Plan Review Details - Permit 03041480
Plan Review Stops For Permit 03041480
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-03-15 Cont ID  
Sent By rmcdouga Date 2004-03-15 Time 07:01 Rev Time 1.00
Received By rmcdouga Date 2004-03-15 Time 07:01 Sent To  
Notes
2004-03-15 00:00:00REVISION TO SHEETS A7 & A9 ADDING
 LOCATION AND DETAILS OF TRUSS HANGER IS
 OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-12-12 Cont ID  
Sent By csiegber Date 2004-03-11 Time 11:28 Rev Time 0.50
Received By rmcdouga Date 2003-12-12 Time 12:08 Sent To P
Notes
2003-12-12 00:00:00REVISION TO CHANGE PRIVACY FENCE TO WALL
 AND CHANGE BEAM SIZE AT REAR PORCH

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-09-09 Cont ID  
Sent By rmcdouga Date 2003-09-09 Time 12:15 Rev Time 1.50
Received By rmcdouga Date 2003-09-09 Time 12:15 Sent To  
Notes
2003-09-09 00:00:00REVISION TO SHEETS A1,A2,A3,A4,A5 ARE
 OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-06-11 Cont ID  
Sent By csiegber Date 2003-09-08 Time 13:48 Rev Time 2.00
Received By rmcdouga Date 2003-06-11 Time 17:30 Sent To  
Notes
2003-06-11 00:00:00BUILDING PROVISO
  
 1) SUBMIT SOIL BORING TEST REPORT PRIOR
 TO POURING THE FOUNDATION.
  
 2) PAY IMPACT FEES TO COUNTY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-02 Cont ID  
Sent By shernand Date 2003-06-11 Time 11:11 Rev Time 3.00
Received By rmcdouga Date 2003-06-02 Time 10:00 Sent To  
Notes
2003-06-02 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY CITY AMEND. TO FBC 1804.2.2.
  
 4) THE 7/8" STUCCO THICKNESS REQUIRED BY
 ASTM C 926 ON METAL LATH OVER PLYWOOD
 SHEATHING WAS CHANGED ON THE WRONG WALL
 SECTION ON SHEET A6. THE 5/8" STUCCO
 OVER CONCRETE BLOCK IS ACCEPTABLE.
 PLEASE CORRECT.
  
 5) DETAIL 25 ON A8,WHICH IS SPECIFIED ON
 SHEETS A7 AND A9, FOR THE CONNECTION OF
 THE FLOOR GIRDER TO THE WOOD POST IN THE
 BEARING WALL IS NOT THE CORRECT DETAIL.
  
 6) THE UPLIFT VALUES FOR THE CONNECTORS
 GIVEN IN DETAILS 24/A8, 29/A8, 32/A8 AND
 36/A8 ARE NOT CORRECT. SEE 2003 USP
 CATALOG AND NOTES ON THE PLAN.
  
 7) THE SECOND FLOOR BRACING PLAN ON A10
 SPECIFIES TC-5 AND TC-6 CONNECTORS.
 THESE ARE NOT LISTED IN THE CONNECTOR
 SCHEDULE ON A9. PLEASE CORRECT.
  
 8) DETAIL 5/A10 IS SPECIFIED ON SHEET
 A10. THERE AREN'T ANY DETAILS ON SHEET
 A10.
  
 SEE NOTATIONS ON THE REVIEWED PLANS.
 PLEASE RETURN OLD PAGES WITH THE NEW
 WHEN RESUBMITTING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-15 Cont ID  
Sent By kstevens Date 2003-05-31 Time 07:10 Rev Time 5.00
Received By rmcdouga Date 2003-05-15 Time 10:55 Sent To  
Notes
2003-05-15 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY CITY AMEND. TO FBC 1804.2.2.
  
 4) THE PRIVACY WALL FOOTING AT THE ZERO
 LOT LINE ENCROACHES ON THE ADJACENT
 PROPERTY.
  
 5) THE FOUNDATION PLAN AND FLOOR PLAN
 SHEETS ARE NOT NUMBERED.
  
 6) THE FLOOR PLAN REFERENCES DETAIL 2 ON
 A3 FOR THE WOOD FRAME BEARING WALL. THE
 CORRECT DETAIL IS 3 ON A3.
  
 7) DETAIL 3 ON A3 REFRENCES THE SFBC.
 THE CURRENT CODE IS 2001 FBC.
  
 8) DETAIL 1 ON A3 SPECIFIES R-11
 INSULATION IN THE ATTIC. THE ENERGY
 CALCULATIONS REQUIRE R-19.
  
 9) SPECIFY ON THE PLANS THAT THE BALCONY
 GUARDRAILS ARE REQUIRED TO HAVE
 INTERMEDIATE RAILS THAT SPACED TO REJECT
 A 4"SPHERE AND A BOTTOM RAIL THAT WILL
 REJECT A 2"SPHERE. SUBMIT SHOP DRAWINGS.
 FBC 1015.3
  
 10) FIREBLOCKING IS REQUIRED AT THE
 CONCEALED SPACES BETWEEN STAIR STRINGERS
 AT THE TOP AND BOTTOM OF THE RUN PER
 FBC 2305.1.4.
  
 11) THE STUCCO ON METAL LATH AT THE
 EXTERIOR WALL SECTION ON A6 IS REQUIRED
 TO BE 7/8" THICK PER ASTM C 926.
  
 12) SPECIFY ON THE PLANS THAT ADEQUATE
 SUBSTRATE WILL BE PROVIDED AT GLAZED
 OPENINGS IN THE WOOD FRAME WALLS FOR THE
 ATTACHMENT OF STORM PANELS.
  
 13) DETAIL 12 ON A7 SPECIFIED ON SHEET
 A9 IS NOT THE CORRECT DETAIL FOR THE
 GIRDER TO WOOD BEARING WALL CONNECTION.
  
 14) THERE IS NO DETAIL 12 ON A8 AS
 SPECIFIED ON SHEET A9AT THE COVERED
 BALCONY.
  
 15) THE TRUSS CONNECTORS IN THE SCHEDULE
 ON A9, ARE ALL DESIGNED TO BE EMBEDDED
 IN CONCRETE. THESE ARE INCORRECTLY
 SPECIFIED AT THE WOOD FRAME WALLS AND
 WOOD GIRDERS AT THE BALCONY.
  
 16)THE CONNECTOR SCHEDULE ON A9 CONTAINS
 INCORRECT INFORMATION. THE MANUFACTURER
 DOES NOT ALLOW AN INCREASE IN THE LOAD
 VALUES BY ADDING MORE NAILS THAN
 SPECIFIED IN THE CATALOG. YOU ARE
 ALLOWED TO SPECIFY LESS NAILS AND REDUCE
 THE LOADS BASED ON SHEAR VALUES OF THE
 NAILS. THE VALUES LISTED IN THE SCHEDULE
 INCLUDE THE ONE THIRD INCREASE ON STEEL
 ALLOWABLE STRESS DESIGN VALUES WHICH IS
 NO LONGER ALLOWED BY FBC 1609.4.3. SEE
 2003 USP CATALOG.
  
 17) THE STORM PANEL INFORMATION IS
 INCORRECT. THE WRONG ANCHOR TYPE IS
 LISTED IN THE SCHEDULE FOR OPENINGS #12,
 13,14,15,18 AND 19, WHICH ARE IN WOOD
 FRAME WALLS. THE OPENINGS SIZES LISTED
 ARE INCORRECT FOR OPENINGS #14,18 & 19.
 THE ALLOWABLE PANEL SPANS ARE EXCEEDED
 AT SEVERAL OPENINGS BASED ON THE SPAN
 TABLES IN THE PRODUCT APPROVAL DRAWINGS.
 PLEASE CORRECT.
  
 18) SEE HANDWRITTEN NOTATIONS ON THE
 REVIEWED PLAN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-07-09 Cont ID  
Sent By btrobaug Date 2004-07-09 Time 10:33 Rev Time 0.50
Received By btrobaug Date 2004-07-09 Time 09:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-08-04 Cont ID  
Sent By csiegber Date 2004-07-07 Time 16:48 Rev Time 0.50
Received By btrobaug Date 2003-08-04 Time 14:56 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-28 Cont ID  
Sent By alange Date 2003-07-28 Time 10:18 Rev Time 0.50
Received By btrobaug Date 2003-05-28 Time 07:07 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-06 Cont ID  
Sent By shernand Date 2003-05-23 Time 15:52 Rev Time 0.75
Received By btrobaug Date 2003-05-06 Time 06:55 Sent To P
Notes
2003-05-06 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 AND RESUBMIT FOR REVIEW.
  
 1} THE #4 GEC IS INCORRECT FOR THE 400
 AMP SERVICE SHOWN.SHOULD BE 1/0 PER
 250-66.
  
 2} THE FEEDER TO PANEL "B" IS MISSING AN
 EQUIPMENT GROUND PER 250-122.
  
 3} THE LAUNDRY CIRCUIT MUST BE
 CALCULATED @ 1500 VA PER 220-16(B).
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} THE SMOKE DETECTOR IN THE KITCHEN
 DOES NOT COMPLY WITH 8-1.4.2
 NFPA-72.MUST BE A LISTED HEAT DETECTOR.
  
 6} THE SMOKE DETECTOR AT THE DOOR OF THE
 MASTER BEDROOM MUT BE IN THE VESTIBULE
 TO COMPLY WITH 8-1.4.1.6(2) NFPA-72.
  
 7} PANELS "A" & "B" ARE SHOWN AS 200 AMP
 & FED AS 200 AMP ON THE RISER,BUT LIST-
 ED AS 150 AMP ON THE SCHEDULES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-07-07 Cont ID  
Sent By csiegber Date 2004-07-07 Time 16:48 Rev Time 0.00
Received By csiegber Date 2004-07-07 Time 16:48 Sent To E
Notes
2004-07-07 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-03-11 Cont ID  
Sent By csiegber Date 2004-03-11 Time 11:28 Rev Time 0.00
Received By csiegber Date 2004-03-11 Time 11:28 Sent To B
Notes
2004-03-11 00:00:00TO RM DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-09-08 Cont ID  
Sent By csiegber Date 2003-09-08 Time 13:46 Rev Time 0.00
Received By csiegber Date 2003-09-08 Time 13:46 Sent To B
Notes
2003-09-08 00:00:00TO RM DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-07-28 Cont ID  
Sent By alange Date 2003-07-28 Time 10:18 Rev Time 0.00
Received By alange Date 2003-07-28 Time 10:18 Sent To E
Notes
2003-07-28 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-07-08 Cont ID  
Sent By shernand Date 2003-07-08 Time 16:27 Rev Time 0.00
Received By shernand Date 2003-07-08 Time 16:27 Sent To B
Notes
2003-07-08 00:00:00RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-27 Cont ID  
Sent By shernand Date 2003-06-27 Time 16:47 Rev Time 0.00
Received By shernand Date 2003-06-27 Time 16:47 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-11 Cont ID  
Sent By shernand Date 2003-06-11 Time 11:11 Rev Time 0.00
Received By shernand Date 2003-06-11 Time 11:11 Sent To B
Notes
2003-06-11 00:00:00RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-23 Cont ID  
Sent By shernand Date 2003-05-23 Time 15:52 Rev Time 0.00
Received By shernand Date 2003-05-23 Time 15:52 Sent To E
Notes
2003-05-23 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-21 Cont ID  
Sent By shernand Date 2003-04-21 Time 10:11 Rev Time 0.00
Received By shernand Date 2003-04-21 Time 10:11 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-13 Cont ID  
Sent By kstevens Date 2003-05-10 Time 15:32 Rev Time 0.20
Received By pkrauss Date 2003-05-13 Time 09:49 Sent To B
Notes
2003-05-13 00:00:00MECH PERMIT 03041510

Review Stop P PLUMBING
Rev No 5 Status P Date 2003-12-13 Cont ID  
Sent By jleech Date 2003-12-13 Time 12:00 Rev Time 0.25
Received By jleech Date 2003-12-13 Time 12:00 Sent To  
Notes
2003-12-13 00:00:00REVISED SANITARY RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-07-03 Cont ID  
Sent By rmcdouga Date 2003-12-12 Time 12:11 Rev Time 0.50
Received By kstevens Date 2003-07-03 Time 16:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-06-14 Cont ID  
Sent By shernand Date 2003-06-27 Time 16:47 Rev Time 0.25
Received By kstevens Date 2003-06-14 Time 07:26 Sent To  
Notes
2003-06-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT FE-
 FLECT FLOOR PLAN. RISER SHOWS PICKING UP
 THE POWDER ROOM PRIOR TO KITCHEN SINK,
 SHOWS 2ND FLOOR BATHROOM REVERSED FROM
 FLOOR LAYOUT, AND THE BAR SINK SHOWN ON
 THE FLOOR PLAN IS MISSING FROM THE RISER
 DIAGRAM. SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-05-31 Cont ID  
Sent By kstevens Date 2003-05-31 Time 07:10 Rev Time 0.50
Received By kstevens Date 2003-05-31 Time 07:10 Sent To B
Notes
2003-05-31 00:00:00PASSED PROVISO - 706.3 & EXTRA DRAIN
 LINE M/B

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-10 Cont ID  
Sent By btrobaug Date 2003-05-28 Time 07:26 Rev Time 0.33
Received By kstevens Date 2003-05-10 Time 15:31 Sent To M
Notes
2003-05-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT FLOOR PLAN.
 2) SEC 909.1 WASH MACHINE AND LAUNDRY
 SINK SHALL NOT DRAIN INTO THE WET VENTED
 HORIZONTAL DRAIN FOR THE MASTER BATH.
 THE LAUNDRY FIXTURES SHALL TIE IN DOWN-
 STREAM OF THE WET VENTED BATHROOM GROUP.
 3) THREE LAVS SHOWN FOR MASTER BATH ON
 RISER DIAGRAM. ONLY TWO SHOWN ON FLOOR
 PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-08-08 Cont ID  
Sent By rmcdouga Date 2003-08-08 Time 11:42 Rev Time 2.00
Received By rmcdouga Date 2003-08-08 Time 11:42 Sent To  
Notes
2003-08-08 00:00:00REVISION TO CHANGE MASONRY PRIVACY FENCE
 TO PVC FENCE IS OK. 8-8-03 RM

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-25 Cont ID  
Sent By shernand Date 2003-04-21 Time 10:11 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***