| 2003-05-18 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03041464 |
| | ADD: 2330 TECUMSEH DRIVE |
| | CONT: COLUMBIA BUILDING GROUP |
| | TEL: (561)719-5333 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1) SHEET ST DETAIL 4 TYPICAL WINDOW DE- |
| | TAIL INDICATES THE USE OF HUGHES PRO- |
| | DUCTS, OUT OF BUSINESS FOR 2 YEARS, |
| | MERGED WITH USP, PROVIDE CURRENT PRODUCT |
| | INFORMATION. USE 2003 CATOLOG WITH |
| | REDUCED VALUES. |
| | |
| | 2) THERE SEEMS TO BE NO TRUSS ANCHOR |
| | SCEDULE FOUND IN THE PLAN. |
| | 1707.3.1 JOIST HANGERS, FRAMING |
| | ANCHORS & SIMILAR DEVICES SHALL BE TEST- |
| | ED IN ACCORDANCE W/ ASTM D 1761 & BE |
| | LABELED AND LISTED FOR THEIR LOAD CARRY- |
| | ING CAPACITY. |
| | |
| | 3)1609.4.3 LOAD REDUCTION. |
| | WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| | MORE LOADS IN COMBINATION WITH DEAD LOAD |
| | ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| | 1609.4.1 OR 1609.4.2, THE COMBINED |
| | EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| | PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| | LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| | FROM THE LOAD COMBINATION OF THE DEAD |
| | LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| | EFFECTS. INCREAS IN ALLOWABLE STRESS SPE |
| | CIFIED IN THE MATERIALS SECTIONS OF THIS |
| | CODE OR A REFRENCED STANDARD SHALL NOT |
| | BE USED WITH THESE LOAD COMBINATIONS |
| | EXCEPT THAT A DURATION OF LOAD INCREASE |
| | SHALL BE PERMITTED IN ACCORDANCE WITH |
| | CHAPTER 23. |
| | |
| | 4) SHEET ST INDICATES TAPPERED BUCK, |
| | 1707.4.4.2 TAPERED BUCKS: |
| | SHALL EXTEND BEYOND THE INTERIOR FACE |
| | OF THE WINDOW OR DOOR FRAME SUCH THAT |
| | FULL SUPPORT OF THE FRAME IS SUPPORTED. |
| | |
| | 5) MISSING PRODUCT TESTING REPORT FOR |
| | THE FRONT DOORS, |
| | 1707.4.3 EACH EXTERIOR DOOR |
| | ASSEMBLY NOT COVERED BY 1707.4.2 |
| | (GLAZED DOORS) SHALL BE LISTED AND TEST- |
| | ED FOR A PERIOD EQUAL TO THE QUANITY |
| | 3600/ V WHERE THE TIME PERIOD IS IN |
| | SECTIONS AND V IS IN MILES PER HR TAKEN |
| | FROM FIGURE 1606. THE TIME PERIOD SHALL |
| | ALSO INCLUDE A 10 SECOND PERIOD AT A |
| | LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| | PRESSURE. DADE COUNTY & SBCCI REPORTS |
| | ARE ACCEPTED. |
| | |
| | 6)1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | |
| | 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST. |
| | |
| | PRODUCT TESTING REPORTS HAVE BEEN SUBMIT |
| | TED INDICATING LARGE MISSLE IMPACT AND |
| | OTHERS WITH NO MISSLE IMPACT RATING INDI |
| | CATING THE USE OF STORM SHUTTERS.STORM |
| | PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4. |
| | |
| | 7)FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. A SAMPLE ATTACHED. |
| | |
| | 8) SHEET A3 GUARDRAILS 1015.2 EXTERIOR |
| | GUARDRAILS TO BE A MINIMUM OF 42" TALL. |
| | |
| | 9)2305.2.2 FLOOR/CEILING ASSEMBLIES |
| | SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/ |
| | ING ASSEMBLIES SEPERATING USEABLE SPACE |
| | INTO 2 OR MORE APPROXIMATE AREAS WITH NO |
| | AREA GREATER THAN 500 SQ FT. DRAFTSTOP- |
| | PING SHALL BE PROVIDED PARALLEL TO THE |
| | MAIN FRAMING MEMBERS. |
| | |
| | 10)FL BLD CODE 2309.6 ATTIC ACCESS, PRO- |
| | VIDE ATTIC ACCESS 20"X36". MISSING ON |
| | THE SECOND FLOOR, NOR OVER THE GARAGE. |
| | |
| | 11)FL BLD CODE 2405.2 HAZARDOUS LOCATION |
| | PROVIDE SAFETY GLASS FOR THIS LOCATION: |
| | MASTERBATH AND ALL SHOWERS WITH A WINDOW |
| | WITHIN 36" OF THE SHOWER STALL. |
| | |
| | 12)2504.2.2 INSTALLATION OF EXTERIOR |
| | LATHING AND FRAMING SHALL COMPLY WITH |
| | ASTM C-1063. SOFFITS HIRIB LATH TO BE |
| | NAILED TO HORIZNTAL FRAMING MEMBERS WITH |
| | 1 3/4" PENETRATION OF WOOD FRAMING |
| | MEMBER AT 4" O.C. |
| | |
| | 13) GAS BARBECUES: 2808 FACTORY BUILT |
| | BARBECUES SHALL BE OF AN APPROVED TYPE |
| | AND SHALL BE INSTALLED IN ACCORDANCE |
| | WITH THE MANUFACTURER'S INSTRUCTIONS. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)659-8096 X 8412 |
| | TEL: (561)805-6715 DIRECT LINE |
| | FAX: (561)659-8026 |