Plan Review Details - Permit 03041473
Plan Review Stops For Permit 03041473
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-10-29 Cont ID  
Sent By sthyng Date 2003-10-29 Time 16:22 Rev Time 0.50
Received By sthyng Date 2003-10-29 Time 16:22 Sent To  
Notes
2003-10-29 00:00:00REVISED ANCHORING SCHEDULE AS PER
 PROVISO

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-06-04 Cont ID  
Sent By csiegber Date 2003-10-24 Time 12:42 Rev Time 0.50
Received By sthyng Date 2003-06-04 Time 14:11 Sent To  
Notes
2003-06-04 00:00:00SEE PREVIOUS STOP FOR PROVISO

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-03 Cont ID  
Sent By shernand Date 2003-06-04 Time 14:07 Rev Time 1.00
Received By sthyng Date 2003-06-03 Time 07:32 Sent To  
Notes
2003-06-03 00:00:00*******PROVISO*******
 SUBMIT A REVISION FOR SHEETS
 A7 AND A8 USING 2003 USP CATALOG
 WITHOUT STRESS INCREASE FOR STEEL.
  
 PASSED WITH PROVISO - NEEDS IMPACT
 FEES ONLY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-16 Cont ID  
Sent By btrobaug Date 2003-05-30 Time 12:35 Rev Time 2.50
Received By sthyng Date 2003-05-16 Time 11:31 Sent To  
Notes
2003-05-16 00:00:00*********CORRECTIONS*********
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 4.)WINDOW V SHOULD BE TEMPERED; CHANGE
 THE FLOOR PLAN A6 AND THE WINDOW
 SCHEDULE FBC 2405.2.
  
 5.)'REPAIR MASONRY GAPS" AND "WINDOW
 & SGD' DETAILS, A12, TO COMPLY WITH
 1707.4.4.2.
  
 6.)WOOD BALCONY RAILING TO COMPLY
 WITH FBC 1015.3.
  
 7.)PROVIDE A STRUCTURAL PLAN FOR THE
 STAIRS INDICATING HOW STAIRS AND LANDING
 WILL BE SUPPORTED.PROVIDE A SECTION
 FOR THE STAIRS SHOWING LOCATION AND
 MATERIALS USED FOR FIREBLOCKING
 FBC 2305.1.4.
  
 8.)THE UPLIFT VALUES FOR SOME OF THE
 CONNECTORS ARE INCORRECT.REFER TO
 USP 2003 CATALOG.
  
 9.)THE SINGLE HUNG WINDOW AND TILE
 SPECS ARE ILLEGIBLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-01-09 Cont ID  
Sent By btrobaug Date 2004-01-09 Time 15:55 Rev Time 0.50
Received By btrobaug Date 2004-01-09 Time 15:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-06-20 Cont ID  
Sent By csiegber Date 2004-01-07 Time 16:51 Rev Time 0.33
Received By btrobaug Date 2003-06-20 Time 16:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-30 Cont ID  
Sent By shernand Date 2003-06-20 Time 11:02 Rev Time 0.50
Received By btrobaug Date 2003-05-30 Time 12:14 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-06 Cont ID  
Sent By shernand Date 2003-05-30 Time 08:47 Rev Time 0.75
Received By btrobaug Date 2003-05-06 Time 08:46 Sent To P
Notes
2003-05-06 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE CORRECT THE FOLLOWING AND
 RESUBMIT FOR REVIEW.
  
 1} THE ELECTRICAL SUB PANEL IS SHOWN AS
 MLO BUT THERE IS NO BREAKER FOR IT
 LISTED IN THE MAIN PANEL.SEE 230-71.
  
 2} THE METER LOCATION APPEARS TO BE IN
 VIOLATION OF 110-26 IN RELATION TO THE
 A/C UNITS.
  
 3} THE SMOKE DETECTORS IN AND OUT OF
 BEDROOM #5 DO NOT COMPLY WITH 8-1.4.2.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-01-07 Cont ID  
Sent By csiegber Date 2004-01-07 Time 16:51 Rev Time 0.00
Received By csiegber Date 2004-01-07 Time 16:51 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 12:42 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 12:42 Sent To B
Notes
2003-10-24 00:00:00TO ST DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-06-20 Cont ID  
Sent By shernand Date 2003-06-20 Time 11:02 Rev Time 0.00
Received By shernand Date 2003-06-20 Time 11:02 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-20 Cont ID  
Sent By shernand Date 2003-06-20 Time 10:41 Rev Time 0.00
Received By shernand Date 2003-06-20 Time 10:41 Sent To E
Notes
2003-06-20 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-04 Cont ID  
Sent By shernand Date 2003-06-04 Time 14:07 Rev Time 0.00
Received By shernand Date 2003-06-04 Time 14:07 Sent To B
Notes
2003-06-04 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-30 Cont ID  
Sent By shernand Date 2003-05-30 Time 08:47 Rev Time 0.00
Received By shernand Date 2003-05-30 Time 08:47 Sent To E
Notes
2003-05-30 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-21 Cont ID  
Sent By shernand Date 2003-04-21 Time 09:28 Rev Time 0.00
Received By shernand Date 2003-04-21 Time 09:28 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-15 Cont ID  
Sent By kstevens Date 2003-05-10 Time 16:02 Rev Time 0.20
Received By pkrauss Date 2003-05-15 Time 09:54 Sent To B
Notes
2003-05-15 00:00:00MECHANICAL PERMIT 03041494

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-05-10 Cont ID  
Sent By btrobaug Date 2003-05-06 Time 08:46 Rev Time 0.33
Received By kstevens Date 2003-05-10 Time 15:53 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-25 Cont ID  
Sent By shernand Date 2003-04-21 Time 09:28 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***