Plan Review Details - Permit 03041708
Plan Review Stops For Permit 03041708
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-08-20 Cont ID  
Sent By csiegber Date 2003-10-08 Time 15:12 Rev Time 0.00
Received By hpiskura Date 2003-08-20 Time 15:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-07-11 Cont ID  
Sent By hpiskura Date 2003-07-11 Time 12:18 Rev Time 0.00
Received By hpiskura Date 2003-07-11 Time 12:10 Sent To  
Notes
2003-07-11 00:00:00THE SOUTHERN STRUCTURES LETTER DATED
 6/19/03 AND SIGNED AND SEALED BY NEAL
 ROBERTSON CITES A WINDLOAD IMPORTANCE
 FACTOR OF 0.77 WHICH IS NOT APPLICABLE
 TO THIS BUILDING.THIS WILL BE A
 CATEGORY II BUILDING AS DESCRIBED IN
 ASCE 7-98 TABLE 1-1 THUS PROVIDING AN
 IMPORTANCE FACTOR "I" OF 1.00.
  
 THE LETTERS REFERENCE TO WOOD STRUCTURAL
 PANELS FOR IMPACT RESISTANCE IS INVALID
 SINCE THAT SAME CODE SECTION LIMITS
 THAT METHOD TO 130 MPH AREAS.
  
 THE COVER SHEET FOR THE SOUTHERN
 STRUCTURES PLAN DATED 6/19/03 HAS THE
 STATEMENT UNDER THE HEADING BASIC
 DESIGNLOADING "SEE BUILDING CODE TO
 OBTAIN
 REQUIRED WIND COEFFICIENTS MULTIPLIERS."
  
 THIS IS NOT AN ACCEPTABLE SUBSTITUTE FOR
 SPECIFIC DESIGN CRITERIA.PLEASE
 PROVIDE COMPLETE STRUCTURAL
 CALCULATIONS, INCLUDING AN
 INVESTIGATION OF THE COMPONENTS AND
 CLADDING FOR THE ROOF AND WALLS.SEE
 FBC 1609 FOR LOAD COMBINATIONS AND
 REDUCTIONS PERMITTED FOR ASD.
  
 PLEASE PROVIDE FLAME SPREAD
 DATA/LISTINGS FOR THE EXPOSED VINYL
 FACED INSULATION.SEE FBC 708.3.
  
 SEE THE PROEVIOUS COMMENT LISTS RE:
 IMPACT FEES.
  
 THE DECLARED VALUATION OF $275,000.00 IS
 TOO LOW FOR THIS SCOPE OF WORK.THE
 CITY ESTIMATE IS $1,727,104.00.
 THE REMAINING FEE TOTAL AT THIS TIME IS
 $17,601.6O.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-19 Cont ID  
Sent By hpiskura Date 2003-05-19 Time 12:06 Rev Time 0.00
Received By hpiskura Date 2003-05-19 Time 08:30 Sent To  
Notes
2003-05-19 00:00:001) BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED THE IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY, THE PERMIT PLANS
 STAMPED BY THAT OFFICE AND ACOPY OF
 THE PAID RECEIPTATTACHED TO THE
 PERMIT APPLICATION.CALL 561-233-5025
 FOR MORE INFORMATION.
  
 2) SHEET S1.1, NOTES #2.6 CALLS FOR
 "EARTHFORMS" WHICH IS NOT ALLOWED BY
 FBC1804.1.1 AS AMENDED BY THE CITY OF
 WEST PALM BEACH.PLEASE REVISE
 ACCORDINGLY.
  
 3) THE SOUTHERN STRUCTURES METAL
 BUILDING PLAN DECLARES WIND DESIGN FOR
 130 MPH.
 THE CITY OF WEST PALM BEACH IS IN AN
 140 MPH ZONE.
  
 4) SHOW THE WIND DESIGN INFORMATION IN
 ACCORDANCE WITH FBC 1606.1.7 ON THE
 STRUCTURAL PAGE.
  
 5)SHEET CV-1 CITES 110 MPH FOR DOORS
 AND WINDOWS, SEE ABOVE.
  
 6) THE AREA INCREASE ALLOWED BY FBC 503.
 2 IS APPLIED TO THE UNSPRINKLERED AREA
 IN TABLE 500 NOT SPRINKLERED. (16000 IN
 THIS CASE.)IT IS STILL WITHIN THE AREA
 INCREASE BUT PLEASE CORRECT AS
 NECESSARY.
  
 7) THE METAL BUILDING PLANS DO NOT
 INDICATE ANY SPECIAL CONDITIONS FOR THE
 ATTACHMENT OF THE EXTERIOR STUCCO
 SYSTEM IN SEVERAL PLACES.SEE FBC
 2504.2 AND PROVIDE THE NECESSARY
 CONSTRUCTION DETAILS.
  
 8)WILL THE MASONRY WALL BE
 TRANSFERRING LOADS OR FORCES TO THE
 METAL BUILDIN?PLEASE NOTE THE
 LOCATION, DIRECTION, NATURE AND
 MAGNITUDE OF THOSE FORCES ON THE PLANS.
  
 9) WHAT IS THE NATURE AND
 CHARACTERISTICS OF THE COMMODITIES THAT
 ARE INTENDED TO BE STORED IN THIS
 BUILDING?

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-02-02 Cont ID  
Sent By dpalmer Date 2004-02-02 Time 15:12 Rev Time 0.50
Received By dpalmer Date 2004-02-02 Time 15:12 Sent To  
Notes
2004-02-02 00:00:00**REDLINED CA #PER FBPE ONLINE.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-01-26 Cont ID  
Sent By csiegber Date 2004-01-29 Time 16:45 Rev Time 0.50
Received By dpalmer Date 2004-01-23 Time 16:56 Sent To FIRE
Notes
2004-01-26 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE CIRCUIT EM/EXT LTS PER
 700.12E. THIS HAS BEEN REDLINED ON ALL
 PREVIOUS DRAWING AND CHANGES HAVE NOT
 BEEN MADE.
  
 2)NOTE: PLEASE INCLUDE ALL LICENSE #'S
 ON TITLE BLOCK(S) FOR ENGINEERS.
 PER FS 471, 471.023, 61G15-23.002
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-22 Cont ID  
Sent By csiegber Date 2004-01-21 Time 14:14 Rev Time 0.75
Received By dpalmer Date 2003-10-22 Time 14:36 Sent To  
Notes
2003-10-22 00:00:00REDLINED PLANS PER 700.12E

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-15 Cont ID  
Sent By csiegber Date 2003-08-20 Time 08:58 Rev Time 1.00
Received By dpalmer Date 2003-07-15 Time 10:36 Sent To  
Notes
2003-07-15 00:00:00PLANS NOTED, MAINS ARE TO BE GROUPED,
 230-72

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-08 Cont ID  
Sent By dpalmer Date 2003-05-08 Time 16:16 Rev Time 1.50
Received By dpalmer Date 2003-05-08 Time 16:08 Sent To  
Notes
2003-05-08 00:00:00************* UNSAT ***********
  
 1)NOTE: PLEASE SEE RISER DIAGRAM, #`ED
 NOTES #5,7 MENTION EQUIPMENT GROUNDING
 CONDUCTORS FROM GUTTER TO METER AND
 METER TO MAIN DISC`S. THIS WOULD BE
 PARALLELING THE NEUTRAL PER 250-24
  
 2)NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ) 215-3/230-42 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2003-05-22 Cont ID  
Sent By mamini Date 2003-05-22 Time 13:16 Rev Time 0.50
Received By mamini Date 2003-05-22 Time 14:08 Sent To  
Notes
2003-07-02 00:00:00PASSED:
 1. SEE PERMIT # 03051688 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-04-23 Cont ID  
Sent By mamini Date 2003-04-23 Time 13:29 Rev Time 1.00
Received By mamini Date 2003-04-23 Time 13:29 Sent To  
Notes
2003-04-23 00:00:00FAILED:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND CIVIL SITE WORK WILL BE
 REQUIRED.
 2. PLEASE INCLUDE IN THIS SUBMITTAL,
 CALCULATION FOR PERVIOUS, IMPERVIOUS
 AREA AND FOR STORM WATER.CIVIL/SITE
 PLAN SHOULD ALSO INCLUDE POLLUTION
 PREVENTION/EROSION PLAN, NOTE TO GC,
 DETAILS,ECT..
 3. CIVIL PLAN MUST BE APPROVED FOR THE
 CONNECTION TO SERVICES AND BACKFLOWS AND
 METER'S LOCATION, ETC. BY PUBLIC
 UTILITIES ENGINEERING SERVICES,659-8040.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723,
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2004-01-26 Cont ID  
Sent By nmccray Date 2004-01-26 Time 10:03 Rev Time 0.00
Received By nmccray Date 2004-01-26 Time 10:02 Sent To  
Notes
2004-01-26 00:00:00REVISION DATED FOR 1-19-04 SHEETS E-2 &
 E-3 ON EMERGENCY LIGHTING & EXIT SIGNS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-10-30 Cont ID  
Sent By dpalmer Date 2004-01-26 Time 07:49 Rev Time 0.00
Received By mcarsill Date 2003-10-30 Time 16:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-07-16 Cont ID  
Sent By mcarsill Date 2003-07-16 Time 17:07 Rev Time 0.00
Received By mcarsill Date 2003-07-16 Time 17:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-05-22 Cont ID  
Sent By nmccray Date 2003-05-22 Time 14:02 Rev Time 0.00
Received By nmccray Date 2003-05-22 Time 14:01 Sent To  
Notes
2003-05-22 00:00:001) PLEASE REF NFPA 101 LIFE SAFETY CODE
 2000 EDITION.
  
 2) WET FIRE HYDRANTS SHALL BE INSTALLED
 AND OPERATIONAL PRIOR TO AND DOING
 CONSTRUCTION. ACCESS TO THESE FIRE
 HYDRANTS MUST BE MAINTAINED THROUGHOUT
 THE CONSTRUCTION.
  
 3) SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED FOR INSTALLATION OF FIRE ALARM
 AND FIRE SPRINKLER SYSTEM.
  
 4) FAN SHUTDOWN DUCT SMOKE DETECTORS
 SHALL BE INTERCONNECTED TO FIRE ALARM
 SYSTEM.
  
 5) FIRE DEPT CONNECTION SHALL BE 150 FT
 OR LESS TO FIRE HYDRANT.
  
 6) BUILDING SHALL HAVE APPROVED ADDRESS
 NUMBERS PLACED IN A POSITION TO BE
 PLAINLY LEGIBLE AND VISIBLE FROM THE
 STREET AND ROAD FRONTING THE PROPERTY.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-01-29 Cont ID  
Sent By csiegber Date 2004-01-29 Time 16:45 Rev Time 0.00
Received By csiegber Date 2004-01-29 Time 16:45 Sent To E
Notes
2004-01-29 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-01-21 Time 14:14 Rev Time 0.00
Received By csiegber Date 2004-01-21 Time 14:14 Sent To E
Notes
2004-01-21 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-12-09 Cont ID  
Sent By csiegber Date 2003-12-08 Time 09:57 Rev Time 0.00
Received By csiegber Date 2003-12-08 Time 09:57 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-11-26 Cont ID  
Sent By mmclean Date 2003-12-05 Time 12:06 Rev Time 0.00
Received By csiegber Date 2003-11-26 Time 09:36 Sent To Z
Notes
2003-11-26 00:00:00TO Z-LANDSCAPING REV`

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-10-15 Cont ID  
Sent By csiegber Date 2003-10-15 Time 16:15 Rev Time 0.00
Received By csiegber Date 2003-10-15 Time 16:15 Sent To  
Notes
2003-10-15 00:00:00TO COMM BD#31

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-10-08 Cont ID  
Sent By csiegber Date 2003-10-08 Time 15:12 Rev Time 0.00
Received By csiegber Date 2003-10-08 Time 15:12 Sent To B
Notes
2003-10-08 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-20 Cont ID  
Sent By csiegber Date 2003-08-20 Time 08:57 Rev Time 0.00
Received By csiegber Date 2003-08-20 Time 09:32 Sent To  
Notes
2003-08-20 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-07 Time 13:58 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 13:57 Sent To  
Notes
2003-07-07 00:00:00COMM BOARD #11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-02 Cont ID  
Sent By shernand Date 2003-07-02 Time 11:46 Rev Time 0.00
Received By shernand Date 2003-07-02 Time 11:46 Sent To  
Notes
2003-07-02 00:00:00COMM BOARD #42

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-23 Cont ID  
Sent By shernand Date 2003-04-23 Time 10:28 Rev Time 0.00
Received By shernand Date 2003-04-23 Time 10:28 Sent To  
Notes
2003-04-23 00:00:00COM BOARD #33. TWO PERMITS IN BOX. NEEDS
 ZONING APPROVAL.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-11-05 Cont ID  
Sent By pkrauss Date 2003-11-05 Time 16:30 Rev Time 0.40
Received By pkrauss Date 2003-11-05 Time 16:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-17 Cont ID  
Sent By pkrauss Date 2003-07-17 Time 06:58 Rev Time 0.50
Received By pkrauss Date 2003-07-17 Time 06:58 Sent To  
Notes
2003-07-17 00:00:00APPROVED 7-15-03 PHK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-05-19 Cont ID  
Sent By pkrauss Date 2003-05-19 Time 14:26 Rev Time 0.40
Received By pkrauss Date 2003-05-19 Time 14:07 Sent To  
Notes
2003-05-19 00:00:00DENIED:
  
 1.DUCT SMOKE DETECTORS SHALL BE R
 INSTALLED IN THE SUPPLY AIR DUCT SYSTEMS
 WITH THE DESIGN CAPACITY GREATER THAN
 2,000 CFM.2001 FBC(M) 606.2.1
  
 2.FAN SHUTDOWN BE DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM STROBE
 IN NORMALLY OCCUPIED AREAS OR ACTIVATE
 A VISIBLE & AUDIBLE SUPERVISORY SIGNAL
 AT A CONSTANTLY ATTENDED LOCATION.
  
 3.CONDENSATE SHALL TERMINATE A
 MINIMUM OF 12" AWAY FROM THE BUILDING
 STRUCTURE.2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-07-14 Cont ID  
Sent By csiegber Date 2003-12-08 Time 09:57 Rev Time 0.50
Received By kstevens Date 2003-07-12 Time 16:50 Sent To  
Notes
2003-07-19 00:00:00DENIED
 REFERENCE: FLORIDA STATUTES
  
 1) 61G15-23.002(2) MORE INFORMATION RE-
 QUIRED ON ENGINGEER'S TITLE BLOCK.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-23 Cont ID  
Sent By kstevens Date 2003-05-23 Time 12:07 Rev Time 1.25
Received By kstevens Date 2003-05-23 Time 12:07 Sent To  
Notes
2003-05-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PLEASE INDICATE THE NATURE OF MATL'S
 BEING STORED IN WAREHOUSE. MSDS AND MAN-
 UFACTURE SHEETS SHALL BE REQUIRED TO DE-
 TERMINE IF AN EMERGENCY EYEWASH/SHOWER
 WILL BE REQUIRED PER SECTION 411.1.
 2) WATER RISER DIAGRAM REQUIRED.
 3) SHUT OFF VALVE REQUIRED FOR HOSE BIBB
 SECTION 606.2(2).
 4) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE.
 5) SHT P-1 PLUMBING PROJECT NOTES:
 #29 AIR CHAMBERS ARE NOT APPROVED.
 PLEASE DELETE REFERENCE.
 #34 DIELECTRIC UNIONS ARE ONLY APPROVED
 FOR GAS APPLICATION. DELETE REFERENCE OR
 MODIFY NOTE TO READ DIELECTRIC COUPLING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 3 Status P Date 2003-12-09 Cont ID  
Sent By mmclean Date 2003-12-09 Time 10:22 Rev Time 0.00
Received By mmclean Date 2003-12-09 Time 10:22 Sent To  
Notes
2003-12-09 00:00:0012/9/03 GIVEN TO PHYLLIS MM

Review Stop Z ZONING
Rev No 2 Status P Date 2003-12-05 Cont ID  
Sent By csiegber Date 2003-12-09 Time 08:53 Rev Time 0.00
Received By mmclean Date 2003-12-05 Time 12:06 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-23 Cont ID  
Sent By csiegber Date 2003-11-26 Time 09:36 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***