001, WHICH DOES NOT |
| | ALLOW33% ALLOWABLE STRESS INCREASE |
| | TO BE USED.SEE USP 2003 CATALOGUE |
| | WHICH HAS THE REVISED VALUES. |
| | 11-REVISE DETAIL 2/A5: NEED 2X BUCK TO |
| | SUPPORT WINDOW. SEE PRODUCT APPROVAL. |
| | SEC. 104.2.1.2. CITY AMENDMENTS TO FBC |
| | 12-ENERGY CALCULATIONS: A)PROVIDE |
| | COMPLETE AND CORRECT INFORMATION ON |
| | TOP OF FORM. EG: ADDRESS AND OWNER |
| | INFORMATION. |
| | B)CONDITIONED FLOOR AREA DOESN'T MATCH |
| | AREA SHOWN ON ARCHITECT'S DRAWINGS. |
| | 13-STORM SHUTTERS: REVISE MINIMUM AND |
| | MAXIMUM PANEL SPAN ON INSTALLATION |
| | SCHEDULE. SEE ENGINEERED DRAWINGS AND |
| | DESIGN PRESSURES CALCULATED ON PLANS. |
| | 14-SEE ADDITIONAL COMMENTS ON REVIEWED |
| | SET OF PLANS. PLEASE RETURN REVIEWED |
| | SET AFTER CORRECTIONS ARE DONE TO THE |
| | ORIGINAL CAD DRAWINGS TO EXPEDITE THE |
| | REVIEW PROCESS. |
| | 15-NEED TO UPDATE WORKER'S COMPENSATION |
| | INSURANCE. |
| | 16-SEE COMMENTS BY PLUMBING. |