Plan Review Details - Permit 03041471
| Plan Review Stops For Permit 03041471 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-05-14 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-05-14 |
Time |
13:10 |
Rev Time |
1.00 |
| Received By |
sthyng |
Date |
2003-05-14 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2003-05-14 00:00:00 | PASSED PER PREINSPECT BY BOBBY COMPTON |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-05-13 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-05-13 |
Time |
16:26 |
Rev Time |
0.50 |
| Received By |
sthyng |
Date |
2003-05-13 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2003-05-13 00:00:00 | ******CORRECTIONS******* | | | | | | 1.)PROVIDE A WALL SECTION. | | | | | | 2.)THE PROJECT DESCRIPTION ON THE | | | PERMIT APPLICATION SAYS THAT YOU ARE | | | INSTALLING INSULATION.WHERE?WHAT | | | TYPE? IT REFERS TO DRYWALL INSTALLATION; | | | WHERE?NEW WALLS ONLY?EXISTING WALLS? | | | IT REFERS TO ROTTON WOOD REPLACEMENT. | | | WHERE?STRUCTURAL?EXTERIOR WALLS OR | | | INTERIOR WALLS?WILL CONNECTIONS BE | | | REPLACED? | | | | | | 3.)A NOTICE OF COMMENCEMENT IS | | | REQUIRED TO BE FILED WITH THE CLERK OF | | | COURTS BEFORE A PERMIT CAN BE ISSUED. | | | | | | 4.)ADDITIONAL PERMITS REQUIRED; | | | ELECTRIC, PLUMBING, MECHANICAL. | | | | | | IF YOU HAVE ANY QUESTIONS, CALL | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2003-04-25 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-21 |
Time |
16:49 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2003-04-24 |
Time |
16:51 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-04-21 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-21 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-21 |
Time |
16:48 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2003-04-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-04-26 |
Time |
07:58 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2003-04-28 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2003-04-28 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR REVIEW | | | | | | PLEASE NOTE, ENERGY CALCS SUBMITTED - | | | 3 COPIES FOR THE 2ND FLOOR AND ONLY ONE | | | COPY SUBMITTED FOR THE 1ST FLOOR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2003-04-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-04-25 |
Time |
16:00 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2003-04-26 |
Time |
07:56 |
Sent To |
M |
|
| Notes |
|
|
|