Plan Review Details - Permit 03040755
Plan Review Stops For Permit 03040755
Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2005-02-10 Cont ID  
Sent By shill Date 2005-02-10 Time 09:02 Rev Time 0.50
Received By shill Date 2005-02-10 Time 09:02 Sent To PC
Notes
2005-02-10 00:00:00REVISED SHEETS AP A5.02, AP A6.01

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status P Date 2004-08-24 Cont ID  
Sent By shill Date 2004-08-24 Time 08:46 Rev Time 1.00
Received By shill Date 2004-08-24 Time 08:46 Sent To  
Notes
2004-08-24 00:00:00SUBMITTALS - STRUC.DETAIL, TRUSS
  
 NEW GROUT FOR NEW OPENING, (FIX FOR
 OPENING BIGGER THAN 12")
  
 TRUSS ENGINEERING, PICNIC PAVILLION AND
 MAIL KIOSK

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status P Date 2004-07-27 Cont ID  
Sent By csiegber Date 2004-08-05 Time 16:45 Rev Time 0.50
Received By alange Date 2004-07-27 Time 15:15 Sent To  
Notes
2004-07-27 00:00:00SUBMITTAL OK, STUCCO

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status P Date 2004-05-14 Cont ID  
Sent By csiegber Date 2004-07-22 Time 09:11 Rev Time 1.00
Received By shill Date 2004-05-14 Time 16:57 Sent To  
Notes
2004-05-14 00:00:00TRUSS REPAIRS PREPARED BY JULIUS LEE, PE
 DATED 4/27/4
 SHEETS 65, 62, 91, 90, 88, 89, 87, 86

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status F Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-12 Time 14:24 Rev Time 0.50
Received By shill Date 2004-05-04 Time 16:50 Sent To  
Notes
2004-05-04 00:00:00****CORRECTIONS****
 RINKER BLOCK SUBMITTAL
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 DOCUMENTS PREPARED BY AN ENGINEER AND
 FILED FOR PUBLIC RECORD ARE TO HAVE AN
 ORIGINAL SEAL AND SIGNATURE.TITLE
 BLOCK REQUIRED INCLUDING PRINTED LICENSE
 NUMBER, FAC61G15-23.002.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status P Date 2004-04-19 Cont ID  
Sent By shill Date 2004-04-19 Time 11:43 Rev Time 0.25
Received By shill Date 2004-04-19 Time 11:43 Sent To  
Notes
2004-04-19 00:00:00LETTER IN RESPONSE TO DOOR LOUVER
 CORRECTION PREPARED BY BJ&K DATED 4/7/4
  
 LETTER IN RESPONSE TO CABINET CORRECTION
  
 STEEL SHOPS (BEAM & COLUMN)

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status P Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-08 Time 08:05 Rev Time 0.50
Received By shill Date 2004-04-01 Time 12:08 Sent To  
Notes
2004-04-01 00:00:00SHORING INSPECTION LETTER, 5TH FLOOR
 PREPARED BY CALVIN FOONG, PE AND
 LETTER FROM BJ&K

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status P Date 2004-03-22 Cont ID  
Sent By shill Date 2004-03-22 Time 14:41 Rev Time 0.50
Received By shill Date 2004-03-22 Time 14:41 Sent To  
Notes
2004-03-22 00:00:00SUBMITTALS
  
 MASONRY SPECS
 WEDGE ANCHOR SPECS

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-03-22 Time 14:26 Rev Time 0.50
Received By shill Date 2004-03-22 Time 13:10 Sent To  
Notes
2004-03-22 00:00:00TRUSS DRAWINGS PREPARED BY JULIUS LEE,PE
 2/12/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2004-03-18 Cont ID  
Sent By csiegber Date 2004-03-19 Time 16:15 Rev Time 0.25
Received By shill Date 2004-03-18 Time 17:19 Sent To  
Notes
2004-03-18 00:00:00SHORING 4TH FLOOR INSPECTION LETTER
 PREPARED BY CALVIN FOONG, PE

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2004-03-06 Cont ID  
Sent By shill Date 2004-03-06 Time 17:31 Rev Time 0.50
Received By shill Date 2004-03-06 Time 17:31 Sent To  
Notes
2004-03-06 00:00:00PRECAST WINDOW SILL SPECS
 CASTCRETE

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2004-03-05 Cont ID  
Sent By shill Date 2004-03-05 Time 08:08 Rev Time 0.50
Received By shill Date 2004-03-05 Time 08:08 Sent To  
Notes
2004-03-05 00:00:00SHORING/RESHORE LETTER, 3RD FLOOR DECK
 PREPARED BY CALVIN FOONG, PE 3/3/4

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2004-03-01 Cont ID  
Sent By shill Date 2004-03-01 Time 18:01 Rev Time 1.00
Received By shill Date 2004-03-01 Time 18:01 Sent To  
Notes
2004-03-01 00:00:00SUBMITTALS - BONSAL GROUT, POWER
 FASTENERS FOR DRILL & EPOXY

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status F Date 2004-02-24 Cont ID  
Sent By csiegber Date 2004-02-25 Time 14:51 Rev Time 1.00
Received By shill Date 2004-02-24 Time 16:33 Sent To  
Notes
2004-02-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)DRAWINGS PREPARED BY AND ENGINEER
 ARE TO HAVE A TITLE BLOCK WITH THE
 FOLLOWING:
 AUTH # OF FIRM
 PRINTED NAME & LIC # OF PERSON SEALING
 THE PLAN
 ADDRESS
  
 POWER SYSTEMS ENGINEERING IS REQUIRED
 TO HAVE AN AUTHORIZATION NUMBER FROM
 FBPE TO PRACTICE ENGINEERING IN FLORIDA.
 SOME SHEETS WERE SUBMITTED WITHOUT
 ANY TITLE BLOCK.PLEASE READ FAC
 61G15-23.002.
  
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2004-02-20 Cont ID  
Sent By shill Date 2004-02-20 Time 10:54 Rev Time 0.50
Received By shill Date 2004-02-20 Time 10:54 Sent To  
Notes
2004-02-20 00:00:00SHORING INSPECTION LETTERS, 2ND FLOOR,
 PREPARED BY CALFIN FOONG, PE AND CAPRI
 ENGINEERING, PE

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2004-02-19 Cont ID  
Sent By shill Date 2004-02-19 Time 12:11 Rev Time 0.50
Received By shill Date 2004-02-19 Time 12:11 Sent To  
Notes
2004-02-19 00:00:00***CORRECTIONS***
  
 TRASH, ELEC METER, PHONE/CABLE, ELEV,
 EQUIP AND FACP ROOM DOORS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE NOTATION ON SHEET 2 TO CUT
 THE DOORS TO INSTALL LOUVERS IS NOT
 COVERED BY THE PRODUCT APPROVALS
 SUBMITTED WITH THE BUILDING PERMIT
 APPLICATION.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2004-02-19 Cont ID  
Sent By shill Date 2004-02-19 Time 11:50 Rev Time 0.50
Received By shill Date 2004-02-19 Time 11:50 Sent To  
Notes
2004-02-19 00:00:00STAIR DOORS SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2004-02-11 Cont ID  
Sent By shill Date 2004-02-11 Time 15:54 Rev Time 0.50
Received By shill Date 2004-02-11 Time 15:54 Sent To  
Notes
2004-02-11 00:00:00REVISED SHORING PLAN DATED 2/10/04
 FILED W/03040756

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-02-09 Time 16:30 Rev Time 1.00
Received By shill Date 2004-02-09 Time 11:20 Sent To  
Notes
2004-02-09 00:00:00SHORING & RESHORINGBY CALVIN FOONG
 PE DATED 2/4/04 (ALSO 03040756)

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2004-01-30 Cont ID  
Sent By csiegber Date 2004-02-06 Time 11:58 Rev Time 0.25
Received By shill Date 2004-01-30 Time 15:16 Sent To  
Notes
2004-01-30 00:00:00ELEVATION TOP OF EXPANSION JOINTS
 CRAIG A SMITH & ASSOCIATES

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2004-01-29 Cont ID  
Sent By csiegber Date 2004-01-30 Time 11:08 Rev Time 0.50
Received By shill Date 2004-01-29 Time 18:31 Sent To  
Notes
2004-01-29 00:00:004000 PSI CONCRETE MIX AND ADMIXTURES
 RINKER MATERIALS (UNDERMINED FOOTINGS)

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2004-01-28 Cont ID  
Sent By shill Date 2004-01-28 Time 11:42 Rev Time 1.00
Received By shill Date 2004-01-28 Time 11:42 Sent To  
Notes
2004-01-28 00:00:00*****CORRECTIONS*****
  
 ELEVATION CERTIFICATE PREPARED BY CRAIG
 A. SMITH & ASSOCIATES
  
 1.)THE ELEVATION CERTIFICATE IS FOR
 "BUILDING 1" WITH A PROJECT NUMBER.
 PLEASE REFER TO AN ADDRESS AND PERMIT
 NUMBER.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2004-01-28 Cont ID  
Sent By shill Date 2004-01-28 Time 11:29 Rev Time 1.00
Received By shill Date 2004-01-28 Time 11:29 Sent To  
Notes
2004-01-28 00:00:00****CORRECTIONS*****
  
 CABINET SHOP DRAWINGS PREPARED BY AC
 CABINETRY CORP 11/25/03
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE SUPPORT BRACKETS (FOR
 ACCESSIBILITY) HAVE DIMENSIONS NOT
 CONSISTENT WITH YOUR APPROVED.THEY
 DO NOT CONFORM TO ANSI 1986 (SEE
 ATTACHED).TO CHANGE THIS SIZE, SUBMIT
 AS A REVISION FROM THE ARCHITECT, NOT
 AS A SHOP DRAWING, FOR REVIEW FOR CODE
 COMPLIANCE.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-01-27 Time 12:24 Rev Time 0.50
Received By shill Date 2004-01-22 Time 19:51 Sent To  
Notes
2004-01-22 00:00:00SHOP DRAWINGS, FILLED CELLS & BEAMS

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2003-12-30 Cont ID  
Sent By csiegber Date 2004-01-20 Time 15:40 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-12-30 00:00:00TRUSS DRAWINGS FROM PRODUCTION TRUSS AND
 FABRICATION ARE NOT SIGNED AND SEALED.
  
 THE ARCHITECTURAL REVISIONS ARE NOT
 SIGNED AND SEALED AND MUST BE SUBMITTED
 AS REVISIONS AND THE FEES PAID.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-12-22 Cont ID  
Sent By rbrown Date 2003-12-22 Time 16:16 Rev Time 0.00
Received By rbrown Date 2003-12-22 Time 16:16 Sent To  
Notes
2003-12-22 00:00:00BUILDING/ELECTRICAL/PLUMBING REVISION
 SUBMITTED ON 11/10/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-09-05 Cont ID  
Sent By csiegber Date 2003-12-12 Time 14:26 Rev Time 0.00
Received By rbrown Date 2003-12-22 Time 16:12 Sent To  
Notes
2003-12-22 00:00:00PASSED BY H. PISKURA ON 9/4/03 SEE BELOW
2003-09-04 00:00:00PROVISO:
  
 THE GENERAL NOTES ON THE FIRE
 PROTECTIONPLANS, SHEET FP 13.01 HAVE
 SEVERAL REFERENCES TO NFPA 13R FOR THE
 DESIGN STANDARD.THIS DESIGN MUST BE
 AN NFPA 13 DESIGN IN ITS ENTIRETY IN
 ACCORDANCE WITH FBC 903.2.
  
 ALSO THE FLORIDA BUILDING CODE INVOKES
 NFPA 13-99 NOT THE 2000 EDITION
 DECLARED.PLEASE REVISE AS NECESSARY
 AND ENSURE COMPLIANCE WITH THE 1999
 EDITION.
  
 SHEET FP 13.02 SHOWS A 6" WAFER CHECK
 VALVE ON THE SUCTION SIDE OF THE PUMP
 WITHIN TEN PIPE DIAMETERS OF THE FLANGE.
 SEE NFPA 20-99 SECTION 2-21.3.
  
 SEE NFPA 13-99 CHAPTER 8 FOR DESIGN
 PLAN AND CALCULATION CRITERIA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-26 Cont ID  
Sent By hpiskura Date 2003-06-26 Time 10:10 Rev Time 0.00
Received By hpiskura Date 2003-06-25 Time 14:26 Sent To  
Notes
2003-06-26 00:00:00SECOND PAID PLAN REVIEW, NOT A PERMIT
 APPLICATION.
  
 COMMENTS ARE APPLICABLE TO BOTH
 BUILDING TYPES.
  
 THE TRESHOLD INSPECTION PLAN MUST BE
 SIGNED, SEALED AND DATED WHEN SUBMITTED
 FOR PERMIT APPLICATION.THE STATEMENT
 CONTAINED IN FBC 105.13.4.4 MUST APPEAR
 ON THE PERMIT PLANS.
  
 ADVISORY NOTE:THE U904 THREE HOUR FIRE
 RATED MASONRY WALL SYSTEM REQUIRES
 BLOCKS WITH UL CLASSIFICATION.THERE
 ARE FEW IF ANY MANUFACTURERS IN THIS
 AREA THAT PROVIDE UL CLASSIFICATION.
  
 SHEET S3.01 GENERAL NOTE #3 DECLARES
 COMPONENT AND CLADDING PRESSURES OF
 +37.1 AND -48.4.THE "ROOF FASTENING
 ZONE" SHOWS 4' AND 5' FOR ZONE 3.
 SHEET 3.02 DECLARES A "BASIC PRESSURE"
 FROM TABLE 1606.2A AS P=38.5 PSF.THE
 TABLE WITH THE COMPONENT AND CLADDING
 PRESSURES FOR OPENINGS IN WALLS CALLS
 OUT AN INTERIOR ZONE AND EDGE STRIP.
 THIS TABLE HAS A COEFFICIENT OF 1.10
 AND LIST OF VALUES.THE ARCHITECT'S
 RESPONSE LETTER DATED 5/28/03 STATED
 THAT THE SIMPLIFIED WINDLOAD METHOD IN
 FBC 1606.2 WAS TO BE USED.
  
 WHERE ARE THE PRESSURES IN GENERAL NOTE
 # 3 TO BE APPLIED?HOW WERE THEY
 DETERMINED?
  
 TABLE 1606.2A IS THE TABLE FOR THE MAIN
 WIND FORCE RESISTING SYSTEM, NOT
 COMPONENTS AND CLADDING.FBC 1606.2
 DOES NOT USE A "BASIC PRESSURE" SUCH AS
 THAT DECLARED AS "P= 38 PSF."SEE FBC
 1606.2.2.1.
  
 WHERE IS THE DETERMINATION FOR THE ZONES
 1 THROUGH 5?SEE FBC 1606.2.3.
  
 AS AN EXAMPLE: SEE FBC TABLE 1606.2B,
 UNDER HEADING "WALL" ZONE 5, EFFECTIVE
 WIND AREA 20 SF, READ ACROSS TO COLUMN
 NUMBERED 140 MPH, TO FIND 33.7 AND
 -44.0.SEE FOOTNOTE 2 TO TABLE 1606.2B.
  
 GO TO TABLE 1606.2D, USING A MEAN ROOF
 HEIGHT OF 50' FIND A COEFFICIENT OF
 1.16 TO BE USED FOR EXPOSURE B.
  
 1.16 X -44.0 = -51.04.THIS DOES NOT
 AGREE WITH THE NUMBERS IN THE TABLE ON
 SHEET S3.02 OR THE GENERAL NOTE #3.
  
 WILL THERE BE ANY TESTS REQUIRED FOR THE
 REINFORCED MASONRY?SECTION 04000 OF
 THE CITED PROJECT MANUAL DOES NOT SPEAK
 TO FREQUENCY OF GROUT TESTS, IF ANY,
 PRISM TESTS, IF ANY OR EVEN
 MANUFACTURER'S CERTIFICATION.THERE
 ARENO QUALIFICATIONS FOR HEIGHTS OF
 GROUT LIFT, CLEAN OUT, CORE SIZE OR ANY
 SIGNIFICANT PORITION OF THE CRITERIA
 CONTAINED IN ACI 530-99/ASCE 5-99/TMS
 402-99, AS NOTED IN FBC 2103.1.
  
 THE DRAFTSTOPPING ON SHEET A5.08 DOES
 NOT APPEAR TO BE EFFECTIVELY PLACED.
 PLEASE SEE FBC 2305.2.3 EXCEPTION #3
 FOR BEST APPLICATION.
  
 THE ENERGY CODE CALCULATIONS SHOULD BE
 ON FORM 400.SEE FBC 13-400.0 AND
 13-101.2.1.ENSURE ALL SIGNATURES AS
 REQUIRED ON THAT FORM ARE PROVIDED.
  
 SHEET A7.01 SHOWS A SLAB RECESS OF
 3/4",THE CITY HAS AMENDED THIS CODE
 SECTION AND REQUIRES 1.5".PLEASE
 REVISE AS NECESSARY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-29 Cont ID  
Sent By hpiskura Date 2003-04-28 Time 16:22 Rev Time 0.00
Received By hpiskura Date 2003-04-25 Time 14:21 Sent To  
Notes
2003-04-29 00:00:00THESE WILL BE THRESHOLD BUILDINGS AND
 MUST COMPLY WITH FBC 105.13 AND FS 553.
  
 SHEET S4.02 ARE THE THIRD THROUGH FIFTH
 FLOORS TO BE ASSUMED THE SAME AS THE
 SECOND?PLEASE CLARIFY DESIGN INTENT
 THROUGHOUT, INCLUDING THE ARCHITECTURAL
 PAGES.SEE FBC 104.2 AND THE LIST IN
 FBC 104.3.1.1 FOR PERMIT PLAN
 INFORMATION.
  
 SHEET S3.01, HOW WERE THE COMPONENT AND
 CLADDING PRESSURES OF +33.7 AND -44.0
 DETERMINED FOR BUILDINGS OF THIS
 HEIGHT.
  
 WILL THERE BE ANY TEST REQUIEMENTS OF
 THE REINFORCED MASONRY?
  
 SHEET S3.02 DECLARES A 130 MPH WIND
 SPEED, WEST PALM BEACH IS IN AN 140 MPH
 ZONE.
  
 SHEET S3.02 CITES COMPONENT AND CLADDING
 PRESSURES FROM FIGURE (TABLE) 1606.2B.
 IT APPEARS THE FACTORS FROM 1606.2D
 HAVE NOT BEEN APPLIED AND THE ZONES
 SHOWN ON SHEET S3.01 ARE NOT CORRECT
 FOR THESE BUILDINGS.FURTHER, THESE
 BUILDINGS DO NOT APPEAR TO HAVE THE
 SYMMETRY OF A SIMPLE DIAPHRAGM BUILDING
 AS PROVIDED FOR IN FBC 1606.2.1 AND
 SHOULD BE DESIGNED TO THE WIND
 PROVISIONS OF ASCE 7-98.
  
 THE WOOD TRUSS NOTES ON S3.01 CITE AN
 NDS STANDARD FOR DESIGN.SEE FBC
 2309.2 FOR MANDATORY DESIGN
 SPECIFICATIONS AND FBC TABLE 1604.1 FOR
 MINIMUM LIVE LOAD REQUIREMENTS.
  
 SHEET A9.01, THE STAIR DOORS SHOWN AS
 #15 ARE REQUIRED TO BE 90 MINUTE, SEE
 FBC TABLE 705.1.
  
 DRAFTSTOPPING OF THE ATTIC SPACE IN
 ACCORDANCE WITH FBC 2305.2.3 IS
 REQUIRED.
  
 SHOW THE ATTIC ACCESS, FBC 2309.6 AND
 VENTILATION REQUIREMENTS OF FBC 2309.7,
 INCLUDE FREE AREA OF ANY SCREEN VENTS.
  
 SHOW THE DESIGN LOADS FOR THE HAND AND
 GUARD RAILS.SEE FBC 1608.2.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. CALL 561-233-5025 FOR MORE
 INFORMATION.
  
 IF PRODUCT ACCEPTANCE AND/OR TEST
 REPORTS FOR THE DOORS, WINDOWS AND ROOF
 COVERINGS ARE NOT INCLUDED WITH THE
 PERMIT APPLICATION, SEPARATE PERMITS
 AND ADDITIONAL FEES WILL BE REQUIRED.
  
 PERMIT INFORMATION, PLANS,
 SPECIFICATIONS, ETC. ARE TO BE PROVIDED
 TO THE CITY IN TRIPLICATE FOR THRESHOLD
 BUILDINGS.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2004-05-08 Cont ID  
Sent By dpalmer Date 2004-05-08 Time 07:08 Rev Time 0.33
Received By dpalmer Date 2004-05-08 Time 07:08 Sent To  
Notes
2004-05-08 00:00:00REV'S STAMPED.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2004-04-23 Cont ID  
Sent By dpalmer Date 2004-04-23 Time 07:21 Rev Time 1.00
Received By dpalmer Date 2004-04-23 Time 07:21 Sent To  
Notes
2004-04-23 00:00:00OK,PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 6 Status   Date 2004-04-06 Cont ID  
Sent By btrobaug Date 2004-04-06 Time 08:34 Rev Time 0.75
Received By btrobaug Date 2004-04-06 Time 08:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-02-02 Cont ID  
Sent By dpalmer Date 2004-02-02 Time 07:20 Rev Time 1.00
Received By dpalmer Date 2004-02-02 Time 07:19 Sent To  
Notes
2004-02-02 00:00:00**** UNSAT ****
  
 SEE NOTES UNDER 03040756

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-11-17 Cont ID  
Sent By btrobaug Date 2003-11-17 Time 16:36 Rev Time 0.25
Received By btrobaug Date 2003-11-17 Time 16:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-09-09 Cont ID  
Sent By dpalmer Date 2003-09-09 Time 19:53 Rev Time 1.00
Received By dpalmer Date 2003-09-09 Time 19:53 Sent To  
Notes
2003-09-09 00:00:00ELECTRICAL PLANS OK,STAMPED AND SIGNED
 OFF.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-06-24 Cont ID  
Sent By dpalmer Date 2003-06-24 Time 08:23 Rev Time 2.00
Received By dpalmer Date 2003-06-24 Time 08:22 Sent To  
Notes
2003-06-24 00:00:00PLEASE SEE NOTES, UNDER 03040756

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-29 Cont ID  
Sent By dpalmer Date 2003-04-29 Time 18:13 Rev Time 2.00
Received By dpalmer Date 2003-04-29 Time 18:13 Sent To  
Notes
2003-04-29 00:00:00********** UNSAT *********
  
 PLEASE SEE NOTES UNDER #03040756

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2003-11-24 Cont ID  
Sent By mamini Date 2003-11-24 Time 08:45 Rev Time 0.50
Received By mamini Date 2003-11-24 Time 08:45 Sent To  
Notes
2003-11-24 00:00:00PASSED:
 1. SEE PERMIT # 03111160 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2003-09-08 Cont ID  
Sent By mamini Date 2003-09-08 Time 11:38 Rev Time 1.00
Received By mamini Date 2003-09-08 Time 11:37 Sent To  
Notes
2003-09-08 00:00:00PASSED WITH PROVISOS:
 1. SEE REVIEW COMMENTS UNDER PERMIT #
 03040754 DATED 9-8-03.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-06-05 Cont ID  
Sent By mamini Date 2003-06-05 Time 14:29 Rev Time 1.00
Received By mamini Date 2003-06-05 Time 14:29 Sent To  
Notes
2003-06-05 00:00:00FAILED:
 1. SEE REVIEW COMMENT UNDER PERMIT #
 0304074 DATED 6-05-03.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-04-16 Cont ID  
Sent By mamini Date 2003-04-16 Time 11:31 Rev Time 1.00
Received By mamini Date 2003-04-16 Time 11:30 Sent To  
Notes
2003-04-16 00:00:00FAILED:
 1. SEE REVIEW COMMENTS UNDER PERMIT #
 03040754. (PLAN CHECK)
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2004-05-10 Cont ID  
Sent By nmccray Date 2004-05-10 Time 12:08 Rev Time 0.00
Received By nmccray Date 2004-05-10 Time 12:07 Sent To  
Notes
2004-05-10 00:00:00REVISION 5-04-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status   Date 2004-04-30 Cont ID  
Sent By mcarsill Date 2004-04-30 Time 12:14 Rev Time 0.00
Received By mcarsill Date 2004-04-30 Time 12:14 Sent To  
Notes
2004-04-30 00:00:001) THE ENTRY SIGN LOCATED NEAR THE
 OPENING SHALL BE IN ADDITION TO THE
 SIGN REQUIRED ON EXECUTIVE CENTER
 DRIVE TO DIRECT EMERGENCY SERVICES TO
 THE TWO APARTMENT BUILDINGS LOCATED
 BEHIND THE EXISTING CLEAR LAKE
 COLONY.
  
 2) END OF LINE DEVICES SHOWN ON FIRE
 ALARM SYSTEM WIRING. THE FIRE ALARM
 SYSTEMS SHALL BE CLASS A, STYLE D, OR
 FULLY ADDRESSABLE.
  
 3) NFPA 13R IS REFERENCED ON PLANS.
 NFPA 13R SYSTEMS ARE FOR RESIDENTIAL
 BUILDINGS OF FOUR OR LESS STORIES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2004-01-29 Cont ID  
Sent By mcarsill Date 2004-01-29 Time 15:02 Rev Time 0.00
Received By mcarsill Date 2004-01-29 Time 15:02 Sent To  
Notes
2004-01-29 00:00:001) ENTRANCE SIGN SHALL PROVIDE THE
 ADDRESSES WITH AT LEAST 6" NUMBERS.
  
 2) STANDPIPE SYSTEM SHALL BE
 EQUIPPED WITH 2 1/2 TO 1 1/2 REDUCERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-12-11 Cont ID  
Sent By csiegber Date 2003-12-12 Time 14:13 Rev Time 0.00
Received By mcarsill Date 2003-12-11 Time 14:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-09-04 Cont ID  
Sent By mcarsill Date 2003-09-04 Time 16:48 Rev Time 0.00
Received By mcarsill Date 2003-09-04 Time 16:48 Sent To  
Notes
2003-09-04 00:00:00APPROVED PROVISO: PLEASE SEE
 COMMENTS AT 03040756.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-07-01 Cont ID  
Sent By mcarsill Date 2003-07-01 Time 07:59 Rev Time 0.00
Received By mcarsill Date 2003-07-01 Time 07:59 Sent To  
Notes
2003-07-01 00:00:00SEE NOTES FOR 03040754.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-05-09 Cont ID  
Sent By mcarsill Date 2003-05-09 Time 15:22 Rev Time 0.00
Received By mcarsill Date 2003-05-09 Time 15:22 Sent To  
Notes
2003-05-09 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING,AND AFTER CONSTRUCTION.
  
 2) PLEASE PROVIDE AN OVERALL SITE PLAN
 DISPLAYING ALL EXISTING BUILDINGS AND
 CONDITIONS.
  
 3) TAMPER SWITCHES,CHAINS AND LOCKS
 ARE REQUIRED ON BACKFLOW DEVICE.
  
 4) ALL GATE ENTRY SYSTEMS ARE TO BE
 PROPERLY PERMITTED.
  
 5) KNOX-BOX RAPID ENTRY SYSTEM ARE
 REQUIRED FOR THE BUILDINGS.
  
 6) BUILDING ADDRESSES REQUIRED.
  
 7) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR
 WALLS AND CEILINGS OF CLUBHOUSE.
  
 8) NFPA 13R NOTE DOES NOT APPLY.
  
 9) THE STANDPIPE SYSTEM SHALL BE
 EQUIPPED WITH 2 1/2 TO 1 1/2 REDUCERS.
  
 10) TACTILE SIGNAGE REQUIRED AT
 STAIRWAYS.
  
 11) ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO SHALL BE
 MARKED SHAFTWAY.
  
 12) PLEASE PROVIDE WRITTEN DOCUMENTATION
 THAT EITHER BUILDING WILL NOT BE SOLD
 INDEPENDENTLY FROM THE OTHER ONE SINCE
 ONLY ONE FIRE PUMP IS SHOWN.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-02-09 Time 14:14 Rev Time 0.00
Received By adarroug Date 2005-02-09 Time 14:14 Sent To B
Notes
2005-02-09 00:00:00TO SHILL DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2004-08-26 Cont ID  
Sent By csiegber Date 2004-08-26 Time 15:11 Rev Time 0.00
Received By csiegber Date 2004-08-26 Time 15:11 Sent To P
Notes
2004-08-26 00:00:00TO KS BOX/SUBMITTAL
 PAN DRAIN DETAIL

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2004-08-05 Cont ID  
Sent By csiegber Date 2004-08-05 Time 16:45 Rev Time 0.00
Received By csiegber Date 2004-08-05 Time 16:43 Sent To B
Notes
2004-08-05 00:00:00TO SH DESK/SUBMITTAL
 FIX FOR OPENING BIGGER THAN 12"
 MAIL KIOSK & PICNIC PAVILLONQA

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 09:11 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 09:10 Sent To B
Notes
2004-07-22 00:00:00TO SH DESK/SUBMITTAL
 STUCCO OVERE BLOCK

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2004-06-09 Cont ID  
Sent By csiegber Date 2004-06-09 Time 10:43 Rev Time 0.00
Received By csiegber Date 2004-06-09 Time 10:43 Sent To P
Notes
2004-06-09 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2004-06-03 Cont ID  
Sent By mmclean Date 2004-06-08 Time 16:36 Rev Time 0.00
Received By csiegber Date 2004-06-03 Time 16:38 Sent To Z
Notes
2004-06-03 00:00:00REV

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-06-03 Time 08:21 Rev Time 0.00
Received By csiegber Date 2004-06-03 Time 08:20 Sent To B
Notes
2004-06-03 00:00:00TO SH DESK/

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2004-05-12 Cont ID  
Sent By csiegber Date 2004-05-12 Time 14:24 Rev Time 0.00
Received By csiegber Date 2004-05-12 Time 14:24 Sent To B
Notes
2004-05-12 00:00:00TO SH DESK/SUBMITTAL/TRUSS CUT OUT &
 CONCRETE MASONRY UNIT

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2004-05-07 Cont ID  
Sent By csiegber Date 2004-05-07 Time 12:07 Rev Time 0.00
Received By csiegber Date 2004-05-07 Time 12:07 Sent To  
Notes
2004-05-07 00:00:00TO COMM BD#36

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2004-05-07 Cont ID  
Sent By csiegber Date 2004-05-07 Time 12:02 Rev Time 0.00
Received By csiegber Date 2004-05-07 Time 12:01 Sent To B
Notes
2004-05-07 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-05-05 Time 14:16 Rev Time 0.00
Received By csiegber Date 2004-04-20 Time 16:16 Sent To  
Notes
2004-04-20 00:00:00TO COMM BD#62

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2004-04-08 Cont ID  
Sent By csiegber Date 2004-04-08 Time 08:05 Rev Time 0.00
Received By csiegber Date 2004-04-08 Time 08:05 Sent To B
Notes
2004-04-08 00:00:00TO SH DESK/4 SUBMITTALS/RINKER MASONARY
 UNITS/DOOR SHOP DRAWS/CABINET SHOP DRAWS
 BOND BEAM -5TH FLR #1 & 2

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-03-22 Time 14:26 Rev Time 0.00
Received By csiegber Date 2004-03-22 Time 14:26 Sent To B
Notes
2004-03-22 00:00:00TO SH DESK/SUBMITTALS/WEDGE ANCHORS FOR
 STRUCTURAL STEEL COL & TPE N&S&M MORTAR
 MIX

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-19 Time 16:15 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 16:15 Sent To B
Notes
2004-03-19 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 14:51 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 14:51 Sent To B
Notes
2004-02-25 00:00:00TO SH DESK/POWER FASTENERS SYSTEM FOR
 DRILL & EPOXY\ BONSAL F-77 GROUT

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-02-09 Time 16:30 Rev Time 0.00
Received By csiegber Date 2004-02-09 Time 16:30 Sent To B
Notes
2004-02-09 00:00:00TO SH DESK/RAILING/SITE & POOL FENCE

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 11:58 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 11:58 Sent To B
Notes
2004-02-06 00:00:00TO SH DESK/SUBMITALL

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 11:57 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 11:57 Sent To P
Notes
2004-02-06 00:00:00TO KS BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-05 Time 10:25 Rev Time 0.00
Received By csiegber Date 2004-02-05 Time 10:25 Sent To B
Notes
2004-02-05 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2004-01-30 Cont ID  
Sent By csiegber Date 2004-01-30 Time 11:08 Rev Time 0.00
Received By csiegber Date 2004-01-30 Time 11:08 Sent To B
Notes
2004-01-30 00:00:00TO SH DESK/SUBMITTAL/PAD ELEV SURVEY 1&2

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-01-27 Time 12:24 Rev Time 0.00
Received By csiegber Date 2004-01-27 Time 12:24 Sent To B
Notes
2004-01-27 00:00:00TO SH DESK/SUBMITTAL/FOOTINGS

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-01-27 Time 11:35 Rev Time 0.00
Received By csiegber Date 2004-01-27 Time 11:35 Sent To B
Notes
2004-01-27 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-01-20 Time 15:46 Rev Time 0.00
Received By csiegber Date 2004-01-20 Time 15:46 Sent To M
Notes
2004-01-20 00:00:00TO PK BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-01-20 Time 15:40 Rev Time 0.00
Received By csiegber Date 2004-01-20 Time 15:40 Sent To B
Notes
2004-01-20 00:00:00TO SH DESK/SUBMITTAL/FILL CELLS & BEAMS
 & CABINET SHOP DRAWING

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-01-08 Cont ID  
Sent By csiegber Date 2004-01-08 Time 16:47 Rev Time 0.00
Received By csiegber Date 2004-01-08 Time 16:47 Sent To  
Notes
2004-01-08 00:00:00TO DON NEELY

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-01-06 Cont ID  
Sent By csiegber Date 2004-01-06 Time 13:45 Rev Time 0.00
Received By csiegber Date 2004-01-06 Time 13:45 Sent To  
Notes
2004-01-06 00:00:00TO DON NEELY'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-12-12 Cont ID  
Sent By csiegber Date 2003-12-12 Time 14:26 Rev Time 0.00
Received By csiegber Date 2003-12-12 Time 14:26 Sent To B
Notes
2003-12-12 00:00:00TO HP DESK/4 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-12-12 Cont ID  
Sent By csiegber Date 2003-12-12 Time 14:13 Rev Time 0.00
Received By csiegber Date 2003-12-12 Time 14:13 Sent To FIRE
Notes
2003-12-12 00:00:00SUBMITTAL/SHOP DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-09 Cont ID  
Sent By csiegber Date 2003-12-09 Time 10:56 Rev Time 0.00
Received By csiegber Date 2003-12-09 Time 10:56 Sent To B
Notes
2003-12-09 00:00:00TO HP DESK/SUBMITTALS/21 MISC SHOP
 DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-10 Cont ID  
Sent By csiegber Date 2004-05-05 Time 14:17 Rev Time 0.00
Received By csiegber Date 2003-11-10 Time 16:25 Sent To  
Notes
2003-11-10 00:00:00TO COMM BD#41

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-05 Cont ID  
Sent By shernand Date 2003-06-05 Time 10:29 Rev Time 0.00
Received By shernand Date 2003-06-05 Time 10:29 Sent To  
Notes
2003-06-05 00:00:00COMM BOARD #39

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 10:08 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 10:08 Sent To  
Notes
2003-04-11 00:00:00COMM BOARD #43

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2004-05-11 Cont ID  
Sent By pkrauss Date 2004-05-11 Time 07:17 Rev Time 0.40
Received By pkrauss Date 2004-05-11 Time 07:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2004-04-24 Cont ID  
Sent By pkrauss Date 2004-04-24 Time 08:24 Rev Time 0.40
Received By pkrauss Date 2004-04-24 Time 08:00 Sent To  
Notes
2004-04-24 00:00:00DENIED:
 PLAN SHEETS AP-M15.01 & M15.03, REMOVAL
 OF LOUVERED DOOR.PLEASE INDICATE HOW
 THIS COMPLIES WITH 2001 FBC(M) 502.1,
 THE TOTAL OUTDOOR MAKE-UP AIR SHALL BE
 EQUAL TO THAT REMOVED.
  
 AUXILIARY DRAIN PAN REQUIRED PER 2001
 FBC(M) 307.2.3 & 307.2.4.
  
 OTHER PLAN SHEETS ARE APPROVED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2004-02-19 Cont ID  
Sent By pkrauss Date 2004-02-19 Time 10:49 Rev Time 0.45
Received By pkrauss Date 2004-02-19 Time 10:49 Sent To  
Notes
2004-02-19 00:00:00DENIED:
 PLANS INDICATE THE REMOVAL OF THE
 OUTSIDE AIR DUCT.PER 2001 FBC(M)
 403.3, THE ONLY BUILDINGS EXEMPT FROM
 THE OUTSIDE AIR REQUIREMENTS ARE ONE
 AND TWO FAMILY DWELLINGS.THIS PROJECT
 IS MULTI-FAMILY THEREFOR OUTSIDE AIR IS
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-01-28 Cont ID  
Sent By hmoser Date 2004-01-28 Time 19:07 Rev Time 0.50
Received By hmoser Date 2004-01-28 Time 19:06 Sent To  
Notes
2004-01-28 00:00:00SUBMITTALS OK

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-09-10 Cont ID  
Sent By csiegber Date 2004-01-20 Time 15:46 Rev Time 1.50
Received By hmoser Date 2003-09-10 Time 15:01 Sent To  
Notes
2003-09-10 00:00:00PASS/PRIVISO
 1) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN PANS
 2) 4IN.CLEARANCE AROUND AIRHANDLERS
 3) NEED PROGRAMMABLE THERMOSTAT FOR
 FINAL INSPECTION
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-06-24 Cont ID  
Sent By pkrauss Date 2003-06-24 Time 10:29 Rev Time 0.45
Received By pkrauss Date 2003-06-24 Time 10:29 Sent To  
Notes
2003-06-24 00:00:00DENIED:BUILDING TYPE I
  
 PLAN SHEET M15.01, INDICATES EXHAUST
 FROM ELEC METER RM HAS A FIRE DAMPER AT
 THE OUTSIDE WALL.THE WALL SEPARATING
 THE ELEC METER RM AND UNIT B2 HAS A FIRE
 RESISTANCE RATING OF 1 HR.A FIRE
 DAMPER IS REQUIRED AT THE PENETRATION
 BETWEEN THE ELEC METER RM & UNIT B2.
  
 PLEASE CLARIFY VENTILATION REQUIREMENTS
 FOR THE CORRIDORS AS PER 2001 FBC(M)
 TABLE 403.3, PUBLIC SPACES - CORRIDORS
 .05 CFM PER SQ FT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-05-05 Cont ID  
Sent By pkrauss Date 2003-05-05 Time 12:35 Rev Time 4.00
Received By pkrauss Date 2003-05-05 Time 11:17 Sent To  
Notes
2003-05-05 00:00:00DENIED:
 APPARTMENTS
  
 1.PLANS SHEET A15.01 ELEC METER RM,
 AS PER 2001 FBC(M) 401.5.2, EXHAUST
 OPENINGS SHALL BE LOCATED AS NOT TO
 CREATE A NUISANCE.EXHAUST AIR SHALL
 NOT BE DIRECTED ONTO WALKWAYS.
  
 2.PLEASE INDICATE THE USE OF THE ROOMS
 WHERE AHU-EL IS LOCATED.
  
 3.CLARIFY EXTERIOR WALL - PLAN SHEET
 M15.03, INDICATES AN EXHAUST TERMINATION
 WITH A FIRE DAMPER.PLAN SHEET A1.04
 EXTERIOR WALL W1 INDICATES 1 HR, NO FIRE
 DAMPERS INDICATED ON O.A. INTAKES.
  
 4.PLAN SHEET M15.06 DETAIL OF THE
 CONDENSATE TRAP CLARIFY VENT CAP IN OPEN
 PLENUM.
  
 5.PROVIDE OUTSIDE AIR CALCS AS PER
 2001 FBC(M) TABLE 403.3
  
 CLUBHOUSE:
 1.PLAN SHEET CH M15.01 DRYER EXHAUST
 PENETRATING RATED WALL AT FIRE PUMP RM,
 THE IS NOT ACCEPTABLE.FIRE DAMPERS
 CANNOT BE INSTALLED IN DRYER DUCT DUE
 TO LINT BUILD-UP.
  
 2.INDICATE WHAT TYPE OF DRYERS ARE TO
 BE INSTALLED IN THE PUBLIC LAUNDRY ROOM.
 (COMMERCIAL?)
  
 3.PLEASE NOTE, SHOULD DRYERS IN THE
 LAUNDRY ROOM EXHAUST GREATER THAN
 2,000 CFM, AIR MAKE UP IS REQUIRED.
  
 4.PROVIDE OUTSIDE AIR CALCS AS PER
 TABLE 403.3.
  
 5.PLEASE CLARIFY THE MOP SINK IN THE
 AHU CLOSET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 12 Status F Date 2004-12-23 Cont ID  
Sent By kstevens Date 2004-12-23 Time 04:21 Rev Time 0.50
Received By kstevens Date 2004-12-23 Time 04:21 Sent To  
Notes
2004-12-23 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER AS WELL AS
 THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 11 Status P Date 2004-09-22 Cont ID  
Sent By kstevens Date 2004-09-22 Time 10:36 Rev Time 0.50
Received By kstevens Date 2004-09-22 Time 10:36 Sent To  
Notes
2004-09-22 00:00:00REVISION OK - NEW EMERGENCY PAN DRAIN
 DETAIL FOR W/HEATER

Review Stop P PLUMBING
Rev No 10 Status P Date 2004-06-18 Cont ID  
Sent By kstevens Date 2004-06-18 Time 09:00 Rev Time 0.50
Received By kstevens Date 2004-06-18 Time 09:00 Sent To  
Notes
2004-06-18 00:00:00REVISION OK - SHTS AP P14.05 & AP P14.07
 CHANGED PIPING TO 1/2" TO BATHROOMS KS

Review Stop P PLUMBING
Rev No 9 Status F Date 2004-06-12 Cont ID  
Sent By kstevens Date 2004-06-12 Time 08:01 Rev Time 1.00
Received By kstevens Date 2004-06-12 Time 08:01 Sent To  
Notes
2004-06-12 00:00:00REVISION DENIED
  
 1) IRRIGATION PLANS WERE NOT PART OF THE
 ORIGINAL PLANS. SEPARATE PERMIT REQUIRED
 FOR IRRIGATION. SUBMIT PLANS WITH PERMIT
 APPLICATION. WATER USE PERMIT REQUIRED
 FROM SOUTH FLORIDA WATER MANAGEMENT DIS-
 TRICT PRIOR TO SUBMITTING FOR PERMIT
 WITH CITY WPB.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 8 Status P Date 2004-04-29 Cont ID  
Sent By kstevens Date 2004-04-29 Time 13:08 Rev Time 1.25
Received By kstevens Date 2004-04-29 Time 13:07 Sent To  
Notes
2004-04-29 00:00:00REVISION OK - SHTS P14.01 THRU P14.08
 W/.06A & .06B

Review Stop P PLUMBING
Rev No 7 Status P Date 2004-02-09 Cont ID  
Sent By jleech Date 2004-02-09 Time 10:45 Rev Time 1.50
Received By jleech Date 2004-02-09 Time 10:44 Sent To  
Notes
2004-02-09 00:00:00MATERIAL SUBMITALS PLUMBING OK

Review Stop P PLUMBING
Rev No 6 Status P Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-02-06 Time 11:57 Rev Time 0.50
Received By jleech Date 2004-02-09 Time 09:06 Sent To  
Notes
2004-02-09 00:00:00SUBMITAL DEMESTIC PUMPS ONLY OK

Review Stop P PLUMBING
Rev No 5 Status F Date 2004-02-05 Cont ID  
Sent By kstevens Date 2004-02-05 Time 13:40 Rev Time 1.00
Received By kstevens Date 2004-02-03 Time 18:38 Sent To  
Notes
2004-02-05 00:00:00REVISIONDENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHTS AP/P14.01 & AP/P14.03 CLEANOUTS
 REQUIRED PER SECTIONS 708.3.1 & 708.3.3.
 2) SHT AP/P14.06 CLEANOUTS REQUIRED PER
 SECTION 708.3.1 & 708.3.3.
 3) SHT AP/P14.08 DETAIL #3 SHOWS THE
 DRAIN LINE FOR THE EMERGENCY SAFETY PAN
 FOR THE WATER HEATER DELETED, AND THE
 RELIEF LINE, (T&P), DRAINING OUTSIDE.
 DETAIL #2 SHOWS T&P LINE DISCHARGING IN-
 TO THE SAFETY PAN FOR THE WATER HEATER.
 PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-12-09 Cont ID  
Sent By kstevens Date 2003-12-09 Time 12:49 Rev Time 0.50
Received By kstevens Date 2003-12-09 Time 12:49 Sent To  
Notes
2003-12-09 00:00:00REVISION OK - SHTS AP/P14.01, AP/P14.02,
 AP/P14.03, AP/P14.07, AP/P14.08

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-09-04 Cont ID  
Sent By kstevens Date 2003-09-04 Time 15:48 Rev Time 2.00
Received By kstevens Date 2003-09-04 Time 15:47 Sent To  
Notes
2003-09-04 00:00:00PASSED/PROVISO
  
 BACKFLOW REQUIRED FOR TRASH CHUTE WASH

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-06-24 Cont ID  
Sent By kstevens Date 2003-06-24 Time 09:33 Rev Time 1.00
Received By kstevens Date 2003-06-24 Time 08:32 Sent To  
Notes
2003-06-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) FROM PREVIOUS REVIEW. CLEANOUTS RE-
 QUIRED IN BOTH BREEZWAYS, (STAIRWAYS),
 SHTS P14.01 & P14.03. CLEANOUTS SHALL BE
 FLOOR CLEANOUTS AS THEY ARE REQUIRED TO
 BE TWO WAY CLEANOUTS, OR MORE CLEANOUTS
 WILL BE REQUIRED AT THE UPSTREAM END OF
 THE BLDG DRAIN. 708.5. CLEANOUTS ARE
 REQUIRED TO BE ACCESSIBLE SO THEY SHALL
 BE LOCATED OUTSIDE OF THE UNITS. 708.10
 2) SHT P14.07 WATER RISER DIAGRAMS. IF
 WATER HAMMER ARRESTORS ARE INSTALLED AT
 THE WATER HEATERS THEY SHALL BE LOCATED
 AS REQUIRED FOR ALL OTHER WATER HAMMER
 ARRESTORS. PDI-WH 201 & MANUF. INSTALL.
 INSTRUCTIONS.
 3) SUBMIT A HORIZONTAL SANITARY RISER
 DIAGRAM. SHOW ALL RISER TIE-INS AND
 SHOW DRAINAGE FIXTURE UNITS AS THEY
 ACCUMULATE IN THE SYSTEM. 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-30 Cont ID  
Sent By kstevens Date 2003-04-30 Time 10:40 Rev Time 3.00
Received By kstevens Date 2003-04-30 Time 08:25 Sent To  
Notes
2003-04-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-AMEND 98 DESIGN MANUAL
  
 1) SHTS A5.05 & A5.06 LAVS SHALL BE 34"
 MAX FROM FLOOR TO FLOOD RIM LEVEL. SEE
 DETAIL PAGE 7.52 DESIGN MANUAL.
 2) ALL UNITS - PLEASE SPECIFY EITHER
 SPECIFICATION "A" OR "B" BATHROOMS AS
 REQUIRED BY DESIGN MANUAL REQUIREMENT
 7B PAGE 7.35
 3) SEPARATE PERMIT REQUIRED FOR IRRIGA-
 TION.
 4) SHT P14.01 CLEANOUTS REQUIRED IN BOTH
 BREEZEWAYS. SECTION 708.3.1 (MAX. 100')
 5) SHT P14.06 RISERS S4 & S5, THE WASTE
 STACH SHALL BE THE SAME SIZE THROUTHOUT
 THE LENGTH OF THE WASTE STACK. SECTION
 910.4.
 6) SHT P14.07 WATER RISER DIAGRAMS, THE
 WATER HAMMER ARRESTORS REQUIRED IN SECT.
 604.9, (ICE MAKER, DISHWASHER. WASH
 MACHINE), SHALL BE LOCATED NEAR THE FIX-
 TURES IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS.
 7) RPZ BACKFLOW REQUIRED FOR WATER
 SERVICE AT EACH BLDG.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 3 Status P Date 2004-06-08 Cont ID  
Sent By mmclean Date 2004-06-08 Time 16:33 Rev Time 0.00
Received By mmclean Date 2004-06-08 Time 16:33 Sent To I
Notes
2004-06-08 00:00:00REVISION APPROVED

Review Stop Z ZONING
Rev No 2 Status P Date 2003-09-12 Cont ID  
Sent By mmclean Date 2003-09-12 Time 11:16 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-09-12 00:00:009/12/03 OK PER GRACE MM

Review Stop Z ZONING
Rev No 1 Status N Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-14 Time 08:50 Rev Time 0.00
Received By shernand Date 2003-05-14 Time 08:50 Sent To  
Notes
2003-05-14 00:00:00PROVIDE SITE PLAN FOR ZONING APPROVAL.