Plan Review Details - Permit 03041300
Plan Review Stops For Permit 03041300
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-22 Cont ID  
Sent By hpiskura Date 2003-05-05 Time 12:49 Rev Time 0.00
Received By hpiskura Date 2003-05-02 Time 15:16 Sent To  
Notes
2003-05-05 00:00:00PLAN REVIEW ONLY NOT A PERMIT
 APPLICATION.
  
 THE PROPOSED BUILDING AREA 9.9 KSF
 EXCEEDS THE ALLOWBLE AREA IN FBC TABLE
 500 FOR TYPE IV CONSTRUCTION, 5.0 KSF.
 THE MINIMUM CONSTRUCTION TYPE IS TYPE
 II FS.
  
 THE MEZZANINE AS SHOWN DOES NOT COMPLY
 WITH THE EGRESS REQUIREMENTS OF FBC
 1005.7 FOR A SINGLE MEANS OF EGRESS IN
 AN GROUP H OCCUPANCY.
  
 AT TIME OF PERMIT APPLICATION AN
 ESTIMATE OF THE TYPE AND QUANTITIES OF
 MATERIALS STORED IN THE BUILDING WILL
 BE NECESSARY.SEE FBC 308.2.3 AND FBC
 308.2.4.
  
 THE PERMIT PLANS MUST SHOW THE SPILL
 CONTROL AND CONTAINMENT METHODS IN
 ACCORDANCE WITH FBC 407.2.3. AND THE
 STANDBY POWERAS PROVIDED FOR IN FBC
 407.2.9.4.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-05 Cont ID  
Sent By dpalmer Date 2003-05-05 Time 16:27 Rev Time 1.50
Received By dpalmer Date 2003-05-05 Time 16:27 Sent To  
Notes
2003-05-05 00:00:00******** UNSAT ************
  
 1)NOTE: PLEASE CLARIFY/ SHOW ANY LOCAT-
 -IONS REQ`D UNDER NEC ART 500?
  
 2)NOTE: PLANS ARE REQ`D TO BE SIGNED
 DATED AND SEALED. PE R FS/ FAC,471.025,
 61G15-23.002, FBC 104.4.1.3 ETC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2003-09-15 Cont ID  
Sent By mamini Date 2003-09-15 Time 16:29 Rev Time 0.50
Received By mamini Date 2003-09-15 Time 16:29 Sent To  
Notes
2003-09-15 00:00:00PASSED:
 1. SEE PERMIT # 03090886 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-04-21 Cont ID  
Sent By mamini Date 2003-04-21 Time 09:25 Rev Time 1.00
Received By mamini Date 2003-04-21 Time 09:25 Sent To  
Notes
2003-04-21 00:00:00FAILED:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND SITE WORK IS REQUIRED.
 2. A BACKFLOW PREVENTER FOR DOMESTIC
 WATER FOR THIS FACILITY IS REQUIRED, A
 DDCV FOR THE PROPOSED PRIVATE FIRE HYD
 IS REQUIRED UNLESS IT TIES TO THE
 SYSTEM WITH EXSITING DDCV.
 3. PLEASE CONTACT, RODNEY COMPO @
 837-4051 EXT. 4074 FOR GREASE/OIL /WATER
 SEPARATOR REQUIREMENT FOR THE PROPOSED
 FACILITIY.
 4. ALL PARKING STALLS MUST PAINTED WITH
 DOUBLE 4" PAINT PER CITY WPB REQUIREMENT
 5. PLEASE VERIFY THE SHEET REFERENCES
 FOR THE DETAILS.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-05-21 Cont ID  
Sent By nmccray Date 2003-05-21 Time 14:38 Rev Time 0.00
Received By nmccray Date 2003-05-21 Time 14:37 Sent To  
Notes
2003-05-21 00:00:001) PLEASE REF CH 40 OF NFPA 101 LIFE
 SAFETY CODE 2000 EDITION.
  
 2) WHAT WILL BE STORED AND HOW MUCH IN
 THIS BUILDING.
  
 3) SEPARATE PLAN AND PERMIT WILL BE
 REQUIRED FOR FIRE ALARM AND FIRE
 SPRINKLER SYSTEM.
  
 4) FIRE HYDRANT MUST BE WITHIN 150 FEET
 OF THE FIRE DEPT. CONNECTION.
  
 PLEASE NOTE COMMENTS FOR BUILDING AND
 MECHANICAL.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-17 Cont ID  
Sent By sgraham Date 2003-05-09 Time 14:13 Rev Time 0.00
Received By shernand Date 2003-04-17 Time 12:51 Sent To  
Notes
2003-04-17 00:00:00COMM BOARD #53

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-05-12 Cont ID  
Sent By pkrauss Date 2003-05-12 Time 09:32 Rev Time 2.00
Received By pkrauss Date 2003-05-12 Time 09:13 Sent To  
Notes
2003-05-12 00:00:00DENIED:
  
 1.PLAN SHEET AC-1 SEEMS TO INDICATE
 THE CONDENSATE TERMINATING INTO THE
 FLOOR DRAIN OF THE MECHANICAL ROOM.
 AS PER CITY CODE SEC 90-125 -
 PROHIBITIONS & LIMITATIONS OF DISCHARGE
 SUB-SECTION (B)(5).CONDENSATE SHALL
 NOT TERMINATE INTO SANITARY.
  
 2.MECHANICAL PLANS DO NOT INDICATE ANY
 OF THE EXHAUST FANS BEING TIED TO
 EMERGENCY POWER.PLEASE CLARIFY.
  
 3.2001 FBC(M) 510.8, DUCTS UTILIZED TO
 CONVEY HAZARDOUS EXHAUST SHALL BE
 CONSTRUCTED OF G90 GALVANIZED, WITH A
 MINIMUM NOMINAL THICKNESS AS SPECIFIED
 IN TABLE 510.8.
  
 SEE ALSO COMMENTS FOR BUILDING AND FIRE
 DEPARTMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-16 Cont ID  
Sent By kstevens Date 2003-05-16 Time 11:08 Rev Time 1.50
Received By kstevens Date 2003-05-16 Time 11:05 Sent To  
Notes
2003-05-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-6 DETAILS A(B), 3(B), & 6(B),
 CONTROLS FOR FLUSH VALVES SHALL BE MOUN-
 TED ON THE WIDE SIDE OF TOILET AREAS, AT
 A MAXIMUM OF 44" ABOVE FLOOR. 11-4.16.5
 W/C TO BE 18" TO CENTER OF FIXTURE OFF
 WALL.
 2) SHT P-3 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL REQUIRED. SEC 607.3.2
 3) SHTS P-2/P-4(SANT RISER DIAGRAM), FDA
 CONDENSATE SHALL NOT DRAIN INTO THE SANT
 SYSTEM. CITY CODE 90-125(B)(5).
 4) SHT P-4 SANT. RISER DIAGRAM DOES NOT
 MEET CODE REQUIREMENTS. WATER CLOSETS
 SHALL NOT BE DOUBLE TRAPPED. W/C HAS AN
 INTEGRAL TRAP IN FIXTURE. - URNALS ARE
 NOT VENTED. - LAVS IN WOMENS TOILET ROOM
 AND BOTH UNISEX TOILET ROOM ARE NOT VEN-
 TED. - LAB SINK IS NOT VENTED. - DRINK-
 ING FOUNTAINS ARE NOT VENTED. - VENTS
 ARE SHOW IN THE MIDDLE OF THE ROOMS IN
 BOTH THE MENS LOCKER ROOM AND ONE OF THE
 UNISEX TOILET ROOMS.
 5) SHT P-4 WATER RISER DIAGRAM, SHUT OFF
 VALVES ARE REQUIRED AT EACH HOSE BIBB.
 SEC 606.2(2).
 6) SHT P-4 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS REQUIRED BY 604.9 SHALL
 BE LOCATED NEAR THE FIXTURE IN AN "EFF-
 ECTIVE RANGE"NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 & MANUF. INSTALLATION
 INSTRUCTIONS.
  
 --------WHEN RESUBMITTING PLANS---------
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-09 Cont ID  
Sent By sgraham Date 2003-05-09 Time 14:13 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***