Plan Review Details - Permit 03040756
Plan Review Stops For Permit 03040756
Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2004-05-17 Cont ID  
Sent By csiegber Date 2004-07-22 Time 09:28 Rev Time 0.50
Received By shill Date 2004-05-17 Time 13:53 Sent To  
Notes
2004-05-17 00:00:00TRUSS REPAIRS PREPARED BY JULIUS LEE PE
 DATED 5/3/4, SHEET 163
 DATED 5/6/4, SHEETS 36, 85, 50, 53,12,
 92, 75, 115
  
 RINKER BLOCK SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2004-05-14 Cont ID  
Sent By shill Date 2004-05-14 Time 16:59 Rev Time 1.00
Received By shill Date 2004-05-14 Time 16:59 Sent To  
Notes
2004-05-14 00:00:00TRUSS REPAIR SUBMITTALS PREPARED BY
 JULIUS LEE, PE DATED 4/20/4
  
 SHEETS 13 & 4

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-12 Time 14:22 Rev Time 1.00
Received By shill Date 2004-05-04 Time 13:28 Sent To  
Notes
2004-05-04 00:00:00TRUSS REPAIR DETAILS PREPARED BY
 JULIUS LEE, PE
  
 PAGES 59,90, 164, 99, 77, 50, 48, 22, 51
 , 133, 49, 45 45A, 26,21, 34, 116

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status F Date 2004-04-22 Cont ID  
Sent By csiegber Date 2004-04-28 Time 15:59 Rev Time 0.50
Received By shill Date 2004-04-21 Time 17:44 Sent To  
Notes
2004-04-21 00:00:00****CORRECTIONS****
 TRUSS REPAIR DETAILS PREPARED BY
 JULIUS LEE, PE
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PLEASE SUBMIT THE ORIGINAL SIGNED
 TRUSS REPAIR DETAILS.PHOTOCOPIES
 WERE PROVIDED.ORIGINAL SIGNATURE, NOT
 INITIALS, ARE REQUIRED PER BUILDING
 OFFICIAL AND FBPE.
  
 2.)PROVIDE INFORMATION REQUIRED TO
 BE ON EACH SHEET PER FAC61G15-23.002.
 (ADDRESS FOR ENGINEER).
  
 3.)PROVIDE A LEGIBLE SEAL.IT APPEARS
 THAT THESE SHEETS HAVE BEEN SEALED BUT
 THE SEAL IS ENTIRELY ILLEGIBLE.
  
 4.)THE REPAIR DETAILS REFER TO A
 DETAIL 4.WHERE IS THIS DETAIL, OR
 DOES THE 4 SIGNIFY SOMETHING ELSE?
  
 6.)PAGE 49 INDICATES THAT THE SAME
 REPAIR IS TO BE USED FOR C45, C45A.
 ARE THEY IDENTICAL (SAME DIMENSIONS, ETC
 )?
  
 CC:DON NEELY/HAROLD PISKURA

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2004-03-26 Cont ID  
Sent By csiegber Date 2004-04-20 Time 16:19 Rev Time 0.50
Received By shill Date 2004-03-26 Time 08:44 Sent To  
Notes
2004-03-26 00:00:00SHROING 5TH FLOOR INSPECTION LETTER
 PREPARED BY CALVIN FOONG, PE 3/25/4
 LETTER FROM BJK

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-03-22 Time 14:27 Rev Time 0.50
Received By shill Date 2004-03-22 Time 13:22 Sent To  
Notes
2004-03-22 00:00:00TRUSS DRAWINGS PREPARED BY JULIUS LEE,PE
 2/12/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2004-03-11 Cont ID  
Sent By csiegber Date 2004-03-22 Time 08:46 Rev Time 0.50
Received By shill Date 2004-03-11 Time 15:22 Sent To  
Notes
2004-03-11 00:00:00SHORING INSPECTION LETTER FOR 4TH FL
 RESHORE INSPECTION 3RD FLOOR PREPARED
 BY CALVIN FOONG, PE 3/10/04
 LETTER FROM BJ&K

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2004-02-27 Cont ID  
Sent By shill Date 2004-02-27 Time 12:21 Rev Time 0.50
Received By shill Date 2004-02-27 Time 12:20 Sent To  
Notes
2004-02-27 00:00:003RD FLOOR SHORING LETTER PREPARED BY
 CALVIN FOONG, PA 2/25/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2005-01-10 Cont ID  
Sent By csiegber Date 2004-02-25 Time 14:51 Rev Time 3.00
Received By shill Date 2004-02-21 Time 09:16 Sent To  
Notes
2005-01-10 00:00:00OKAY - BLOCK WORK 2 COAT (1/2" OK) AND
 NO VERTICAL STUCCO
2004-02-21 00:00:00****CORRECTIONS*****
  
 REVISION DATED 1/15/04 (REV #S 9-16)
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PLASTER WORK IS TO CONFORM TO
 ASTM C926, FBC2504.2 (STUCCO OVER BLOCK
 5/8", STUCCO OVER WIRE LATH IN VERTICAL
 APPLICATION, 7/8").
  
 2.)THE ENTRANCE SIGN ON SHEET SGA1.01
 WAS TO BE PERMITTED SEPARATELY AS PER
 ZONING.IT APPEARS THAT THIS WAS DONE
 ON PERMIT #03120101.SUBMIT THIS SHEET
 AS A REVISION TO THE SIGN PERMIT.
  
 3.)TITLE BLOCKS ARE TO CONTAIN
 INFORMATION REQUIRED BY FAC61G15-23.002
 AND FAC61G1-16.004.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2004-02-11 Cont ID  
Sent By shill Date 2004-02-11 Time 15:53 Rev Time 1.00
Received By shill Date 2004-02-11 Time 15:53 Sent To  
Notes
2004-02-11 00:00:00REVISED SHORING PREPARED BY CALVIN
 FOONG PE, INSPECTION LETTERS FROM
 CONTRACTOR, INSPECTOR AND FOONG
 PLAN DATED 2/10/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-02-09 Time 16:30 Rev Time 1.00
Received By shill Date 2004-02-09 Time 11:06 Sent To  
Notes
2004-02-09 00:00:00SHORING & RESHORING PREP BY CALVIN
 FOONG, PE DATED 2/4/04
  
 INCLUDES BUILDINGS 1 & 2, 580 & 540
 EXECUTIVE CENTER DRIVE

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2004-02-06 Cont ID  
Sent By shill Date 2004-02-06 Time 16:59 Rev Time 0.50
Received By shill Date 2004-02-06 Time 16:59 Sent To  
Notes
2004-02-06 00:00:00ELEVATION PREPARED BY RICHARD H. SMITH

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2004-01-30 Cont ID  
Sent By csiegber Date 2004-02-06 Time 11:58 Rev Time 0.25
Received By shill Date 2004-01-30 Time 15:43 Sent To  
Notes
2004-01-30 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE ADDRESS FOR PERMIT # 03040756
 IS 580 EXECUTIVE CENTER DRIVE, NOT
 560.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2004-01-28 Cont ID  
Sent By csiegber Date 2004-01-30 Time 11:09 Rev Time 0.50
Received By shill Date 2004-01-28 Time 11:48 Sent To  
Notes
2004-01-28 00:00:00*****CORRECTIONS******
  
 ELEVATION CERTIFICATE PREPARED BY CRAIG
 A. SMITH & ASSOCIATES 1/26/04
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE ELEVATION CERTIFICATE IS TO
 REFERENCE AN ADDRESS AND PERMIT NUMBER.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-01-10 Cont ID  
Sent By shill Date 2004-01-28 Time 11:37 Rev Time 0.50
Received By shill Date 2004-01-28 Time 11:37 Sent To  
Notes
2005-01-10 00:00:001/10/05 - PER CONTRACTOR, CABINETS ARE
 BEING MANUFACTURED & INSTALLED ACCORDING
 TO APPROVED PLAN
2004-01-28 00:00:00****CORRECTIONS****
  
 CABINET SHOP DRAWINGS PREPARED BY AC
 CABINETRY CORP 11/25/03
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 SEE 03040755
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-01-12 Cont ID  
Sent By csiegber Date 2004-01-27 Time 12:24 Rev Time 0.50
Received By shill Date 2004-01-12 Time 13:53 Sent To  
Notes
2004-01-12 00:00:00REBAR SHOP DRAWINGS PREPARED BY
 SOUTHWESTERN SUPPLIERS DATED 10/30/03,
 2ND THROUGH 5TH FLOOR SLABS BOTTOM
 AND PERIMETER REINFORCING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-01-12 Cont ID  
Sent By shill Date 2004-01-12 Time 13:44 Rev Time 0.50
Received By shill Date 2004-01-12 Time 13:44 Sent To  
Notes
2004-01-12 00:00:00REBAR SHOP DRAWINGS FOR 2ND THROUGH 5TH
 FLOOR SLABS PREPARED BY SOUTHWESTERN
 SUPPLIERS DATED 10/30/03 (TOP ONLY).

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-01-12 Cont ID  
Sent By shill Date 2004-01-12 Time 13:41 Rev Time 1.00
Received By shill Date 2004-01-12 Time 13:41 Sent To  
Notes
2004-01-12 00:00:00FOOTER REBAR SHOP DRAWINGS PREPARED BY
 SOUTHWESTERN SUPPLIERS DATED 8/26/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-12-22 Cont ID  
Sent By rbrown Date 2003-12-22 Time 16:18 Rev Time 0.00
Received By rbrown Date 2003-12-22 Time 16:18 Sent To  
Notes
2003-12-22 00:00:00BUILDING/ELECTRICAL/PLUMBING REVISION
 SUBMITTED ON 11/10/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-09-05 Cont ID  
Sent By csiegber Date 2003-12-12 Time 14:23 Rev Time 0.00
Received By hpiskura Date 2003-09-04 Time 09:28 Sent To  
Notes
2003-09-05 00:00:00PROVISO NOTES ON PERMIT #03040755 APPLY
 TO THIS BUILDING TO ALSO

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-29 Cont ID  
Sent By hpiskura Date 2003-04-29 Time 09:04 Rev Time 0.00
Received By hpiskura Date 2003-04-29 Time 09:04 Sent To  
Notes
2003-04-29 00:00:00PLEASE SEE NOTES UNDER REVIEW 03040755

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2004-10-28 Cont ID  
Sent By dpalmer Date 2004-10-28 Time 09:48 Rev Time 0.33
Received By dpalmer Date 2004-10-28 Time 09:48 Sent To  
Notes
2004-10-28 00:00:00REV FOR LIGHT POLE J-BOX.

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2004-09-22 Cont ID  
Sent By csiegber Date 2004-10-20 Time 17:07 Rev Time 0.50
Received By dpalmer Date 2004-09-22 Time 16:14 Sent To  
Notes
2004-09-22 00:00:00REV FOR LOCATION OF METER CT FOR FIRE
 PUMP.

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2004-07-28 Cont ID  
Sent By csiegber Date 2004-09-15 Time 12:36 Rev Time 0.33
Received By dpalmer Date 2004-07-28 Time 15:03 Sent To  
Notes
2004-07-28 00:00:00******* UNSAT *********
  
 1)NOTE: PLEASE SEE LIFT STATION NEEDS TO
 BE UNDER SEPARATE PERMIT.
 PLANS WERE STAMPED IN ERROR, VOID HAS
 SINCE BEEN VOIDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2004-05-08 Cont ID  
Sent By csiegber Date 2004-07-22 Time 09:28 Rev Time 0.33
Received By dpalmer Date 2004-05-08 Time 07:09 Sent To  
Notes
2004-05-08 00:00:00ELEC REV'S STAMPED.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2004-04-23 Cont ID  
Sent By dpalmer Date 2004-04-23 Time 07:20 Rev Time 1.00
Received By dpalmer Date 2004-04-23 Time 07:20 Sent To  
Notes
2004-04-23 00:00:00OK, STAMPED.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2004-02-02 Cont ID  
Sent By dpalmer Date 2004-02-02 Time 06:58 Rev Time 2.00
Received By dpalmer Date 2004-02-02 Time 06:40 Sent To  
Notes
2004-02-02 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE SHOW AND INDICATE ALL
 LICENSE #'S ON TITLE BLOCKS AS REQ'D
 UNDER FAC 61G1-16.004? ARCHS AND 61G15-
 -23.002 FOR ENG'S.
 PLEASE SEE FS 481.219 FOR ARCHS CA #'S.
 PLEASE ALSO INCLUDE ARCH'S NAME AND
 LICENSE # ON TITLE BLOCK(S).
 THIS IS REQ'D FOR ALL PAGES/TRADES
 WEATHER OR NOT COMMENT IS MADE BY OTHER
 REVIEWS.
 ARCH'S TITLE BLOCKS ARE ALSO ON ELECTRIC
 AL SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2003-11-17 Cont ID  
Sent By btrobaug Date 2003-11-17 Time 16:36 Rev Time 0.25
Received By btrobaug Date 2003-11-17 Time 16:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-09-12 Cont ID  
Sent By dpalmer Date 2003-09-12 Time 13:02 Rev Time 1.50
Received By dpalmer Date 2003-09-12 Time 13:02 Sent To  
Notes
2003-09-12 00:00:00PLANS OK, JUST NEED TO BE RE-SATMPED
 FOR NEW SHEETS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-09-10 Cont ID  
Sent By dpalmer Date 2003-09-09 Time 19:51 Rev Time 1.00
Received By dpalmer Date 2003-09-09 Time 19:51 Sent To  
Notes
2003-09-09 00:00:00PLANS ARE NOW ON HOLD DUE TO AN ISSUE
 THAT HAS COME UP WITH THE SERVICE.
 MAY BE ABLE TO ISSUED WITH A PROVISO.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-06-24 Cont ID  
Sent By dpalmer Date 2003-06-24 Time 07:08 Rev Time 1.50
Received By dpalmer Date 2003-06-24 Time 07:07 Sent To  
Notes
2003-06-24 00:00:00************** UNSAT ***********
  
 1)NOTE: PLEASE SEE THAT THERE ARE STILL
 SOMERECEPTS MISSING FOR 2' OF WALL
 SPACE.210-52
  
 2)NOTE: PLANS/RISER SHOW 3 PARALLEL RUNS
 OF UNGROUNDED CONDUCTORS, HOWEVER ONLY
 SHOWS TWO PARALLEL RUNS OF GROUNDED
 CONDUCTORS? DUE TO INDUCTIONAND INDUCT-
 -IVE HEATING, A 3RD RUN OF THE GROUNDED
 (NEUTRAL) CONDUCTOR WILL BE REQ`D.
 300-20/310-4
 THIS WOULD NOT BE REQ`D FOR BLDG 1, SERV
 -#4.
  
 3)NOTE: PLEASE SEE 250-24, NOTE ON RISER
 DIAGRAM FOR CLUBHOUSE MENTIONS, TO BOND
 GROUND AND NEUTRAL TOGETHER, THIS DONE
 AT THE FIRST MEANS OF DISC, AS PER
 250-24
  
 4)NOTE: PLEASE SEE THAT THERE IS NOT
 ENOUGH INFORMATION FOR FIRE PUMP,
 FIRE PUMP VOLTAGE, MEANS OF DISC, CODE
 LETTER, SIZING OF DISC MEANS FOR LOCKED
 ROTOR, RISER DIAGRAM ETC.430-150,430-151
 (B), 695-4B-1,2 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 PLEASE SEE OTHER REVIEWS, THAT MAY HAVE
 AN AFFECT ON ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-29 Cont ID  
Sent By dpalmer Date 2003-04-29 Time 14:15 Rev Time 4.00
Received By dpalmer Date 2003-04-29 Time 14:15 Sent To  
Notes
2003-04-29 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE CLARIFY DISTANCE FOR
 VOLTAGE DROP ON SITE LIGHTING.
 WE ARE UNDER 2002FBC. PLEASE SEE WIND
 LOAD REQ`D FOR POLES. NOTES 120MPH.
  
 2)NOTE: PLEASE PLACE NOTE/REQUIREMENTS
 ON PLAN FOR FHAC 24 CFR 100.205.
  
 3)NOTE: PLEASE SEE PLANS FOR RECEPT
 SPACING. SOME MISSING PER 210-52.
 2' OF WALL SPACE.
  
 4)NOTE: PLEASE NOTE, SD`S ARE TO BE A
 MIN OF 3' FROM BATH DOOR AND KITCHEN.
  
 5)NOTE: PLEASE CLARIFY ALL SERVICE
 ENTRANCE CONDUCTORS SIZE AND # OF PARA-
 -LLEL RUNS. PLEASE SEE 240-3 B&C
 110-14 AND 310-16
  
 6)NOTE: PLEASE CLARIFY WATER HEATER LOAD
 SHOWN AT 11800W?
 PLEASE CORRELATE W/ PANEL SCHEDULE.
 SHOWN BEING DIFFERENT.
  
 7)NOTE: PLEASE SEE E-16.09 NOTE AT
 BOTTOM OF PANELS MENTIONS : SEE EXX FOR
 LOADS. PLEAS FILL IN APPROPRIATE PAGE.
  
 8)NOTE: PLEASE SEE LIST/CLARIFY THE
 REQ`D ARC FAULT PROTECTED CIRCUITS PER
 210-12
  
 9)NOTE: PLEASE PANEL C2, SHOWS LOCATION
 TO BE IN UTILITY ROOM. PLEASE SEE FLOOR
 PLAN, SHOWN IN HALL? PLEASE CORRELATE.
  
 10)NOTE: PLEASE CORRELATE LOAD SHOWN FOR
 WASHER. PANEL SHOWS AS 1.0KW AND LOAD
 CALCS SHOWS AS 1.5KW(REQ`D) 220-16B
  
 11)NOTE: PLEASE SEE MAIN GROUNDING
 ELECTRODE REQ`D TO FOOTER STEEL 250-50/
 SIZED PER 250-66 SHOWN AS #4/#6 AND #2
 FOR ALL OTHERS AND BONDING?
  
 12)NOTE: PLEASE CLARIFY MAINS SHOWN AS
 "SHUNT TRIP". PLEASE CLARIFY IF THERE
 IS STILL A MANUAL MEANS OF DISCAND
 RATED FOR SERVICE. 230-76-230-79
 PLEASE NOTE, SHUNT TRIPS ARE NOT RATED
 FOR MEANS OF DISC.
  
 13)NOTE: PLEASE NOTE, PLANS AND RISER
 MENTIONS ALUM CONDUCTORS FOR GROUNDING
 AND BONDING. PLEASE NOTE, PER LOCAL
 AMENDMENTS TO FBC/NEC AS ADOPTED BY THE
 CITY OF WEST PALM BEACH, ART 250-62/
 310-2.
 PLEASE ALSO ADJUST EQUIPMENT GROUNDING
 TO APT UNITS. PLEASE NOTE, MIXING OF
 CONDUCTOR AND OR DISSIMILAR METALS.
  
 14)NOTE: PLEASE SEE APPLICATION, MENTION
 -S CLUBHOUSE UNDER THIS #. PLEASE NOTE,
 WILL BE SEPARATED UNDER SEPARATE PERMIT
 AND IS ONLY REVIEW UNDER THIS PERMIT #
 AT THIS TIME.
  
 15)NOTE: PLEASE CLARIFY AND PROVIDE
 MORE INFORMATION ON FIRE PUMP SHOWN IN
 CLUBHOUSE? A COMPLETE REVIEW CAN NOT BE
 DONE AT THIS TIME FOR THIS.SPECS ETC
  
 16)NOTE: PLEASE SEE LOCATION OF PANEL
 "LPA" SHOWN IN LIBARY. PLEASE CHANGE
 LOCATION DUE TO PROXIMITY OF EASILY
 IGNITABLE MATERIALS.384-7
  
 17)NOTE: PLEASE PROVIDE GROUNDING
 ELECTRODE CONDUCTOR SIZES FOR CLUBHOUSE,
 NOTES MENTIONS SEE RISER, RISER SAYS
 SEE GROUNDING DETAIL? PLEASE SHOW AND
 CORRELATE.
  
 PLEASE NOTE: THERE MAY BE FURTHER
 COMMENTS DUE TO SOME ITEMS NOT BEING
 COMPLETE AT THIS TIME.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 PLEASE ALSO SEE FIRE REVIEW COMMENTS
 THAT MAY AFFECT ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2003-11-24 Cont ID  
Sent By mamini Date 2003-11-24 Time 08:48 Rev Time 0.50
Received By mamini Date 2003-11-24 Time 08:48 Sent To  
Notes
2003-11-24 00:00:00PASSED:
 1. SEE PERMIT # 03111160 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2003-09-08 Cont ID  
Sent By mamini Date 2003-09-08 Time 11:44 Rev Time 1.00
Received By mamini Date 2003-09-08 Time 11:44 Sent To  
Notes
2003-09-08 00:00:00PASSED WITH PROVISOS:
 1. SEE REVIEW COMMENTS UNDER PERMIT #
 03040754 DATED 9-8-03.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-06-05 Cont ID  
Sent By mamini Date 2003-06-05 Time 14:34 Rev Time 1.00
Received By mamini Date 2003-06-05 Time 14:33 Sent To  
Notes
2003-06-05 00:00:00FAILED:
 1. SEE REVIEW COMMENT UNDER PERMIT #
 03040754 DATED 6-05-03.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-04-16 Cont ID  
Sent By mamini Date 2003-04-16 Time 11:23 Rev Time 1.00
Received By mamini Date 2003-04-16 Time 11:23 Sent To  
Notes
2003-04-16 00:00:00FAILED:
 1. SEE REVIEW COMMENTS UNDER PERMIT #
 03040754 (PLAN CHECK).
 IF ANY QUESTION PLEASE CONNTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2004-05-10 Cont ID  
Sent By nmccray Date 2004-05-10 Time 12:09 Rev Time 0.00
Received By nmccray Date 2004-05-10 Time 12:09 Sent To  
Notes
2004-05-10 00:00:00REVISION 5-04-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2004-01-29 Cont ID  
Sent By mcarsill Date 2004-01-29 Time 14:57 Rev Time 0.00
Received By mcarsill Date 2004-01-29 Time 14:57 Sent To  
Notes
2004-01-29 00:00:001) ENTRANCE SIGN SHALL PROVIDE THE
 ADDRESSES WITH AT LEAST 6" NUMBERS.
  
 2) STANDPIPE SYSTEM SHALL BE EQUIPPED
 WITH 2 1/2 TO 1 1/2 REDUCERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-12-11 Cont ID  
Sent By csiegber Date 2003-12-12 Time 14:19 Rev Time 0.00
Received By mcarsill Date 2003-12-11 Time 14:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-09-04 Cont ID  
Sent By mcarsill Date 2003-09-04 Time 16:43 Rev Time 0.00
Received By mcarsill Date 2003-09-04 Time 16:43 Sent To  
Notes
2003-09-04 00:00:00APPROVED PROVISO:
  
 1) ELECTRONIC SWITCHES ARE REQUIRED
 ON THE BACKFLOW DEVICE FOR FIRE
 SERVICE.
  
 2) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER
 CONSTRUCTION.
  
 3) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING IS THREE STORIES
 OR THIRTY FEET IN HEIGHT.
  
 4) THE FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE
 SINCE PERMITS WILL BE RECEIVED AFTER
 THE AUGUST 1, 2003 EFFECTIVE DATE.
  
 5) NFPA 13R SYSTEMS ARE NOT ALLOWED
 FOR 5 STORY BUILDINGS.
  
 6) WAFER CHECK VALVES ON THE SUPPLY
 SIDE OF A FIRE PUMP CANNOT BE INSTALLED
 SO CLOSE TO THE PUMP.
  
 7) FINAL EASEMENTS WITH REGARDS TO
 FIRE LINES AND UTILITIES HAVE NOT
 YET BEEN WORKED OUT. ALL APPROVALS
 MUST BE OBTAINED FROM THE PROPER
 AUTHORITIES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-07-01 Cont ID  
Sent By mcarsill Date 2003-07-01 Time 08:00 Rev Time 0.00
Received By mcarsill Date 2003-07-01 Time 08:00 Sent To  
Notes
2003-07-01 00:00:00SEE NOTES FOR 03040754.

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2004-12-06 Cont ID  
Sent By mjacobs Date 2004-12-06 Time 09:50 Rev Time 0.00
Received By mjacobs Date 2004-12-06 Time 09:50 Sent To P
Notes
2004-12-06 00:00:00SENT TO "P" BOX./REV.

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-20 Time 17:07 Rev Time 0.00
Received By csiegber Date 2004-10-20 Time 17:06 Sent To E
Notes
2004-10-20 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 12:36 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 12:36 Sent To E
Notes
2004-09-15 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2004-08-26 Cont ID  
Sent By csiegber Date 2004-08-26 Time 15:12 Rev Time 0.00
Received By csiegber Date 2004-08-26 Time 15:12 Sent To P
Notes
2004-08-26 00:00:00TO KS BOX/SUBMITTAL
 PAN DRAIN DETAIL

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 09:28 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 09:28 Sent To E
Notes
2004-07-22 00:00:00TO DP DESK/REV/FOR POWER TO LIFT STATION

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 09:27 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 09:27 Sent To B
Notes
2004-07-22 00:00:00TO SH DESK/SUBMITTAL
 STUCCO OVER BLOCK

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2004-06-14 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 14:35 Rev Time 0.00
Received By mjacobs Date 2004-06-14 Time 14:35 Sent To P
Notes
2004-06-14 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2004-06-09 Cont ID  
Sent By csiegber Date 2004-06-09 Time 10:49 Rev Time 0.00
Received By csiegber Date 2004-06-09 Time 10:49 Sent To P
Notes
2004-06-09 00:00:00TO KS BOX/REV/

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2004-06-03 Cont ID  
Sent By mmclean Date 2004-06-08 Time 16:36 Rev Time 0.00
Received By csiegber Date 2004-06-03 Time 16:40 Sent To Z
Notes
2004-06-03 00:00:00REV

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2004-05-12 Cont ID  
Sent By csiegber Date 2004-05-12 Time 14:22 Rev Time 0.00
Received By csiegber Date 2004-05-12 Time 14:21 Sent To B
Notes
2004-05-12 00:00:00TO SH DESK/SUBMITTALS/TRUSS & RE-SUB
 FOR CONCRETE MASONRY UNIT

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2004-05-07 Cont ID  
Sent By csiegber Date 2004-05-07 Time 16:26 Rev Time 0.00
Received By csiegber Date 2004-05-07 Time 16:26 Sent To  
Notes
2004-05-07 00:00:00TO COMM BD#36

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-04-28 Time 15:59 Rev Time 0.00
Received By csiegber Date 2004-04-28 Time 15:59 Sent To B
Notes
2004-04-28 00:00:00TO SH DESK/TRUSS FIXES PAGES . . .

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-20 Time 16:19 Rev Time 0.00
Received By csiegber Date 2004-04-20 Time 16:19 Sent To B
Notes
2004-04-20 00:00:00TO SH DESK/SUBMITTAL/TRUSS REPAIRS

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2004-04-08 Cont ID  
Sent By csiegber Date 2004-04-08 Time 08:07 Rev Time 0.00
Received By csiegber Date 2004-04-08 Time 08:07 Sent To  
Notes
2004-04-08 00:00:00TO SH DESK/4 SUBMITTALS/RINKER MASONARY
 REJECTED DOOR SHOP DRAWS/CABINET SHOP
 DRAWS/BOND BEAM 5TH FLR BLDG 1 & 2

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-03-22 Time 14:27 Rev Time 0.00
Received By csiegber Date 2004-03-22 Time 14:27 Sent To B
Notes
2004-03-22 00:00:00TO SH DESK/SUBMITTALS/WEDGE ANCHORS FOR
 STRUCTURAL STEEL COL & TYPE N&S&M MORTOR
 MIX

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-03-22 Time 08:46 Rev Time 0.00
Received By csiegber Date 2004-03-22 Time 08:46 Sent To B
Notes
2004-03-22 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2004-02-27 Cont ID  
Sent By shill Date 2004-02-27 Time 12:21 Rev Time 0.00
Received By shill Date 2004-02-27 Time 12:21 Sent To B
Notes
2004-02-27 00:00:00PRECAST WINDOW SILL SUBMITTAL TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 14:51 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 14:51 Sent To B
Notes
2004-02-25 00:00:00TO SH DESK/POWER FASTENERS SYSTEM FOR
 DRILL & EPOXY\BONSAL F-77 GROUT

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-02-09 Time 16:30 Rev Time 0.00
Received By csiegber Date 2004-02-09 Time 16:30 Sent To B
Notes
2004-02-09 00:00:00TO SH DESK/RESUB/RAILING/SITE & POOL FEN
 CE

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 11:58 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 11:58 Sent To B
Notes
2004-02-06 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 11:57 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 11:57 Sent To P
Notes
2004-02-06 00:00:00TO KS BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-05 Time 10:26 Rev Time 0.00
Received By csiegber Date 2004-02-05 Time 10:26 Sent To B
Notes
2004-02-05 00:00:00TO SH DESK/SUBMITTAL/TRASH,ELEC METER,PH
 ONE CABLE,ELEV EQUIQ & FACP ROOMS DOORS/
 PAD ELEV SURVEY BLDG #2

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2004-01-30 Cont ID  
Sent By csiegber Date 2004-01-30 Time 11:09 Rev Time 0.00
Received By csiegber Date 2004-01-30 Time 11:09 Sent To B
Notes
2004-01-30 00:00:00TO SH DESK/SUBMITTAL/PAD ELEV SURVEY 1&2

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-01-27 Time 12:23 Rev Time 0.00
Received By csiegber Date 2004-01-27 Time 12:23 Sent To B
Notes
2004-01-27 00:00:00TO SH DESK/SUBMITTAL/FOOTINGS

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-01-27 Time 11:33 Rev Time 0.00
Received By csiegber Date 2004-01-27 Time 11:33 Sent To B
Notes
2004-01-27 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-01-27 Time 10:16 Rev Time 0.00
Received By csiegber Date 2004-01-27 Time 10:16 Sent To  
Notes
2004-01-27 00:00:00TO COMM BD#62

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-01-20 Time 15:41 Rev Time 0.00
Received By csiegber Date 2004-01-20 Time 15:41 Sent To B
Notes
2004-01-20 00:00:00TO SH DESK/FILL CELLS & BEAMS/CAB SHOP
 DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-01-08 Cont ID  
Sent By csiegber Date 2004-01-08 Time 16:47 Rev Time 0.00
Received By csiegber Date 2004-01-08 Time 16:47 Sent To  
Notes
2004-01-08 00:00:00TO DON NEELY

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-06 Cont ID  
Sent By csiegber Date 2004-01-06 Time 13:44 Rev Time 0.00
Received By csiegber Date 2004-01-06 Time 13:44 Sent To  
Notes
2004-01-06 00:00:00TO DON NEELY'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-12 Cont ID  
Sent By csiegber Date 2003-12-12 Time 14:20 Rev Time 0.00
Received By csiegber Date 2003-12-12 Time 14:20 Sent To B
Notes
2003-12-12 00:00:00TO HP DESK/SUBMITTAL/SLAB REINFORCING;
 FOOTINGS;FLOOR SLABS (3)

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-12 Cont ID  
Sent By csiegber Date 2003-12-12 Time 14:19 Rev Time 0.00
Received By csiegber Date 2003-12-12 Time 14:19 Sent To FIRE
Notes
2003-12-12 00:00:00SUBMITTAL/SHOP DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-26 Cont ID  
Sent By csiegber Date 2003-11-26 Time 16:29 Rev Time 0.00
Received By csiegber Date 2003-11-26 Time 16:29 Sent To B
Notes
2003-11-26 00:00:00TO HP DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-10 Cont ID  
Sent By csiegber Date 2003-11-10 Time 16:25 Rev Time 0.00
Received By csiegber Date 2003-11-10 Time 16:25 Sent To  
Notes
2003-11-10 00:00:00TO COMM BD#41

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-05-11 Cont ID  
Sent By pkrauss Date 2004-05-11 Time 07:23 Rev Time 0.40
Received By pkrauss Date 2004-05-11 Time 07:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-02-19 Cont ID  
Sent By pkrauss Date 2004-02-19 Time 11:01 Rev Time 0.45
Received By pkrauss Date 2004-02-19 Time 11:00 Sent To  
Notes
2004-02-19 00:00:00DENIED:
 PLANS INDICATE THE REMOVAL OF THE
 OUTSIDE AIR DUCT.PER 2001 FBC(M)
 403.3, THE ONLY BUILDINGS EXEMPT FROM
 THE OUTSIDE AIR REQUIREMENTS ARE ONE
 AND TWO FAMILY DWELLINGS.THIS PROJECT
 IS MULTI-FAMILY THEREFOR OUTSIDE AIR IS
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-09-10 Cont ID  
Sent By hmoser Date 2003-09-10 Time 15:48 Rev Time 1.50
Received By hmoser Date 2003-09-10 Time 15:48 Sent To  
Notes
2003-09-10 00:00:00PASS/PRIVISO
 SEE PROVISO PERMIT # 03040755

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-28 Cont ID  
Sent By pkrauss Date 2003-06-24 Time 12:23 Rev Time 0.50
Received By hmoser Date 2003-06-24 Time 12:23 Sent To  
Notes
2003-06-24 00:00:00TYPE II BUILDING:
 PLEASE CLARIFY VENTILATION REQUIREMENTS
 FOR THE CORRIDORS AS PER 2001 FBC(M)
 TABLE 403.3, PUBLIC SPACES - CORRIDORS
 .05 CFM PER SQ FT.
  
 CLUBHOUSE:
 COMMENT #3 FROM PREVIOUS REVIEW, DRYERS
 THAT EXHAUST GREATER THAN (SHOULD READ
 200 CFM NOT 2,000 CFM) SHALL BE PROVIDED
 WITH MAKE UP AIR.
  
 PLEASE NOTE, THE WALL SEPARATING THE
 FIRE PUMP RM & LAUNDRY RM HAS A 1 HR
 FIRE RESISTANT RATING.(FIRE DAMPERS
 ARE NOT PERMITTED IN DRYER EXHAUST).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 10 Status F Date 2004-12-23 Cont ID  
Sent By kstevens Date 2004-12-23 Time 04:28 Rev Time 0.25
Received By kstevens Date 2004-12-23 Time 04:28 Sent To  
Notes
2004-12-23 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 SEE COMMENTS DATED 12-23-4 ON PERMIT
 NUMBER 03040755-KSTEVENS
  
 REVISION DENIED FOR BOOSTER PUMP

Review Stop P PLUMBING
Rev No 9 Status P Date 2004-09-22 Cont ID  
Sent By kstevens Date 2004-09-22 Time 07:56 Rev Time 0.50
Received By kstevens Date 2004-09-22 Time 07:56 Sent To  
Notes
2004-09-22 00:00:00REVISION OK - EMERGENCY PAN DRAIN LINE
 REVISION FOR W/HEATER

Review Stop P PLUMBING
Rev No 8 Status F Date 2004-06-12 Cont ID  
Sent By kstevens Date 2004-06-12 Time 08:09 Rev Time 0.25
Received By kstevens Date 2004-06-12 Time 08:09 Sent To  
Notes
2004-06-12 00:00:00REVISION DENIED
  
 1) IRRIGATION PLANS WERE NOT PERT OF THE
 ORIGINAL PLANS. SEPARATE PERMIT REQUIRED
 FOR IRRIGATION. SUBMIT PLANS WITH PERMIT
 APPLICATION. WATER USE PERMIT REQUIRED
 FROM SOUTH FLORIDA WATER MANAGEMENT DIS-
 TRICT PRIOR TO SUBMITTING FOR PERMIT
 WITH CITY WPB.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2004-04-29 Cont ID  
Sent By kstevens Date 2004-04-29 Time 13:10 Rev Time 1.25
Received By kstevens Date 2004-04-29 Time 13:10 Sent To  
Notes
2004-04-29 00:00:00REVISION OK - SHEETS P14.01 THRU P14.08
 W/.06A & .06B

Review Stop P PLUMBING
Rev No 6 Status F Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-06 Time 11:57 Rev Time 1.00
Received By kstevens Date 2004-02-03 Time 18:38 Sent To  
Notes
2004-02-05 00:00:00REVISIONDENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHTS AP/P14.01 & AP/P14.03 CLEANOUTS
 REQUIRED PER SECTIONS 708.3.1 & 708.3.3.
 2) SHT AP/14.06 CLEANOUTS REQUIRED PER
 SECTION 708.3.1 & 708.3.3.
 3) SHT AP/P14.08 DETAIL #3 SHOWS THE
 DRAIN LINE FOR THE EMERGENCY SAFETY PAN
 FOR THE WATER HEATER DELETED, AND THE
 RELIEF LINE, (T&P), DRAINING OUTSIDE.
 DETAIL #2 SHOWS T&P LINE DISCHARGING IN-
 TO THE SAFETY PAN FOR THE WATER HEATER.
 PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2003-12-17 Cont ID  
Sent By kstevens Date 2003-12-17 Time 10:46 Rev Time 1.00
Received By kstevens Date 2003-12-17 Time 10:46 Sent To  
Notes
2003-12-17 00:00:00PASSED- INFORMATION REQUIRED FOR CLEAN-
 OUTS IN FIRE WALL AT THE END OF THE
 BLDG DRAINS ON SHEETS AP/P14.01 AND AP/
 14.03 - SUGGEST EXTENDING THE DRAIN INTO
 THE BREEZEWAY AND ADDING FLOOR C/O'S

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-12-09 Cont ID  
Sent By kstevens Date 2003-12-09 Time 12:50 Rev Time 0.50
Received By kstevens Date 2003-12-09 Time 12:50 Sent To  
Notes
2003-12-09 00:00:00REVISION OK - SHTS RP/P14.01, RP/P14.02,
 RP/P14.03, RP/P14.07, RP/P14.08

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-09-04 Cont ID  
Sent By kstevens Date 2003-09-04 Time 15:49 Rev Time 2.00
Received By kstevens Date 2003-09-04 Time 15:49 Sent To  
Notes
2003-09-04 00:00:00PASSED/PROVISO
  
 BACKFLOW PROTECTION REQUIRED FOR TRASH
 CHUTE WASH.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-06-24 Cont ID  
Sent By kstevens Date 2003-06-24 Time 09:55 Rev Time 0.25
Received By kstevens Date 2003-06-24 Time 09:55 Sent To  
Notes
2003-06-24 00:00:00DENIED
  
 1) FROM PREVIOUS REVIEW. CLEANOUTS RE-
 QUIRED IN BOTH BREEZWAYS, (STAIRWAYS),
 SHTS P-14.01 & P-14.03. CLEANOUTS SHALL
 BE FLOOR CLEANOUTS AS THEY ARE REQUIRED
 TO BE TWO WAY CLEANOUTS, OR MORE CLEAN-
 OUTS WILL BE REQUIRED ANT THE UPSTREAM
 END OF THE BLDG DRAIN. 708.5 CLEANOUTS
 ARE REQUIRED TO BE ACCESSIBLE SO THEY
 SHALL BE LOCATED OUTSIDE OF THE UNITS.
 708.10.
 2) SHT P14.07 WATER RISER DIAGRAMS. IF
 WATER HAMMER ARRESTORS ARE INSTALLED AT
 THE WATER HEATERS THEY SHALL BE LOCATED
 AS REQUIRED FOR ALL OTHER WATER HAMMER
 ARRESTORS. PDI-WH 201 & MANUF. INSTALL.
 INSTRUCTIONS.
 3) SUBMIT A HORIZONTAL SANITARY RISER
 DIAGRAM. SHOW ALL RISER TIE-INS AND
 SHOW DRAINAGE FIXTURE UNITS AS THEY
 ACCUMULATE IN THE SYSTEM. 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-30 Cont ID  
Sent By kstevens Date 2003-04-30 Time 12:24 Rev Time 0.50
Received By kstevens Date 2003-04-30 Time 12:17 Sent To  
Notes
2003-04-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-AMEND 98 DESIGN MANUAL
  
 1) SHTS A5.05 & A5.06 LAVS SHALL BE 34"
 MAX FROM FLOOR TO FLOOD RIM LEVEL. SEE
 DETAIL PAGE 7.52 DESIGN MANUAL.
 2) SHT A5.02 - 11-4.16.5 FLUSH CONTROLS
 SHALL BE MOUNTED ON THE WIDE SIDE OF
 TOILET AREAS. (AWAY FROM SIDE GRAB BARS)
 3) SEPARATE POOL PERMIT REQUIRED. HEALTH
 DEPT. PLAN REVIEW REQUIRED FOR FACILIT-
 IES.
 3) SEPARATE IRRIGATION PERMIT REQUIRED.
 4) SHT P14.03 CLEANOUTS REQUIRED IN BOTH
 BREEZEWAYS. SECTION 708.3.1 (MAX 100')
 5) ALL UNITS - PLEASE SPECIFY EITHER
 SPECIFICATION "A" OR "B" BATHROOMS AS
 REQUIRED BY DESIGN MANUAL REQUIREMENT
 7B, PAGE 7.35.
 6) SHT P14.07 WATER RISER DIAGRAMS, THE
 WATER HAMMER ARRESTORS REQUIRED IN SEC.
 604.9, (ICE MAKER, DISHWASHER, WASH
 MACHINE), SHALL BE LOCATED NEAR THE FIX-
 TURE IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 7) SHT P14.06 RISERS S4 & S5, THE WASTE
 STACK SHALL BE THE SAME SIZE THROUGHOUT
 THE LENGTH OF THE WASTE STACK. SECTION
 910.4
 8) RPZ BACKFLOW REQUIRED IN WATER SERV.
 AT EACH BLDG.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 2 Status P Date 2004-06-08 Cont ID  
Sent By mmclean Date 2004-06-08 Time 16:34 Rev Time 0.00
Received By mmclean Date 2004-06-08 Time 16:34 Sent To I
Notes
2004-06-08 00:00:00APPROVED REVISION.

Review Stop Z ZONING
Rev No 1 Status P Date 2003-09-12 Cont ID  
Sent By mmclean Date 2003-09-12 Time 11:17 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-09-12 00:00:009/12/03 OK PER GRACE JOYCE MM