| Plan Review Stops For Permit 03041561 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-04-21 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-21 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-21 |
Time |
13:57 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2003-04-24 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-21 |
Time |
13:57 |
Rev Time |
1.33 |
| Received By |
kstevens |
Date |
2003-04-23 |
Time |
18:54 |
Sent To |
|
|
| Notes |
| 2003-04-24 00:00:00 | DRYER ROOMS ARE CONFINED SPACES. | | | OPENINGS REQUIRED PER SECTION 304.3.1 0R | | | SECTION 304.3.2 - 1,100 CU FT REQUIRED | | | IN EACH. 1ST FLOOR PROVIDES 955 CU FT | | | AND 2ND FLOOR PROVIDES 255 CU FT OR 803 | | | CU FT DEPENDING ON DOORS TO CLOSET AND | | | CEILING HEIGHT, (CALCULATED AT 9'4") | | | **SHUT OFF VALVES REQD. 409.7 | | | **SEDIMENT TRAPS REQD. 408.4 |
|
|
|