Plan Review Details - Permit 03041590
Plan Review Stops For Permit 03041590
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-06-02 Cont ID  
Sent By sthyng Date 2003-06-02 Time 08:04 Rev Time 1.50
Received By sthyng Date 2003-06-02 Time 08:04 Sent To  
Notes
2003-06-02 00:00:00******PROVISO******
  
 1.)SUBMIT FOR A SEPARATE PERMIT FOR
 THE GARAGE DOORS.
 2.)SUBMIT A REVISION FOR SHEET A5
 USING 2003 CATALOG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-22 Cont ID  
Sent By kstevens Date 2003-05-31 Time 08:01 Rev Time 3.50
Received By sthyng Date 2003-05-21 Time 18:45 Sent To  
Notes
2003-05-22 00:00:00*******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ADDITIONAL FEES REQUIRED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND ORIGINAL RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.233-5025
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 4.)SEPARATE PERMITS REQUIRED (GAS,
 FENCING, POOL).
  
 5.)SHEET A1, WINDLOAD, IS PER 1997
 SBC.CURRENT CODE IS FBC 2001.
  
 6.)TYPICAL WINDOW AND SGD JAMB DETAIL
 MUST COMPLY WITH FBC 1707.4.4.2.
  
 7.)THE TEXT FOR THE GLASS AT THE TUB
 (MASTER BATH), A4, IS UPSIDE DOWN AND
 BACKWARDS.TEXT ON ELEVATION A1 IS
 BACKWARDS.
  
 8.)A 24" WIDE IMPACT CASEMENT WINDOW
 DOES NOT COMPLY WITH FBC 1005.4, EGRESS
 REQUIREMENTS, BEDROOM 2, A4.
  
 9.)THE INSULATION FOR THE ADJACENT
 WALL IS NOT SHOWN (A4).PROVIDE A
 DETAIL FOR THIS WALL.
  
 10.)PROVIDE AN INTERIOR WALL SECTION.
  
 11.)THE TRUSS ANCHOR SCHEDULE REFERS
 TO HUGHES CONNECTORS.HUGHES IS NO
 LONGER MANUFACTURED.REFER TO ANOTHER
 MANUFACTURER; ALSO NOT 2003 CATALOGS
 WITH NEW UPLIFT LIMITATIONS (A5).
  
 12.)PROVIDE A ROOF SHEATHING
 ATTACHMENT SCHEDULE.
  
 13.)PROVIDE THE CEILING FINISH
 INFORMATION FOR THE ENTRY AND COVERED
 PATIO, WITH ATTACHMENTS.
  
 14.)PROVIDE PRODUCT APPROVALS FOR THE
 CASEMENT WINDOWS WITH IMPACT PROTECTION,
 AND THE 16' AND 8' GARAGE DOORS.
  
 15.)FLOOR PLAN REFERS TO SECTION 1-A6,
 NOT ON PLAN.THE UNMARKED SECTION ON
 PAGE A6 REFERS TO (3), WHERE IS THIS
 DETAIL?ALSO REFERS TO A DIAPHRAGM
 SCHEDULE, NOT ON PLAN.
  
 16.)TEXT (BOTTOM LEFT CORNER), A5, IS
 ILLEGIBLE.WHEN RESUBMITTING, READ
 THE PLAN TO ENSURE THAT ALL TEXT ON THE
 PLAN IS LEGIBLE.
  
 17.)PROVIDE A SOILS INVESTIGATION
 REPORT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-08-08 Cont ID  
Sent By btrobaug Date 2003-08-08 Time 17:10 Rev Time 0.50
Received By btrobaug Date 2003-08-08 Time 17:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-28 Cont ID  
Sent By alange Date 2003-08-06 Time 14:25 Rev Time 0.50
Received By btrobaug Date 2003-05-28 Time 17:01 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-09 Cont ID  
Sent By shernand Date 2003-05-28 Time 08:52 Rev Time 0.75
Received By btrobaug Date 2003-05-09 Time 09:03 Sent To P
Notes
2003-05-09 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 TO THE PLAN FOR CODE COMPLIANCE.
  
 1} INDICATE THE LOCATION OF THE SERVICE
 EQUIPMENT ON THE DRAWING.
  
 2} PLEASE NOTE THAT THE GROUNDING
 ELECTRODE CONDUCTOR MUST BE SIZED PER
 250-66 AND RAN CONTINUOUS PER 250-64(C).
  
 3} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1.
  
 4} THE OVEN LISTED FOR THE LOAD CALC
 MUST COMPLY WITH 220-19 (8KW).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-06 Cont ID  
Sent By alange Date 2003-08-06 Time 14:23 Rev Time 0.00
Received By alange Date 2003-08-06 Time 14:23 Sent To E
Notes
2003-08-06 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-28 Cont ID  
Sent By shernand Date 2003-05-28 Time 08:52 Rev Time 0.00
Received By shernand Date 2003-05-28 Time 08:52 Sent To E
Notes
2003-05-28 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-22 Cont ID  
Sent By shernand Date 2003-04-22 Time 16:02 Rev Time 0.00
Received By shernand Date 2003-04-22 Time 16:02 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-19 Cont ID  
Sent By kstevens Date 2003-05-12 Time 09:13 Rev Time 0.30
Received By pkrauss Date 2003-05-19 Time 13:14 Sent To B
Notes
2003-05-19 00:00:00MECHANICAL PERMIT 03041602

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-05-31 Cont ID  
Sent By kstevens Date 2003-05-31 Time 08:01 Rev Time 0.33
Received By kstevens Date 2003-05-31 Time 08:01 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-12 Cont ID  
Sent By btrobaug Date 2003-05-28 Time 17:28 Rev Time 0.33
Received By kstevens Date 2003-05-10 Time 17:22 Sent To M
Notes
2003-05-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN.
 2) 909.1 WASH MACHINE & LAUNDRY SINK
 SHALL NOT DRAIN INTO THE HORIZONTAL WET
 VENT OF THE BATHROOM GROUP. W/M & L/T
 SHALL TIE IN DOWNSTREAM OF THE BATHROOM
 GROUP.
 3) VERTICAL RISE ON A ISOMETRIC INDICAT-
 ES A SECOND FLOOR.
 4) 905.3 NO HORIZONTAL DRY VENTS.
 5) KITCHEN SINK MISLABELED AS LAVS.
 6) BIDET NOT VENTED.
 7) PIPE SIZES MISSING.
 (SEE ATTACHED SHEET FOR EXAMPLE OF APP-
 ROVED SANITARY RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-25 Cont ID  
Sent By shernand Date 2003-04-22 Time 16:02 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***