Plan Review Details - Permit 03041672
Plan Review Stops For Permit 03041672
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-05-01 Cont ID  
Sent By rbrown Date 2003-05-01 Time 14:12 Rev Time 0.00
Received By rbrown Date 2003-05-01 Time 14:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-25 Cont ID  
Sent By rbrown Date 2003-04-25 Time 09:06 Rev Time 0.00
Received By rbrown Date 2003-04-25 Time 09:06 Sent To  
Notes
2003-04-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* APPENDIX F102.2.4ROOF COVERING
 IN THE FIRE DISTRICT SHALL CONFORM TO
 THE REQUIREMENTS OF CLASS A OR B ROOF
 COVERINGS AS DEFINED IN FBC1505.PAGE 3
 OF THE SUBMITTED AEICOR PRODUCT APPROVAL
 NOA# 01-0820.01 GIVES THREE OPTIONS FOR
 THE FIRE BARRIER BOARD NECESSARY TO
 ACHIEVE CLASS A OR B FIRE RATING.NONE
 OF THESE OPTIONS HAVE BEEN SPECIFIED ON
 EITHER THE PLANS OR SECTION D OF THE
 SUBMITTED UNIFORM PERMIT APPLICATION.
 AMEND THE PLANS, AND THE UNIFORM PERMIT
 APPLICATION, TO SPECIFY FIRE BARRIER
 BOARD.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-22 Cont ID  
Sent By shernand Date 2003-04-22 Time 15:58 Rev Time 0.00
Received By shernand Date 2003-04-22 Time 15:58 Sent To B
Notes
2003-04-22 00:00:00MISC BOX