Plan Review Details - Permit 03041303
Plan Review Stops For Permit 03041303
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-05-29 Cont ID  
Sent By kstevens Date 2003-05-29 Time 12:40 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-16 Cont ID  
Sent By dpalmer Date 2003-05-16 Time 16:36 Rev Time 0.25
Received By dpalmer Date 2003-05-16 Time 16:36 Sent To P
Notes
2003-05-16 00:00:00*********NOTE *************
 VERIFY CONDUCTORS/ CONDUIT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-08 Cont ID  
Sent By shernand Date 2003-05-14 Time 15:17 Rev Time 0.25
Received By dpalmer Date 2003-05-08 Time 06:48 Sent To P
Notes
2003-05-08 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 ON EXISTING SERVICE AND INCLUDE ALL NEW
 LOADS.HEAT PUMP ETC.
  
 2)NOTE: PLEASE SEE WIRING DIAGRAM, DOES
 NOT INCLUDE HEAT PUMP/WIRING ETC.
 PLEASE SHOW.
  
 PLEASE NOTE, ALL PLANS DONE BY AN
 ENGINEER MUST CONTAIN ORIGINAL SIGNATURE
 (NOT COPIES) . FS/FAC 417.025/ 61G15-23
 -.002. SUBMITTALS ARE COPIES WITH A
 RAISED SEAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-05-28 Cont ID  
Sent By shernand Date 2003-05-28 Time 08:39 Rev Time 0.00
Received By shernand Date 2003-05-28 Time 08:39 Sent To P
Notes
2003-05-28 00:00:00KSTEVENS DESK
 '

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-14 Time 15:17 Rev Time 0.00
Received By shernand Date 2003-05-14 Time 15:17 Sent To E
Notes
2003-05-14 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 15:46 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 15:46 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-24 Cont ID  
Sent By shernand Date 2003-04-24 Time 10:54 Rev Time 0.00
Received By shernand Date 2003-04-24 Time 10:54 Sent To Z
Notes
2003-04-24 00:00:00SUBMITTAL TO ORIGINAL APPLICATION.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-18 Cont ID  
Sent By shernand Date 2003-04-18 Time 15:30 Rev Time 0.00
Received By shernand Date 2003-04-18 Time 15:30 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-05-29 Cont ID  
Sent By kstevens Date 2003-05-29 Time 12:40 Rev Time 0.75
Received By kstevens Date 2003-05-29 Time 12:40 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-05-23 Cont ID  
Sent By shernand Date 2003-05-28 Time 08:39 Rev Time 0.25
Received By kstevens Date 2003-05-23 Time 09:28 Sent To  
Notes
2003-05-23 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FLA STATUTES
  
 A) PREVIOUS REVIEW COMMENTS NOT ADDRESS-
 ED.
 1) PIPING SCHEMATIC AND POOL LAYOUT DO
 NOT MATCH. NO VACUUM LINE SHOWN ON
 PIPING SCHEMATIC.
 2) 61G15-23.002(1) THE DATE THAT THE
 PLAN IS SIGNED AND SEALED SHALL BE
 ENTERED ON PLANS.
 3) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-10 Cont ID  
Sent By dpalmer Date 2003-05-16 Time 16:44 Rev Time 0.50
Received By kstevens Date 2003-05-10 Time 09:36 Sent To B
Notes
2003-05-10 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) PIPING SCHEMATIC AND POOL LAYOUT DO
 NOT MATCH. NO VACUUM LINE SHOWN ON PIP-
 ING SCHEMATIC.
 2) 61G15-23.002 A PROFESSIONAL ENGINEER
 SHALL SIGN HIS NAME ON THE SEAL. ALSO
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED SHALL BE ENTERED ON THE PLANS.
 THE SIGNATURE ON THE ADDITIONAL PAGE IS
 A COPY AND NO DATE ON SIGNATURE OF PLANS
 3) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-24 Time 10:58 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***