| 2003-05-16 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT A-6 DETAILS A(B), 3(B), & 6(B), |
| | CONTROLS FOR FLUSH VALVES SHALL BE MOUN- |
| | TED ON THE WIDE SIDE OF TOILET AREAS, AT |
| | A MAXIMUM OF 44" ABOVE FLOOR. 11-4.16.5 |
| | W/C TO BE 18" TO CENTER OF FIXTURE OFF |
| | WALL. |
| | 2) SHT P-3 WATER HEATER DETAIL, THERMAL |
| | EXPANSION CONTROL REQUIRED. SEC 607.3.2 |
| | 3) SHTS P-2/P-4(SANT RISER DIAGRAM), FDA |
| | CONDENSATE SHALL NOT DRAIN INTO THE SANT |
| | SYSTEM. CITY CODE 90-125(B)(5). |
| | 4) SHT P-4 SANT. RISER DIAGRAM DOES NOT |
| | MEET CODE REQUIREMENTS. WATER CLOSETS |
| | SHALL NOT BE DOUBLE TRAPPED. W/C HAS AN |
| | INTEGRAL TRAP IN FIXTURE. - URNALS ARE |
| | NOT VENTED. - LAVS IN WOMENS TOILET ROOM |
| | AND BOTH UNISEX TOILET ROOM ARE NOT VEN- |
| | TED. - LAB SINK IS NOT VENTED. - DRINK- |
| | ING FOUNTAINS ARE NOT VENTED. - VENTS |
| | ARE SHOW IN THE MIDDLE OF THE ROOMS IN |
| | BOTH THE MENS LOCKER ROOM AND ONE OF THE |
| | UNISEX TOILET ROOMS. |
| | 5) SHT P-4 WATER RISER DIAGRAM, SHUT OFF |
| | VALVES ARE REQUIRED AT EACH HOSE BIBB. |
| | SEC 606.2(2). |
| | 6) SHT P-4 WATER RISER DIAGRAM, WATER |
| | HAMMER ARRESTORS REQUIRED BY 604.9 SHALL |
| | BE LOCATED NEAR THE FIXTURE IN AN "EFF- |
| | ECTIVE RANGE"NOT IN THE CEILING AS |
| | SHOWN. PDI-WH 201 & MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | --------WHEN RESUBMITTING PLANS--------- |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |