Plan Review Details - Permit 03041464
Plan Review Stops For Permit 03041464
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-06-24 Cont ID  
Sent By kstevens Date 2004-04-20 Time 07:37 Rev Time 0.15
Received By jwitmer Date 2003-06-24 Time 12:49 Sent To  
Notes
2003-06-24 00:00:00STOREFRONT DRAWINGS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-06-24 Cont ID  
Sent By jwitmer Date 2003-06-24 Time 12:17 Rev Time 1.33
Received By jwitmer Date 2003-06-24 Time 12:17 Sent To  
Notes
2003-06-24 00:00:00************BUILDING PROVISO************
 PERMIT: 03041464
 ADDRESS:2330 TECUMSEH DRIVE
 CONT: COLUMBIA BUILDING GROUP
  
 1) STORM SHUTTER SCHEDULE CORRECT
 OPENINGS 2 & 3 TO REFLECT THE CORRECT
 WIDTH AND HEIGHT OF SHUTTER AND THE SPAN
 VERTICAL OR HORIZONTALBEFORE
 FINAL INSPECTION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)805-6715

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-13 Cont ID  
Sent By kstevens Date 2003-06-24 Time 08:13 Rev Time 3.00
Received By jwitmer Date 2003-06-13 Time 15:51 Sent To  
Notes
2003-06-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03041464
 ADD: 2330 TECUMSEH DR
 CONT: COLUMBIA BUILDING GROUP
 TEL: (561)624-9610
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) PLANS STILL INDICATE HUGHES PRODUCT
 OR THE NAME CHANGED FROM HUGHES TO USP
 AND THE OLD MODEL NUMBER.
  
 2) META 20(2) STRAPS @ 130%= 1985 NOT
 THE 2410 INSCHEDULE
  
 3) STORM SHUTTER SCHEDULE WINDOW 2& 3
 ARE 24"X120" THE SHUTTER 15X36?????
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)805-6715

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-18 Cont ID  
Sent By kstevens Date 2003-06-10 Time 11:17 Rev Time 2.22
Received By jwitmer Date 2003-05-18 Time 12:24 Sent To  
Notes
2003-05-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03041464
 ADD: 2330 TECUMSEH DRIVE
 CONT: COLUMBIA BUILDING GROUP
 TEL: (561)719-5333
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) SHEET ST DETAIL 4 TYPICAL WINDOW DE-
 TAIL INDICATES THE USE OF HUGHES PRO-
 DUCTS, OUT OF BUSINESS FOR 2 YEARS,
 MERGED WITH USP, PROVIDE CURRENT PRODUCT
 INFORMATION. USE 2003 CATOLOG WITH
 REDUCED VALUES.
  
 2) THERE SEEMS TO BE NO TRUSS ANCHOR
 SCEDULE FOUND IN THE PLAN.
 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
  
 3)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 4) SHEET ST INDICATES TAPPERED BUCK,
 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 5) MISSING PRODUCT TESTING REPORT FOR
 THE FRONT DOORS,
 1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 6)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 PRODUCT TESTING REPORTS HAVE BEEN SUBMIT
 TED INDICATING LARGE MISSLE IMPACT AND
 OTHERS WITH NO MISSLE IMPACT RATING INDI
 CATING THE USE OF STORM SHUTTERS.STORM
 PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 7)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE. A SAMPLE ATTACHED.
  
 8) SHEET A3 GUARDRAILS 1015.2 EXTERIOR
 GUARDRAILS TO BE A MINIMUM OF 42" TALL.
  
 9)2305.2.2 FLOOR/CEILING ASSEMBLIES
 SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/
 ING ASSEMBLIES SEPERATING USEABLE SPACE
 INTO 2 OR MORE APPROXIMATE AREAS WITH NO
 AREA GREATER THAN 500 SQ FT. DRAFTSTOP-
 PING SHALL BE PROVIDED PARALLEL TO THE
 MAIN FRAMING MEMBERS.
  
 10)FL BLD CODE 2309.6 ATTIC ACCESS, PRO-
 VIDE ATTIC ACCESS 20"X36". MISSING ON
 THE SECOND FLOOR, NOR OVER THE GARAGE.
  
 11)FL BLD CODE 2405.2 HAZARDOUS LOCATION
 PROVIDE SAFETY GLASS FOR THIS LOCATION:
 MASTERBATH AND ALL SHOWERS WITH A WINDOW
 WITHIN 36" OF THE SHOWER STALL.
  
 12)2504.2.2 INSTALLATION OF EXTERIOR
 LATHING AND FRAMING SHALL COMPLY WITH
 ASTM C-1063. SOFFITS HIRIB LATH TO BE
 NAILED TO HORIZNTAL FRAMING MEMBERS WITH
 1 3/4" PENETRATION OF WOOD FRAMING
 MEMBER AT 4" O.C.
  
 13) GAS BARBECUES: 2808 FACTORY BUILT
 BARBECUES SHALL BE OF AN APPROVED TYPE
 AND SHALL BE INSTALLED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTRUCTIONS.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 TEL: (561)805-6715 DIRECT LINE
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2004-05-11 Cont ID  
Sent By dpalmer Date 2004-05-11 Time 12:56 Rev Time 0.50
Received By dpalmer Date 2004-05-11 Time 12:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2004-04-27 Cont ID  
Sent By dpalmer Date 2004-04-27 Time 18:12 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2004-04-27 00:00:00NO REVIEW DONE, 4X FEE HAS BEEN REMOVED
 DUE TO REPEATED COMMENT WERE FOR FS/FAC
 PER BLDG OFFICAL.ALL INFORMATION FOR
 FS'S AND FAC IS STILL REQ'D BY LAW.
 PLANS ARE STILL REQ'D TO MEET CODE
 COMPLIANCE FOR ELECTRICAL INSTALLATION
 AND PLANS.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2004-04-17 Cont ID  
Sent By dpalmer Date 2004-04-17 Time 18:10 Rev Time 0.75
Received By dpalmer Date 2004-04-17 Time 18:10 Sent To P
Notes
2004-04-17 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SEE SOMES NOTES FROM TWO
 PREVIOUS REVIEWS.
 A NOTICE WAS GIVEN PER FS 553.80(2)(B)
 FOR ANY OF THE SAME COMMETS 3 OR MORE
 TIMES, A 4X FEE SHALL BE ACCESSED.
 PLEASE SEE BZ#240060 ATTACHED. ARCH
 OF RECORD PER FS IS RESPONSIBLE FOR
 THE FEE. $4,380.00
 PLEASE SEE THE FOLLOWING COMMENTS FOR
 CORRECTIONS TO BE MADE TO PLANS FOR
 CODE COMPLIANCE AND CORRECTIONS REQ'D
 UNDER FS 481.219,481.221/ FAC 61G1-16.00
 -4.
  
 2)NOTE: PLEASE HAVE PLANS REPRINTED
 WITH ALL REVISIONS. PLANS ARE TO BE
 CLEAR AND VISABLE WITH ALL CHANGES.
 HAND WRITTEN/PENCIL/PEN CHANGES ON
 PLANS ARE NOT PERMITTED.
 PLANS ARE COPIES OF ORIG SIGNED AND
 SEALED PLANS WITH NEW SEAL OVER THEM?
 THIS IS A DIRECT VIOLATION OF FS.481.221
 ETC.
 PLEASE ALSO SEE FS 481.219, A CERTIFI-
 -CATE OF AUTHORIZATION # IS REQ'D FOR
 TITLE BLOCK SHOWN.
 PLEASE NOTE: IF CORRECTIONS ARE NOT
 MADE , AN ADDTIONAL 4X FEE WILL BE ADDED
 AND PLANS WILL BE TURNED INTO THE STATE
 DPBR FOR REVIEW.
  
 3)NOTE: PLEASE SEE 210.52C2 FOR REQ'D
 RECEPT FOR ISLAND. PLEASE SEE THEY ARE
 DRAWN IN ON SIGNED AND SEALED PLANS.
 NOT PERMITTED.
  
 4)NOTE: PLEASE CORRELATE RISER AND PANEL
 SCHEDULE. PANEL "B" HAS A BRKR FEED TO
 NEW POOL PANEL, YET RISER NOTES NEW
 FUSE PNL FOR POOL?? PLEASE CLARIFY.
  
 5)NOTE: PLEASE SEE 250.66 FOR SIZING
 OF GROUNDING ELECTRODE. THIS IS SHOWN
 AS A 400A SERVICE. 310.15B6, PLACES
 MIN SEC'S AS 400MCM, 400MCM ON TABLE
 250.66, INDICATES A 1/0. PLEASE ADJUST
 230.42B
 6)NOTE: PLEASE ALSO INCLUDE FOOTER STEEL
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM AS REQ'D PER 250.50
 FOOTER STEEL IS NOT SHOWN ON RISER??
  
 7)NOTE: PLEASE SEE 220.3B4 FOR LOADS
 TO BE FIGURED FOR RECESSED LTS.
 PLEASE RE-CONFIGURE AND ADJUST LOAD
 CALCULATIONS.
  
 8)NOTE: PLEASE SEE 210.12 FOR REQ'D
 ARC FAULT PROTECTION, THIS SHOULD BE
 NOTED, AND/OR LISTED ON PANEL SCHEDULE.
  
 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
  
 10)NOTE: PLEASE SEE 250.122 FOR SIZING
 OF EQUIPMENT GROUNDING CONDUCTOR FROM
 PANEL "B" TO POOL PANEL WITH A 80A OCP
 FEED. #10 IS NOT PERMITTED.
  
 11)NOTE: PLEASE SEE 220 FOR LOADING
 OF 80A BRKR FOR POOL PANEL. AS SHOWN
 LOAD IS EXCEEDING 80% RATING OF BRKR.??
 230.4
 PLEASE SEE LOAD CALCS IN 220
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-03-12 Cont ID  
Sent By csiegber Date 2004-04-08 Time 14:31 Rev Time 0.75
Received By btrobaug Date 2004-03-12 Time 11:57 Sent To P
Notes
2004-03-12 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SEE NOTE #2 FROM PREVIOUS REVIEW.
 " ANY CHANGES MADE TO PLANS THAT WERE
 DRAWN BY A DESIGN PROFESSIONAL MUST BE
 MADE BY THE DESIGNER OF RECORD PER
 61G1-16.003 FAC."
  
 2} NOTE #6 FROM PREVIOUS REVIEW: SUBMIT
 A PANEL SCHEDULE FOR "C". NOW BEING
 CALLED "POOL PANEL".
  
 3} PLEASE NOTE THAT THE 20K CALCULATION
 SHOWN ON PANEL "B" FOR THE POOL PANEL
 EXCEEDS 80 AMPS, WHICH IS SHOWN AS THE
 MAIN FOR THAT PANEL.
  
 4} LIST THE OCP RATINGS FOR ALL
 CIRCUITS LISTED ON PANEL SCHEDULES.
  
 5} INDICATE COMPLIANCE WITH 210.8(A)(6)
 FOR THE ISLAND ON THE PLAN.(KITCHEN).
  
 PLEASE NOTE THAT ATTACHED IS A COPY OF
 FL. 553.80(2)(B), BE SURE THAT THE
 ARCHITECT IS MADE AWARE OF THIS
 ATTACHMENT AS THIS FEE IS HIS
 RESPONSIBILITY, AND IS MANDATORY BY
 STATUTE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-01-09 Cont ID  
Sent By csiegber Date 2004-03-08 Time 12:13 Rev Time 0.75
Received By btrobaug Date 2004-01-09 Time 08:21 Sent To  
Notes
2004-01-09 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE NOTE, ALL PLANS DRAWN
 BY AN ARCHITECT/ENGINEER CONTAIN-
 -ING A TITLE BLOCK: MUST BE SIGNED,
 DATED AND SEALD BY THAT ARCH/ENG.
 PER FS 481.221 471.025.HAND DRAWN
 CHANGES TO PLANS FOR PUBLIC RECORD ARE
 NOT ACCEPTABLE.
  
 2} ANY CHANGES MADE TO PLANS THAT WERE
 DRAWN BY A DESIGN PROFESSIONAL MUST BE
 MADE BY THE DESIGNER OF RECORD PER
 61GI-16.003 FAC.
  
 3} PANEL "A" DOES NOT LIST THE OCP FOR
 PANEL "C" AND THE LOAD CALC REMAINED
 THE .AME.PLEASE CORRECT.
  
 4} PLEASE NOTE THAT RECESSED LUMINAIRS
 ARE TO BE CALCULATED PER 220.3(B)(4).
  
 5} RECOMPUTE THE LOAD CALCULATIONS TO
 REFLECT ALL REVISED LOADS.
  
 6} SUBMIT A PANEL SCHEDULE FOR "C".
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-06-23 Cont ID  
Sent By csiegber Date 2004-01-05 Time 11:52 Rev Time 0.50
Received By btrobaug Date 2003-06-23 Time 13:45 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-06-04 Cont ID  
Sent By shernand Date 2003-06-20 Time 10:12 Rev Time 0.50
Received By btrobaug Date 2003-06-04 Time 12:42 Sent To P
Notes
2003-06-04 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE: PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
 ONLY ONE SET IS SEALED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-28 Cont ID  
Sent By shernand Date 2003-06-03 Time 15:03 Rev Time 1.00
Received By btrobaug Date 2003-04-24 Time 17:41 Sent To M
Notes
2003-04-28 00:00:00DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 TO THE PLANS FOR CODE COMPLIANCE AND RES
 UBMIT FOR REVIEW.
  
 1} THE GEC IS INCORRECT PER 250-66,#2CU
 MINIMUM.
  
 2} THE 1/0 EQUIPMENT GROUND FROM THE
 METER TO THE DISCONNECTS CREATES A
 PARALLEL PATH TO GROUND WITH THE
 NEUTRAL AND MUST NOT BE INSTALLED
 BEFORE THE FIRST MEANS OF DISCONNECT.
  
 3} THE OCP FOR AIR HANDLERS #1 & #3 ARE
 INCORRECT.
  
 4} THE CONDUCTORS AND OCP ARE INCORRECT
 FOR AHU #2.
  
 5} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S), PER 210-11-C-3
 MUST BE 20A AND #12AWG, ON THE PANEL
 SCHEDULE.
  
 6} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 7} ALL LIGHTING FOR CLOSETS MUST COMPLY
 WITH 410-8, NOTE LIGHTS DRAWN OVER
 SHELVING.
  
 8} ALL ELECTRICAL PANELS,DISCONNECT AND
 EQUIPMENT MUST COMPLY WITH 110-26.
  
 9} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 10} PLEASE IDENTIFY ALL AREAS AND ROOMS
 ON THE ELECTRICAL SHEETS.
  
 THE ARCHITECTURAL & ELECTRICAL DRAWINGS
 DO NOT CORRESPOND IN SOME AREAS. NOTE
 THE BATH/HALLWAY WALL OFF BED ROOM #2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-05-11 Cont ID  
Sent By csiegber Date 2004-05-11 Time 10:02 Rev Time 0.00
Received By csiegber Date 2004-05-11 Time 10:02 Sent To P
Notes
2004-05-11 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-04-08 Cont ID  
Sent By csiegber Date 2004-04-08 Time 14:31 Rev Time 0.00
Received By csiegber Date 2004-04-08 Time 14:31 Sent To E
Notes
2004-04-08 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-03-08 Cont ID  
Sent By csiegber Date 2004-03-08 Time 12:13 Rev Time 0.00
Received By csiegber Date 2004-03-08 Time 12:13 Sent To E
Notes
2004-03-08 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-05 Cont ID  
Sent By csiegber Date 2004-01-05 Time 11:52 Rev Time 0.00
Received By csiegber Date 2004-01-05 Time 11:52 Sent To E
Notes
2004-01-05 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-29 Cont ID  
Sent By csiegber Date 2003-12-29 Time 13:44 Rev Time 0.00
Received By csiegber Date 2003-12-29 Time 13:44 Sent To P
Notes
2003-12-29 00:00:00TO KS BOX.REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-20 Cont ID  
Sent By shernand Date 2003-06-20 Time 10:12 Rev Time 0.00
Received By shernand Date 2003-06-20 Time 10:12 Sent To E
Notes
2003-06-20 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-03 Cont ID  
Sent By shernand Date 2003-06-03 Time 15:03 Rev Time 0.00
Received By shernand Date 2003-06-03 Time 15:03 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-18 Cont ID  
Sent By shernand Date 2003-04-18 Time 16:12 Rev Time 0.00
Received By shernand Date 2003-04-18 Time 16:12 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-12 Cont ID  
Sent By kstevens Date 2003-06-24 Time 07:52 Rev Time 0.15
Received By pkrauss Date 2003-05-12 Time 08:31 Sent To B
Notes
2003-05-12 00:00:00MECH PERMIT 03041467

Review Stop P PLUMBING
Rev No 8 Status P Date 2004-05-11 Cont ID  
Sent By kstevens Date 2004-05-11 Time 18:07 Rev Time 0.50
Received By kstevens Date 2004-05-11 Time 18:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 7 Status F Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-05-11 Time 10:02 Rev Time 0.50
Received By kstevens Date 2004-04-20 Time 07:25 Sent To B
Notes
2004-04-20 00:00:00REVISION DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) CHANGES TO A SIGNED AND SEALED SET OF
 PLAN SHALL NOT BE HAND DRAWN. PLEASE
 SUBMIT REDRAWN PLANS WITH OUT WHITE-OUT
 AND HAND DRAWN CHANGES.
 2) SEE ELECTRICAL COMMENTS CONCERNING
 FAC 61G1-16.004 & FS 481.219.
 3) ALL PLANS SHALL BE OF SUFFICIENT
 CLARITY PER SECTION 104.2.1 AND SECTION
 104.2.1.3 CHAPTER 1 0F THE FBC-2001.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 6 Status F Date 2004-03-29 Cont ID  
Sent By dpalmer Date 2004-04-17 Time 18:23 Rev Time 0.50
Received By kstevens Date 2004-03-17 Time 18:16 Sent To  
Notes
2004-03-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FLOOR PLAN REQUIRED TO SHOW CHANGES
 TO SANITARY RISER DIAGRAM. SUBMIT AN
 ARCHITECTURAL REVISION. SEC 104.2.1
 2) TITLE BLOCK REQUIRED ON SIGNED SEALED
 SET OF REVISIONS FOR RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2004-01-21 Cont ID  
Sent By btrobaug Date 2004-03-12 Time 13:03 Rev Time 0.50
Received By kstevens Date 2004-01-10 Time 14:22 Sent To  
Notes
2004-01-21 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) ANY REVISION TO A SANITARY RISER DIA-
 GRAM SHALL BE CHANGED ON THE FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-06-27 Cont ID  
Sent By csiegber Date 2003-12-29 Time 13:45 Rev Time 1.00
Received By kstevens Date 2003-06-27 Time 16:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-06-24 Cont ID  
Sent By kstevens Date 2003-06-24 Time 07:51 Rev Time 1.25
Received By kstevens Date 2003-06-23 Time 18:47 Sent To B
Notes
2003-06-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS, CHAPTER
 1, ADMIN CODE
  
 1) SHT E2 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN NOR DOES IT
 MEET CODE REQUIREMENTS. THE RISER DIA-
 GRAM SHALL BE DRAWN AS IT WILL BE IN-
 STALLED. MASTER BATH SHALL BE UPSTREAM
 OF POWDER ROOM, BATH 2 SHALL BE UPSTREAM
 OF THE LAUNDRY ROOM. 104.2.1
 ALL TUB AND SHOWER TRAPS SHALL BE TAKEN
 OFF THE BRANCH LINES ON THE HORIZONTAL
 AS TO NOT BE AN "S" TRAP. BATH 2 TUB NOT
 VENTED. WASH MACHINE IS NOT VENTED AND
 REQUIRES A STANDPIPE. W/C AND SHOWER IN
 BATH 3 NOT VENTED. BBQ SINK SHALL NOT
 DRAIN INTO THE HORIZONTAL WET VENT OF
 THE CABANA BATH.
 SEE SECTIONS 909.1 - 1002.3(5) - 901.2.1
 802.4
 2) SEE ATTACHED SHEET CONCERNING FLORIDA
 STATUTE 553.80(2)(B)
 3) FLA STATUTE 61G1-16.003 THE PERSONAL
 SEAL, SIGNATURE, AND DATE ARE REQUIRED
 ON ALL DOCUMENTS TO BE FILED FOR PUBLIC
 RECORD PREPARED BY AN ARCHITECT. THE
 DATE IS MISSING FROM ALL SHEETS. ALSO
 ALL CHANGES TO A SIGNED AND SEALED SET
 OF DRAWINGS SHALL BE SIGNED AND DATED BY
 THE ARCHITECT OF RECORD.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-06-10 Cont ID  
Sent By btrobaug Date 2003-06-23 Time 14:13 Rev Time 0.75
Received By kstevens Date 2003-06-10 Time 11:10 Sent To B
Notes
2003-06-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT E2 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS. SOME FIXTURES
 ARE NOT SHOWN ON RISER, SOME FIXTURES
 ARE NOT VENTED, AND THE LAYOUT DOES NOT
 REFLECT THE FLOOR PLAN.
 2) PLEASE SEE ATTACHED SHEET AS AN EXAM-
 PLE OF A RISER DIAGRAM THAT MEETS CODE
 REQUIREMENTS AND REFLECTS THE FLOOR PLAN
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-23 Cont ID  
Sent By btrobaug Date 2003-06-04 Time 14:27 Rev Time 0.50
Received By jleech Date 2003-04-23 Time 19:14 Sent To E
Notes
2003-04-23 00:00:00DENIED;
 RISER DIAGRAM DOES NOT MATCH FLOOR PLAN.
 FIRST FLOOR; MISSING FIXTURES, 2 TOILETS
 2 LAVS, 1 TUB, AND WASHING MACHINE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-24 Cont ID  
Sent By shernand Date 2003-04-18 Time 16:12 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***